11.2 Measurement Subsystem
This subsystem programs the measurement capability of the power supply.
Subsystem Syntax
MEASure
:CURRent?
[:LEVel]
Returns
the
average
DC
value
of
current
:AMPLitude
:MAX?
Returns
peak
current
measurement
reading
:RESet
Resets
the
peak
current
measurements
:POWer
Returns
the
DC
power
measurement
reading.
:VOLTage?
Returns the DC voltage measurement reading
MEASure:CURRent[:LEVel]?
This query returns the DC value of the DC current being sourced at the output terminals. Note that
the output must be on to obtain current flow.
Query Syntax
MEASure:CURRent?
Parameters None
Examples MEAS:CURR?
Returned Parameters
<NR2>
Related Commands
OUTP 0
⎜
1
MEAS:CURR:AMPL:MAX?
MEASure:CURRent:AMPLitude:MAX?
This query returns the peak current value of the output current being sourced at the output terminals.
Note that the output must be ON to obtain current flow. The peak current measurement circuit uses a
sample and hold method and latches the highest peak current value found since the last peak
measurement reset command.
Query Syntax
MEASure:CURRent:AMPLitude:MAX?
Parameters None
Examples MEAS:CURR:AMPL:MAX?
Returned Parameters
<NR2>
Related Commands
OUTP 0
⎜
1
MEAS:CURR?
MEASure:CURRent:AMPLitdue:RESet
This command resets the peak current measurement sample and hold circuit to zero.
Query Syntax
MEASure:CURRent:AMPLitude:RESet
Parameters None
Examples MEAS:CURR:AMPL:RES
Related Commands
MEAS:CURR:AMPL:MAX?
Содержание XDS 100-100
Страница 4: ...User and Programming Manual 4 XDS Series Electrical Safety Symbols Used in This Manual ...
Страница 27: ...User and Programming Manual XDS Series 27 Figure 3 5 Outline Drawing XDS DC Supply ...
Страница 41: ...User and Programming Manual XDS Series 41 Figure 5 4 Parallel Cable Interconnect Accessory ...
Страница 45: ...User and Programming Manual XDS Series 45 Figure 6 1 DC Power Supply Block Diagram IF option shown ...
Страница 69: ...User and Programming Manual XDS Series 69 Figure 8 3 Replaceable Fuse Locations ...