Table 88:
Light sensor input connectors
Terminal
Description
X13
Input Light sensor 1
X14
Input Light sensor 2
X15
Input Light sensor 3
5.1.5
RTD/mA inputs
It is possible to connect mA and RTD based measurement sensors to the IED if the
IED is provided with optional RTD0001 module in standard configurations A and B
and with AIM0003 module in standard configurations E, F, H, J and N.
Table 89:
Optional RTD/mA inputs with RTD0001 module
Terminal
Description
X130:1
mA1 (AI1), +
X130:2
mA1 (AI1), -
X130:3
mA2 (AI2), +
X130:4
mA2 (AI2), -
X130:5
RTD1 (AI3), +
X130:6
RTD1 (AI3), -
X130:7
RTD2 (AI4), +
X130:8
RTD2 (AI4), -
X130:9
RTD3 (AI5), +
X130:10
RTD3 (AI5), -
X130:11
Common
1)
X130:12
Common
2)
X130:13
RTD4 (AI6), +
X130:14
RTD4 (AI6), -
X130:15
RTD5 (AI7), +
X130:16
RTD5 (AI7), -
X130:17
RTD6 (AI8), +
X130:18
RTD6 (AI8), -
1) Common ground for RTD channels 1-3
2) Common ground for RTD channels 4-6
Table 90:
Optional RTD/mA inputs with AIM0003 module
Terminal
Description
X130:1
mA 1 (AI1), +
X130:2
mA 1 (AI1), -
X130:3
RTD1 (AI2), +
X130:4
RTD1 (AI2), -
Table continues on next page
Section 5
1MRS756378 S
IED physical connections
388
REF615
Application Manual