![ABB relion REF615 Скачать руководство пользователя страница 72](http://html.mh-extra.com/html/abb/relion-ref615/relion-ref615_applications-manual_2824072.webp)
TCSSCBR1
BLOCK
ALARM
TCSSCBR2
BLOCK
ALARM
OR
B1
B2
O
TCSSCBR1_ALARM
TCSSCBR1_ALARM
TCSSCBR2_ALARM
TCSSCBR2_ALARM
TCSSCBR_BLOCKING
TCSSCBR_BLOCKING
TCSSCBR_ALARM
GUID-F6281256-8B8D-41D9-AD19-014D604AFCEC V1 EN
Figure 36:
Trip circuit supervision function
OR6
B1
B2
B3
B4
B5
B6
O
TRPPTRC2_TRIP
X120_BI3_CB_OPENED
TRPPTRC1_TRIP
TCSSCBR_BLOCKING
GUID-F0B3AFC4-7D62-49A3-BF0D-AD03041EA78D V1 EN
Figure 37:
Logic for blocking of trip circuit supervision
3.3.3.4
Functional diagrams for control and interlocking
The circuit breaker closing is enabled when the
ENA_CLOSE
input is activated. The
input can be activated using the configuration logic, which is based on the status of the
trip logics. However, other signals can be connected based on the application needs.
The
SYNC_ITL_BYP
input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position.
SYNC_ITL_BYP
overrides, for example, active interlocking conditions when the
circuit breaker truck is closed in service position.
CBXCBR1
POSOPEN
POSCLOSE
ENA_OPEN
ENA_CLOSE
BLK_OPEN
BLK_CLOSE
AU_OPEN
AU_CLOSE
TRIP
SYNC_OK
SYNC_ITL_BYP
SELECTED
EXE_OP
EXE_CL
OP_REQ
CL_REQ
OPENPOS
CLOSEPOS
OKPOS
OPEN_ENAD
CLOSE_ENAD
TRUE
X120_BI3_CB_OPENED
X120_BI2_CB_CLOSED
CBXCBR1_ENA_CLOSE
CBXCBR1_EXE_CL
CBXCBR1_EXE_OP
FALSE
CBXCBR1_AU_OPEN
CBXCBR1_AU_CLOSE
CBXCBR1_SELECTED
GUID-FD60A0AB-713C-461F-BB52-7195A5AD23DA V2 EN
Figure 38:
Circuit breaker control logic: Circuit breaker 1
Section 3
1MRS756378 S
REF615 standard configurations
66
REF615
Application Manual
Содержание relion REF615
Страница 1: ...Relion 615 series Feeder Protection and Control REF615 Application Manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 398: ...392 ...
Страница 402: ...396 ...
Страница 403: ...397 ...