Chapter 6 ,P9 Failure and protection
P8-34
Zero current detection level 0.0%~300.0% 100.0% corresponds to
the rated current of the motor
Default
:
5.0%
P8-35
Zero current detection
delay time
0.01s
~
600.00s
Default
:
0.10s
When the output current of the inverter is less than or equal to the zero current detection
level and the duration exceeds the zero current detection delay time, the inverter outputs ON
signal. Figure 6-21 Schematic diagram of zero current detection.
ON
Zero current detection
levelP8-34
Output current
OFF
time
time
Zero current
detection signal
Zero current detection delay timeP8-35
Figure 6-21 Schematic diagram of zero current detection
P8-36
Output current limit
0.0% (not detected)
0.1%~300.0% motor rated
current
Default
:
200.0%
P8-37
Output current overrun
detection delay time
0.00s
~
600.00s
Default
:
0.00
When the output current of the inverter is greater than or exceeds the detection point
and the duration exceeds the software over-current detection delay time, the inverter outputs
an ON signal. Figure 6-22 shows the output current over-limit function.