Chapter 6 A5 control optimization
consistent with the expected set value. Take AI1 as an example. The field calibration method is
as follows:
Given AI1 voltage signal (about 2V)
Actual measurement of AI1 voltage value, stored in function parameter AC-00 View U0-21
display value, stored in function parameter AC-01;
Given AI1 voltage signal (about 8V)
Actual measurement of AI1 voltage value, stored in function parameters AC-02
View U0-21 display value, save function parameters AC-03
When AI2 and AI3 are corrected, the actual sampling voltage viewing positions are U0-22 and
U0-23 respectively.
For AI1 and AI2, it is recommended to use 2V and 8V as the calibration point pair AI3. It is
recommended to sample -8V and 8V as the correction point.
AC-12
AO1 target voltage 1
0.500V
~
4.000V
factory reset
AC-13
AO1 measured voltage
1
0.500V
~
4.000V
factory reset
AC-14
AO1 target voltage 2
6.000V
~
9.999V
factory reset
AC-15
AO1 measured voltage
2
6.000V
~
9.999V
factory reset
AC-16
AO2 target voltage 1
0.500V
~
4.000V
factory reset
AC-17
AO2 measured voltage
1
0.500V
~
4.000V
factory reset
AC-18
AO2 target voltage 2
6.000V
~
9.999V
factory reset
AC-19
AO2 measured voltage
2
6.000V
~
9.999V
factory reset
AC-20
AI2 measured current 1 0.000mA
~
20.000mA
factory reset
AC-21
AI2 sampling current 1
0.000mA
~
20.000mA
factory reset
AC-22
AI2 measured current 2 0.000mA
~
20.000mA
factory reset
AC-23
AI2 sampling current 2
0.000mA
~
20.000mA
factory reset
AC-24
AO1 ideal current 1
0.000mA
~
20.000mA
factory reset
AC-25
AO1 measured current 1 0.000mA
~
20.000mA
factory reset