OR6
B1
B2
B3
B4
B5
B6
O
TPGAPC3
IN1
IN2
OUT1
OUT2
VOLTAGE_AND_FREQ_OPERATE_PULSE
PHPTOV_OPERATE
PHPTUV_OPERATE
FREQUENCY_OPERATE
GUID-59484B34-0407-4D36-B78B-DBE34269795B V1 EN
Figure 503:
Timer logic for voltage and frequency operate pulse
3.12.3.8
Other functions
The configuration includes few instances of multipurpose protection MAPGAPC,
high-impedance fault detection PHIZ, runtime counter for machines and devices
MDSOPT and different types of timers and control functions. These functions are not
included in application configuration but they can be based on the system
requirements.
3.13
Standard configuration L
3.13.1
Applications
The standard configuration for directional overcurrent and directional earth-fault
protection with phase voltage-based measurements, undervoltage and overvoltage
protection, frequency protection and measurement functions is mainly intended for
cable and overhead-line feeder applications in isolated or resonant-earthed
distribution networks. The configuration also includes additional options for selecting
earth-fault protection based on admittance, wattmetric or harmonic-based principles.
The IED with a standard configuration is delivered from the factory with default
settings and parameters. The end user flexibility for incoming, outgoing and internal
signal designation within the IED enables this configuration to be further adapted to
different primary circuit layouts and the related functionality needs by modifying the
internal functionality using PCM600.
Standard configuration L provides the highest functionality level of REF615 standard
configurations supporting sensor inputs. Standard configuration L is delivered
preconfigured with directional overcurrent protection but it also supports non-
directional overcurrent protection as well as directional overpower. Depending on the
specific feeder application, the appropriate functionality can be selected and an own
configuration created with the Application Configuration tool in PCM600. Standard
configuration L is not designed for using all the available functionality content in one
IED at the same time. To ensure the performance of the IED, the user specific
configuration load is verified with the Application Configuration tool of PCM600.
Section 3
1MRS756378 S
REF615 standard configurations
322
REF615
Application Manual