User and Programming Manual
38 XDS
Series
5.2 Changing
Configurations
Factory configured models are pre-configured and calibrated for their indicated mode of
operation. If a unit has to be redeployed for a different application than originally purchased for,
the XDS unit can be reconfigured in the field.
To do so requires removal of the top cover. This voids the warranty seal and Argantix should be
notified to ensure your warranty period remains in effect. Contact
to
obtain authorization to reconfigure a unit.
All configuration changes are made through a series of jumper of the 5005-720-1 Controller
assembly. This assembly is located directly behind the front panel. The jumpers are on the far
side of the controller assembly and can be accessed without removing the controller from the
XDS chassis.
The figure below shows the located on the controller assembly and jumpers when facing the front
of the unit. Note that the top cover has been pushed back about 4 inches.
Figure 5-1: XDS Configuration Jumper Locations
Available configuration settings are shown in the table below.
Configuration
W1
W2
W5
W6
W9
W10
W11
W12
W13
W14
W15
W16
Master
1 0 1 0 0 1 0 1 0 0 0 1
Auxiliary
(-AUX) 1 0 1 0 1 0 0 0 1 1 0 1
Master,
-RPV
0 1 1 0 0 1 0 1 0 0 0 1
Master,
-RPC
1 0 0 1 0 1 1 1 0 0 0 1
Table 5-2: Configuration Jumper Settings - Mode
Note: W15 and W16 jumpers settings shown apply to 10 and 15 KW Chassis. For 5 KW models,
remove W16.
Содержание XDS 100-100
Страница 4: ...User and Programming Manual 4 XDS Series Electrical Safety Symbols Used in This Manual ...
Страница 27: ...User and Programming Manual XDS Series 27 Figure 3 5 Outline Drawing XDS DC Supply ...
Страница 41: ...User and Programming Manual XDS Series 41 Figure 5 4 Parallel Cable Interconnect Accessory ...
Страница 45: ...User and Programming Manual XDS Series 45 Figure 6 1 DC Power Supply Block Diagram IF option shown ...
Страница 69: ...User and Programming Manual XDS Series 69 Figure 8 3 Replaceable Fuse Locations ...