disconnector or breaker truck and earth-switch position status, status of the trip logics,
gas pressure alarm and circuit-breaker spring charging status.
The
OKPOS
output from DCSXSWI defines whether the disconnector or breaker
truck is either open (in test position) or close (in service position). This output,
together with the open earth-switch and non-active trip signals, activates the close-
enable signal to the circuit breaker control function block. The open operation for
circuit breaker is always enabled.
The
SYNC_ITL_BYP
input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position.
SYNC_ITL_BYP
overrides, for example, active interlocking conditions when the
circuit breaker truck is closed in service position.
CBXCBR1
POSOPEN
POSCLOSE
ENA_OPEN
ENA_CLOSE
BLK_OPEN
BLK_CLOSE
AU_OPEN
AU_CLOSE
TRIP
SYNC_OK
SYNC_ITL_BYP
SELECTED
EXE_OP
EXE_CL
OP_REQ
CL_REQ
OPENPOS
CLOSEPOS
OKPOS
OPEN_ENAD
CLOSE_ENAD
TRUE
X120_BI3_CB_OPENED
X120_BI2_CB_CLOSED
CBXCBR1_ENA_CLOSE
CBXCBR1_EXE_CL
CBXCBR1_EXE_OP
FALSE
CBXCBR1_AU_OPEN
CBXCBR1_AU_CLOSE
CBXCBR1_SELECTED
GUID-54C9EDF5-8EE3-4C65-85A8-D098A2EC7326 V2 EN
Figure 79:
Circuit-breaker control logic: Circuit breaker 1
Connect the additional signals required for the application for closing
and opening of circuit breaker.
OR
B1
B2
O
CB_CLOSE_COMMAND
CBXCBR1_EXE_CL
DARREC1_CLOSE_CB
GUID-CBE9421A-1896-448B-903A-86C63FAC47E9 V1 EN
Figure 80:
Circuit-breaker control logic: Signals for closing coil of circuit breaker
OR6
B1
B2
B3
B4
B5
B6
O
CB_OPEN_COMMAND
CBXCBR1_EXE_OP
TRPPTRC1_TRIP
DARREC1_OPEN_CB
GUID-E3C59277-527E-48D1-9815-0E1416827C6F V1 EN
Figure 81:
Circuit-breaker control logic: Signals for opening coil of circuit
breaker
Section 3
1MRS756378 S
REF615 standard configurations
90
REF615
Application Manual
Содержание relion REF615
Страница 1: ...Relion 615 series Feeder Protection and Control REF615 Application Manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 398: ...392 ...
Страница 402: ...396 ...
Страница 403: ...397 ...