![ABB relion REF615 Скачать руководство пользователя страница 235](http://html.mh-extra.com/html/abb/relion-ref615/relion-ref615_applications-manual_2824235.webp)
LED
Description
7
Disturbance recorder triggered
8
Circuit breaker condition monitoring alarm
9
Supervision alarm
10
Arc fault detected
11
Autoreclose in progress
3.10.2.2
Default disturbance recorder settings
Table 49:
Default disturbance recorder analog channels
Channel
Description
1
IL1
2
IL2
3
IL3
4
Io
5
Uo
6
U1
7
U2
8
U3
9
U1B
10
-
11
-
12
-
Table 50:
Default disturbance recorder binary channels
Channel
ID text
Level trigger mode
1
PHLPTOC1 - start
Positive or Rising
2
PHHPTOC1 - start
Positive or Rising
3
PHHPTOC2 - start
Positive or Rising
4
PHIPTOC1 - start
Positive or Rising
5
NSPTOC1 - start
Positive or Rising
6
NSPTOC2 - start
Positive or Rising
7
EFLPTOC1 - start
Positive or Rising
8
EFLPTOC2 - start
Positive or Rising
9
EFHPTOC1 - start
Positive or Rising
10
EFIPTOC1 - start
Positive or Rising
11
PDNSPTOC1 - start
Positive or Rising
12
PHPTOV1 - start
Positive or Rising
13
PHPTOV2 - start
Positive or Rising
Table continues on next page
1MRS756378 S
Section 3
REF615 standard configurations
REF615
229
Application Manual