![ABB relion REF615 Скачать руководство пользователя страница 115](http://html.mh-extra.com/html/abb/relion-ref615/relion-ref615_applications-manual_2824115.webp)
TCSSCBR1
BLOCK
ALARM
TCSSCBR2
BLOCK
ALARM
OR
B1
B2
O
TCSSCBR1_ALARM
TCSSCBR1_ALARM
TCSSCBR2_ALARM
TCSSCBR2_ALARM
TCSSCBR_BLOCKING
TCSSCBR_BLOCKING
TCSSCBR_ALARM
GUID-74BD5A42-E773-4714-9EDF-97F22B96687A V1 EN
Figure 112:
Trip circuit supervision function
OR6
B1
B2
B3
B4
B5
B6
O
TRPPTRC2_TRIP
X120_BI3_CB_OPENED
TRPPTRC1_TRIP
TCSSCBR_BLOCKING
GUID-1D7B03CB-17B8-4B99-AAE9-9825BC9B0322 V1 EN
Figure 113:
Logic for trip circuit supervision function
3.5.3.4
Functional diagrams for control and interlocking
The circuit breaker closing is enabled when the
ENA_CLOSE
input is activated. The
input can be activated using the configuration logic, which is based on the status of the
trip logics. However, other signals can be connected based on the application needs.
The
SYNC_ITL_BYP
input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position.
SYNC_ITL_BYP
overrides, for example, active interlocking conditions when the
circuit breaker truck is closed in service position.
Any additional signals required by the application can be connected
for opening and closing of circuit breaker.
1MRS756378 S
Section 3
REF615 standard configurations
REF615
109
Application Manual
Содержание relion REF615