Chapter 5 Function parameter
26
19: Undervoltage status output
20: Communication setting
23: 2 in zero speed operation (also output when
stopping)
24: Accumulated power-on time arrives
25: Frequency level detection FDT2
26: Frequency 1 reaches output
27: Frequency 2 reaches output
28: Current 1 reaches the output
29: Current 2 reaches the output
30: Timing arrives at output
31: AI1 input exceeds limit
32: Offload
33: Reverse running
34: Zero current state
35: Module temperature reached
36: Output current overrun
37: Lower limit frequency arrives (stop output
also)
38: Fault warning output (continue to run)
39: Motor overheat pre-alarm
40: This running time arrives
P5-02
Relay
output
function selection
2
〇
P5-03
Relay
output
function selection
2(Optional)
0
〇
P5-04
Y1 switch output
function selection
1
〇
P5-05
Y3 switch output
function selection
(optional)
4
〇
P5-06
Y2
Pulse
output
function selection
0: running frequency 1: setting frequency
2: Output current 3: Output torque
(absolute value)
4: Output power 5: Output voltage
6: Pulse input (100.0% corresponds to
100.0kHz)
7: AI1 8: AI2
9: AI3 (extended) 10: length
11: Record the value 12: Communication
settings
13: Motor speed
14: Output current (100.0% corresponds to
1000.0A)
15: Output voltage (100.0% corresponds
to 1000.0V)
0
〇
P5-07
AO Output function
selection
0
〇
P5-08
AO2 Output function
selection (optional)
1
〇
P5-09
Y2
Pulse
output
Maximum frequency
0.01kHz
~
100.00kHz
50.00kHz
〇
P5-10
AO
Zero
offset
coefficient
-100.0%
~
+100.0%
0.0%
〇
P5-11
AO Gain
-10.00
~
+10.00
1.00
〇
P5-12
Extended AO2 zero
bias coefficient
-100.0%
~
+100.0%
0.0%
〇