ESSXSWI1
POSOPEN
POSCLOSE
OPENPOS
CLOSEPOS
OKPOS
ESSXSWI1_OPENPOS
X110_BI8_ES1_OPENED
X110_BI7_ES1_CLOSED
GUID-EFCDB6F6-3081-4D3D-BB35-1A525173EE10 V1 EN
Figure 420:
Earth switch control logic
The circuit breaker closing is enabled when the
ENA_CLOSE
input is activated. The
input can be activated by the configuration logic, which is a combination of the
disconnector or breaker truck and earth-switch position status, status of the trip logics,
gas pressure alarm, circuit-breaker spring charging and synchronizing ok status.
The
OKPOS
output from DCSXSWI defines if the disconnector or breaker truck is
definitely either open (in test position) or close (in service position). This, together
with the open earth-switch and non-active trip signals, activates the close-enable
signal to the circuit breaker control function block. The open operation for circuit
breaker is always enabled.
The
SYNC_ITL_BYP
input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position.
SYNC_ITL_BYP
overrides, for example, active interlocking conditions when the
circuit breaker truck is closed in service position.
CBXCBR1
POSOPEN
POSCLOSE
ENA_OPEN
ENA_CLOSE
BLK_OPEN
BLK_CLOSE
AU_OPEN
AU_CLOSE
TRIP
SYNC_OK
SYNC_ITL_BYP
SELECTED
EXE_OP
EXE_CL
OP_REQ
CL_REQ
OPENPOS
CLOSEPOS
OKPOS
OPEN_ENAD
CLOSE_ENAD
TRUE
X120_BI3_CB_OPENED
X120_BI2_CB_CLOSED
CBXCBR1_ENA_CLOSE
CBXCBR1_EXE_CL
CBXCBR1_EXE_OP
CBXCBR1_BLK_CLOSE
FALSE
CBXCBR1_AU_CLOSE
CBXCBR1_AU_OPEN
CBXCBR1_SELECTED
GUID-E24C973A-67F1-48CC-811F-067BFF2CEF28 V2 EN
Figure 421:
Circuit breaker 1 control logic
OR
B1
B2
O
CB_CLOSE_COMMAND
CBXCBR1_EXE_CL
DARREC1_CLOSE_CB
GUID-58728843-DCDD-473D-86E8-487CC8B5204F V1 EN
Figure 422:
Signals for closing coil of circuit breaker 1
OR6
B1
B2
B3
B4
B5
B6
O
CB_OPEN_COMMAND
CBXCBR1_EXE_OP
TRPPTRC1_TRIP
DARREC1_OPEN_CB
GUID-2A26C519-C690-4A30-A7F2-5FF22E25DFFC V1 EN
Figure 423:
Signals for opening coil of circuit breaker 1
Section 3
1MRS756378 S
REF615 standard configurations
280
REF615
Application Manual