Chapter 5: Installing the Chassis in an Equipment Rack
122
Section II: Installing the Chassis
3. Insert one end of the grounding wire into the grounding lug, as shown
in Figure 48, and use a crimping tool to secure the wire to the
grounding lug.
Figure 48. Attaching the Grounding Wire to the Grounding Lug
4. Install the grounding lug on the rear panel of the chassis, as shown in
Allied Telesis recommends tightening the screws to 20 inch-lbs.
Figure 49. Installing the Grounding Lug and Wire
5. Connect the other end of the grounding wire to the building protective
earth.
6. Go to Chapter 6, “Installing the Power Supplies” on page 123.