Chapter 5 Function parameter
35
P9-58
Motor overheat pre-
alarm threshold
0
℃~
200
℃
90
℃
〇
P9-59
Instantaneous power
failure action selection
0
:
Invalid
1: deceleration
2: Deceleration stop
0
〇
P9-60
Instantaneous stop
action pause judgment
voltage
80.0
~
100.0%
90.0%
〇
P9-61
Instantaneous power
failure voltage rise
judgment time
0.00s
~
100.00s
0.50s
〇
P9-62
Instantaneous power
failure action judgment
voltage
60.0%
~
100.0%
(
Standard bus voltage
)
80.0%
〇
P9-63
Drop protection option
0
:
Invalid
1
:
Valid
0
〇
P9-64
Drop detection level
0.0
~
100.0
%
10.0%
〇
P9-65
Drop detection time
0.0
~
60.0s
1.0s
〇
P9-67
Overspeed detection
value
0.0
%~
50.0
%(
Maximum frequency
)
20.0%
〇
P9-68
Overspeed detection
time
0.0s
~
60.0s
5.0s
〇
P9-69
Speed deviation
excessive detection
value
0.0
%~
50.0
%(
Maximum frequency
)
20.0%
〇
P9-70
Speed deviation too
large detection time
0.0s
~
60.0s
5.0s
〇
P9-71
Instantaneous stop
non-stop gain Kp
0~100
40
〇
P9-72
Instantaneous stop
non-stop integral
coefficient Ki
0~100
30
〇
P9-73
Instantaneous stop and
stop motion
deceleration time
0~300.0s
20.0s
●
PA Group PID function
function
code
Parameter Name
Setting Range
Default Prop
erty
PA-00
PID given source
0
:
PA-01 set
1
:
AI1
2
:
AI2
3: AI3 (panel potentiometer)
4: Pulse setting
5: Communication given
6: Multi-speed given
0
〇
PA-01
PID value given
0.0%
~
100.0%
50.0%
〇