Main unit
Slot ID Content options
Case
X130
AI/BI module
Only with configurations E, F, H, J, K and N:
3 phase voltage inputs (60-210 V)
1 residual voltage input (60-210 V)
4 binary inputs
Additionally with configurations H, J, K and N:
1 reference voltage input for SECRSYN1 (60-210 V)
AI/RTD/mA module
Only with configurations E, F, H, J and N:
3 phase voltage inputs (60-210 V)
1 residual voltage input (60-210 V)
1 generic mA input
2 RTD sensor inputs
Additionally with configurations H, J and N:
1 reference voltage input for SECRSYN1 (60-210 V)
Sensor input
module
Only with configurations G and L:
3 combi sensor inputs (three-phase current and voltage)
1 residual current input (0.2/1 A)
1)
Optional BIO
module
Optional for configurations B and D:
6 binary inputs
3 SO contacts
Optional RTD/mA
module
Optional for configurations B and D:
2 generic mA inputs
6 RTD sensor inputs
X000
Optional
communication
module
See the technical manual for details about different types
of communication modules.
1) The 0.2/1 A input is normally used in applications requiring sensitive earth-fault protection and featuring
core-balance current transformers.
Rated values of the current and voltage inputs are basic setting parameters of the
protection relay. The binary input thresholds are selectable within the range 16…176
V DC by adjusting the binary input setting parameters.
The connection diagrams of different hardware modules are presented in this manual.
See the installation manual for more information about the case and
the plug-in unit.
Section 2
1MRS756378 S
REF615 overview
22
REF615
Application Manual