![ABB relion REF615 Скачать руководство пользователя страница 267](http://html.mh-extra.com/html/abb/relion-ref615/relion-ref615_applications-manual_2824267.webp)
Channel
ID text
Level trigger mode
40
CCSPVC1 - fail
Level trigger off
41
X120 BI1 - ext OC blocking
Level trigger off
42
X120 BI2 - CB closed
Level trigger off
43
X120 BI3 - CB opened
Level trigger off
44
ARCSARC1 - ARC flt det
Level trigger off
ARCSARC2 - ARC flt det
ARCSARC3 - ARC flt det
45
DARREC1 - close CB
Level trigger off
DARREC1 - unsuc recl
46
ARCSARC1 - operate
Positive or Rising
47
ARCSARC2 - operate
Positive or Rising
48
ARCSARC3 - operate
Positive or Rising
49
DARREC1 - inpro
Level trigger off
50
FRPFRQ1 - start
Positive or Rising
51
FRPFRQ2 - start
Positive or Rising
52
FRPFRQ3 - start
Positive or Rising
53
FRPFRQ1 - operate
Level trigger off
FRPFRQ2 - operate
FRPFRQ3 - operate
54
SECRSYN1 - sync inpro
Level trigger off
55
SECRSYN1 - sync ok
Level trigger off
56
SECRSYN1 - cl fail al
Level trigger off
57
SECRSYN1 - cmd fail al
Level trigger off
3.11.3
Functional diagrams
The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed and changed with
PCM600 according to the application requirements.
The analog channels have fixed connections to the different function blocks inside the
IED’s standard configuration. However, the 12 analog channels available for the
disturbance recorder function are freely selectable as a part of the disturbance
recorder’s parameter settings.
The phase currents to the IED are fed from a current transformer. The residual current
to the IED is fed from either residually connected CTs, an external core balance CT,
neutral CT or internally calculated.
The phase voltages to the IED are fed from a voltage transformer. The residual voltage
to the IED is fed from either residually connected VTs, an open delta connected VT
or internally calculated.
1MRS756378 S
Section 3
REF615 standard configurations
REF615
261
Application Manual
Содержание relion REF615
Страница 1: ...Relion 615 series Feeder Protection and Control REF615 Application Manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 398: ...392 ...
Страница 402: ...396 ...
Страница 403: ...397 ...