Chapter 6 A0 torque control and limit
123
PP
组
user password
PP-00
user password
0
~
65535
Default
:
0
PP-00 sets any non-zero number, then the password protection function takes effect.
The next time you enter the menu, you must enter the password correctly. Otherwise, you
cannot view and modify the function parameters. Please remember the user password you
set.
If PP-00 is set to 00000, the set user password will be cleared, and the password
protection function will be invalid.
PP-01
Parameter initialization
0
:
No operation
1: Restore Default, excluding motor
parameters
2: Clear record information
4: Backup user current parameters
501: Restore user backup parameters
without operation
1: Restore Default, excluding motor
parameters
2: Clear record information
4: Backup user current parameters
501: Restore user backup parameters
Default
:
0
1
、
Restore factory settings, excluding motor parameters:
After setting PP-01 to 1, most of the inverter's function parameters are restored to the
factory default parameters, but the motor parameters, frequency command decimal point
(P0-22), fault record information, cumulative running time (P7-09), cumulative power-on
Time (P7-13) and accumulated power consumption (P7-14) are not restored.
2. Clear the record information: clear the inverter fault record, accumulated
operation/power-on time (P7-09/P7-13), and accumulated power consumption (P7-14).
4. Backup user current parameters: Back up the current setting values of all function
parameters to facilitate the customer to recover after the parameter adjustment is
disordered.
501. Restore user backup parameters: restore the user parameters that were backed up
before, that is, restore the backup parameters by setting PP-01 to 4.
PP-02
Function parameter
group display
selection
Function parameter group display
selection
Default
:
11
PP-04
Function code
modification attribute
0
:
Can be modified 1: not modifiable
Default
:
0
Whether the user can set the function code parameter can be modified to prevent the risk
of the function parameter being mistakenly changed.
When the function code is set to 0, all function codes can be modified; when set to 1, all
function codes can only be viewed and cannot be modified.
A0-00
Speed/torque control
selection
0
:
Speed control 1: torque control
Default
:
0
Used to select the inverter control mode: speed control or torque control.
The multi-function input terminals of the inverter are equipped with torque control
inhibition (function 29) and speed control/torque control switching (function 46).