6.3 Switching the Control On/Off
407
6.3.4 Programming station mode
You can switch the control into programming-station mode with
MP_simMode
. The control can then be used as a programming station. No
drives are enabled. You can create and test the PLC program and NC pro-
grams. The operation of the machine is simulated in the programming station
mode. As OEM, you have access to the machine configuration in the program-
ming station mode. This way the control can be adapted to the machine before
actual commissioning, for example, or be used for training purposes
The
MP_simMode
parameter offers three different setting possibilities for the
programming station mode:
With
FullOperation
the control starts in normal operation. The programming
station mode is deactivated. All drives and the PLC are active.
Choose the
CcOnly
setting in order to simulate the CC controller unit while
the PLC is active. In this case all PLC inputs and outputs, as well as the emer-
gency-stop loop (X41/34 and X42/4), must already be connected correctly in
order to switch the control on correctly.
Choose
CcAndExt
in order to simulate the CC controller unit and all PLC
inputs and outputs. The PLC runs in simulation mode, and the emergency-stop
loop and PLC inputs and outputs are not interrogated.
The control must be restarted after changes in
MP_simMode
in order for the
new settings to become active.
MP_simMode
Defines the programming station mode
Format:
Selection menu
Selection:
FullOperation
Programming station mode is switched off, the emergency-
stop loop (X41/34 and X52/4) must be complete. The drives are
moved.
CcOnly
Simulation of the controlled drives. All PLC inputs and outputs,
as well as the emergency-stop loop, must be connected cor-
rectly in order to switch the control on correctly.
CcAndExt
Simulation of the controlled drives and all PLC inputs and out-
puts. The emergency-stop loop dos not need to be complete.
The PLC runs in simulation mode.
Default:
FullOperation
Access:
LEVEL 3
Reaction:
RESET
Settings in the configuration editor:
System
CfgMachineSimul
simMode
skipReferencing
skipEmStopTest
Содержание MILLPWR G2
Страница 1: ...Technical Manual ACU RITE MILLPWRG2 ...
Страница 2: ......
Страница 14: ...14 ACU RITE Technical Manual MILLPWRG2 ...
Страница 40: ...40 ACU RITE Technical Manual MILLPWRG2 ...
Страница 56: ...56 ACU RITE Technical Manual MILLPWRG2 3 10 Dimensions 3 10 1 MILLPWRG2 Weight 8 0 kg Dim Inch mm ...
Страница 58: ...58 ACU RITE Technical Manual MILLPWRG2 3 10 3 USB Hub ...
Страница 60: ...60 ACU RITE Technical Manual MILLPWRG2 TS 220 Adapter cable for TS 120 TS 220 ...
Страница 61: ...3 10 Dimensions 61 SE 640 transmitter receiver unit ...
Страница 62: ...62 ACU RITE Technical Manual MILLPWRG2 SE 540 transmitter receiver unit ...
Страница 63: ...3 10 Dimensions 63 TS 440 TS 640 ...
Страница 64: ...64 ACU RITE Technical Manual MILLPWRG2 ...
Страница 392: ...392 ACU RITE Technical Manual MILLPWRG2 ...
Страница 545: ......