Chapter 6 P4 input terminal
P4-39
Input terminal valid
mode selection 2
Unit’s digit
:
X5
Ten’s digit
:
X7
Hundred’s digit
:
X8
Thousand’s digit
:
X9
0: The X terminal is connected to COM and the
disconnection is invalid.
1: X terminal and COM connection are invalid,
the disconnection is valid.
Default
:
00000
Used to set the active status mode of the digital input terminal.
0: Positive logic, the corresponding terminal is valid when connected to COM, and the
disconnection is invalid.
1: Inverse logic, the corresponding terminal is invalid when connected to COM, and the
disconnection is valid.
P5 Group Output terminal
The inverter comes standard with one multi-function analog output terminal, one multi-
function digital output terminal, one multi-function relay output terminal, and one FM terminal
(optional as a high-speed pulse output terminal, or as a collector open circuit) Switch output).
If the above output terminal does not meet the field application, you need to select the multi-
function input and output expansion card.
。
P5-00
Y2 output mode
selection
0: Pulse output 1: Switch output
Default
:
0
The Y2 terminal is a programmable multiplexing terminal that can be used as a high-
speed pulse output terminal or as an open collector output terminal. As a pulse output, the
maximum frequency of the pulse is 100 kHz, see P5-06
。
P5-01
Y2 switching output function
selection
Default: 0 has no function
P5-02
Relay output function selection
Default: 2 fault output
P5-03
Relay output 2 selection
(extended)
Default: 0 has no function
P5-04
Y1 switch output function
selection
Default: 1 inverter running signal output
P5-05
Y3 switching output selection
(extended)
Default: 4 frequency arrival signal output
The above function code is used to select the function of 5 digital outputs. The function
of the multi-function output terminal is as follows
:
Setting
value
Function
Instructions