Software • Upgrade information
230
Panel PC 800 User's Manual V1.30
2.6 Return to main menu
Returns to the main menu
Item 3:
Opens Submenu 3 for upgrading the add-on UPS firmware and battery settings
3.1 Upgrade add-on UPS firmware (5AC600.UPSI-00)
Updates the firmware for the add-on UPS
3.2 Upgrade battery settings (5AC600.UPSB-00)
Automatically updates the battery settings for 5AC600.UPSB-00
3.3 Return to main menu
Returns to the main menu
Item 4:
Returns to the shell (MS-DOS)
•
The system must be rebooted after a successful upgrade.
2.2.2 Possible upgrade problems and software dependencies (for V1.02)
•
The SDLR firmware can only be updated if an Automation Panel with Automation Panel Link transceiver
(5DLSDL.1000-01) and Automation Panel Link receiver (5DLSDL.1000-00) is connected.
•
Automation Panel Link transceivers (5DLSDL.1000-01) or Automation Panel Link receivers
(5DLSDL.1000-00) with a firmware version less than or equal to V00.10 can no longer be com-
bined with Automation Panel Link transceivers (5DLSDL.1000-01) or Automation Panel Link receivers
(5DLSDL.1000-00) with a firmware version greater than or equal to V01.04. Daisy chain mode is not pos-
sible with this type of a combination.
•
If a UPS (e.g. 5AC600.UPSI-00) + battery unit (e.g. 5AC600.UPSB-00) is connected to the system and
ready to be operated, then either the battery must be disconnected or the Power button pushed after
upgrading the MTCX or SDLT (to put the system in standby mode) before powering the system off and
back on. If this is not done, the firmware upgrade will not work since the UPS is buffering the system.