Chapter 6 PA Process control PID
PID parameter1
PA-05
、
PA-06
、
PA-07
PI
parameter
PID parameter 2
PA-15
、
PA-16
、
PA-17
PA-19
PA-20
PID deviation
Figure 6-26 PID parameter switching
PA-21
PID initial value
0.0%
~
100.0%
Default
:
0.0%
PA-22
PID initial value hold
time
0.00
~
650.00s
Default
:
0.00s
When the inverter starts, the PID output is fixed to the PID initial value PA-21. After the
PID initial value hold time PA-22, the PID starts the closed-loop adjustment operation. Figure
6-27 shows the function of the PID initial value.
PIDInitial value
PA-21
Output frequeny
time
PIDInitial value retention timePA-22
Figure 6-27 Schematic diagram of PID initial value function
This function is used to limit the difference between PID output two beats (2ms/beat),
so as to suppress the PID output from changing too fast, and the inverter operation tends
to be stable.
PA-25
PID integral attribute
Unit’s digit
:
Integral separation 0: Invalid
1: Valid
Ten’s digit: Whether to stop the integration
after outputting the limit
0: Continue to integrate 1: Stop the
points
Default
:
00
Integral separation: