Chapter 6 P5 output terminal
15
Ready to run
When the inverter is stable after power-on, and the inverter
does not detect any fault information, the inverter will output an
ON signal when it is in the operable state.
16
AI1>AI2
When the value of the input AI1 is greater than the input value
of AI2, an ON signal is output.
17
Upper limit
frequency arrival
When the running frequency reaches the upper limit frequency,
an ON signal is output.
18
The lower limit
frequency arrives
(no output when
stopped)
When the running frequency reaches the lower limit frequency,
the ON signal is output.
This signal is OFF in the stop state.
19
Undervoltage status
output
When the inverter is under voltage, it outputs ON signal.
20
Communication
setting
Please refer to the communication protocol.
23
2 at zero speed
(also output when
stopped)
When the inverter output frequency is 0, the ON signal is output.
This signal is also ON in the stop state.
24
Cumulative power-
on time arrives
The inverter's accumulated power-on time P7-13 exceeds the
P8-16 set time output ON signal.
25
Frequency level
detection FDT2
output
Please refer to the description of function codes P8-28 and P8-
29.
26
Frequency 1
reaches the output
Please refer to the description of function codes P8-30 and P8-
31.
27
Frequency 2
reaches the output
Please refer to the description of function codes P8-32 and P8-
33.
28
Current 1 reaches
the output
Please refer to the description of function code P8-38, P8-39.
29
Current 2 reaches
the output
Please refer to the description of function codes P8-40 and P8-
41.
30
Timing arrival output When the timing function (P8-42) is valid, the inverter will output
the ON signal after the current running time reaches the set
timing time.