90
Chapter 6 start and stop control
P7group Keyboard and display
P7-01
JOG/REV
key
function selection
0: F/R key is invalid
1: Keyboard command and terminal
(communication) command switching
2: Forward and reverse switching 3:
Forward rotation
4: Reverse jog
Default
:
0
JOG/REV The key is a multi-function key, and the function of the JOG/REV key can
be set by this function code. This button can be used to switch between stop and run.
0: This button has no function.
1: Keyboard command and remote operation switch. Refers to the switching of the
command source, that is, the current command source and keyboard control (local
operation) switching. If the current command source is keyboard control, this key
function is invalid.
2: Forward/reverse switching the direction of the frequency command is switched
by the JOG/REV button. This function is only available when the command source is
the operator panel command channel.
3: Forward jog through the keyboard JOG / REV button to achieve forward rotation
4: Reverse jog through the keyboard JOG/REV button to achieve reverse jog
P7-02
STOP/RESETkey
Function
selection
0
:
Only the keyboard command is valid under the
keyboard command
1: In any case, the key stop is valid
Default
:
1
P6-21
Demagnetization time
0.0~5.0s
Default
:
depending
The demagnetization time is the minimum interval between stop and start. This function
code will only take effect after the speed tracking function is turned on. If the setting value is too
small, it will cause overvoltage fault.