The upstream blocking from the start of the second low stage of three-phase non-
directional overcurrent protection PHLPTOC2 is connected to the binary output
X110:SO1. This output can be used for sending a blocking signal to the relevant
overcurrent protection stage of the IED at the infeeding bay.

OR6

B1

B2

B3

B4

B5

B6

O

UPSTEAM_OC_BLOCKING

PHLPTOC2_START

GUID-97C38BE4-34C3-408A-95E1-3AD7BEBD8588 V1 EN

Figure 563:

Upstream blocking logic

The output 

BLK2H

 of three-phase inrush detector INRPHAR1 enables either blocking

the function or multiplying the active settings for any of the available overcurrent or
earth-fault function blocks.

INRPHAR1

BLOCK

BLK2H

INRPHAR1_BLK2H

GUID-4BBC0DE7-8C67-4E17-A6CF-F0D0E5535D53 V1 EN

Figure 564:

Inrush detector function

Two negative-sequence overcurrent protection stages NSPTOC1 and NSPTOC2 are
provided for phase unbalance protection. These functions are used to protect the
feeder against phase unbalance.

NSPTOC1

BLOCK

ENA_MULT

OPERATE

START

NSPTOC2

BLOCK

ENA_MULT

OPERATE

START

OR

B1

B2

O

NSPTOC1_OPERATE

NSPTOC1_OPERATE

NSPTOC2_OPERATE

NSPTOC2_OPERATE

NSPTOC1_START

NSPTOC2_START

NSPTOC_OPERATE

GUID-D2BCBB3A-C69C-438B-BC3F-31C77B49BCC5 V1 EN

Figure 565:

Negative sequence overcurrent protection function

Four non-directional earth-fault stages and three directional earth-fault stages are
offered earth-fault protection. However in the configuration three non-directional
earth fault stages are considered. One stage is dedicated to sensitive earth-fault
protection EFLPTOC2. According to the IED's order code, the directional earth-fault
protection method can be based on conventional directional earth-fault DEFxPDEF
only or alternatively used together with admittance-based earth-fault protection

Section 3

1MRS756378 S

REF615 standard configurations

360

REF615

Application Manual

Содержание relion REF615

Страница 1: ...Relion 615 series Feeder Protection and Control REF615 Application Manual ...

Страница 2: ......

Страница 3: ...Document ID 1MRS756378 Issued 2016 05 20 Revision S Product version 5 0 FP1 Copyright 2016 ABB All rights reserved ...

Страница 4: ...is document is furnished under a license and may be used copied or disclosed only in accordance with the terms of such license Trademarks ABB and Relion are registered trademarks of the ABB Group All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders Warranty Please inquire about the terms of warranty from your nearest ABB...

Страница 5: ...cted and communicate data and information via a network interface which should be connected to a secure network It is the sole responsibility of the person or entity responsible for network administration to ensure a secure connection to the network and to take the necessary measures such as but not limited to installation of firewalls application of authentication measures encryption of data inst...

Страница 6: ...nd concerning electrical equipment for use within specified voltage limits Low voltage directive 2006 95 EC This conformity is the result of tests conducted by ABB in accordance with the product standard EN 60255 26 for the EMC directive and with the product standards EN 60255 1 and EN 60255 27 for the low voltage directive The product is designed in accordance with the international standards of ...

Страница 7: ...ackage version 19 Operation functionality 20 Optional functions 20 Physical hardware 20 Local HMI 24 Display 25 LEDs 26 Keypad 26 Web HMI 26 Authorization 28 Audit trail 28 Communication 30 Self healing Ethernet ring 31 Ethernet redundancy 32 Process bus 34 Secure communication 36 Section 3 REF615 standard configurations 37 Standard configurations 37 Addition of control functions for primary devic...

Страница 8: ... 87 Functional diagrams for control and interlocking 89 Functional diagrams for measurement functions 91 Functional diagrams for I O and alarm LEDs 93 Functional diagrams for other timer logics 96 Other functions 97 Standard configuration C 97 Applications 97 Functions 98 Default I O connections 98 Default disturbance recorder settings 99 Functional diagrams 101 Functional diagrams for protection ...

Страница 9: ...ional diagrams for measurement functions 159 Functional diagrams for I O and alarm LEDs 161 Functional diagrams for other timer logics 164 Other functions 165 Standard configuration F 165 Applications 165 Functions 166 Default I O connections 166 Default disturbance recorder settings 168 Functional diagrams 170 Functional diagrams for protection 171 Functional diagrams for disturbance recorder 184...

Страница 10: ... Functional diagrams for I O and alarm LEDs 252 Functional diagrams for other timer logics 255 Other functions 256 Standard configuration J 256 Applications 256 Functions 257 Default I O connections 257 Default disturbance recorder settings 259 Functional diagrams 261 Functional diagrams for protection 262 Functional diagrams for disturbance recorder 275 Functional diagrams for condition monitorin...

Страница 11: ...s for other timer logics 353 Other functions 354 Standard configuration N 354 Applications 354 Functions 355 Default I O connections 355 Default disturbance recorder settings 357 Functional diagrams 358 Functional diagrams for protection 359 Functional diagrams for disturbance recorder 366 Functional diagrams for condition monitoring 367 Functional diagrams for control and interlocking 369 Functio...

Страница 12: ...ase voltages 384 Residual voltage 384 Sensor inputs 384 Auxiliary supply voltage input 384 Binary inputs 385 Optional light sensor inputs 387 RTD mA inputs 388 Outputs 389 Outputs for tripping and controlling 389 Outputs for signalling 389 IRF 391 Section 6 Glossary 393 Table of contents 6 REF615 Application Manual ...

Страница 13: ... be used The manual can also be used when calculating settings 1 2 Intended audience This manual addresses the protection and control engineer responsible for planning pre engineering and engineering The protection and control engineer must be experienced in electrical power engineering and have knowledge of related technology such as protection schemes and principles 1MRS756378 S Section 1 Introd...

Страница 14: ...6124C V2 EN Figure 1 The intended use of documents during the product life cycle Product series and product specific manuals can be downloaded from the ABB Web site http www abb com relion 1 3 2 Document revision history Document revision date Product version History A 2007 12 20 1 0 First release B 2008 02 08 1 0 Content updated C 2008 07 02 1 1 Content updated to correspond to the product versio...

Страница 15: ...documents from the ABB Web site http www abb com substationautomation 1 3 3 Related documentation Name of the document Document ID Modbus Communication Protocol Manual 1MRS756468 DNP3 Communication Protocol Manual 1MRS756709 IEC 60870 5 103 Communication Protocol Manual 1MRS756710 IEC 61850 Engineering Guide 1MRS756475 Engineering Manual 1MRS757121 Installation Manual 1MRS756375 Operation Manual 1...

Страница 16: ...ution notices 1 4 2 Document conventions A particular convention may not be used in this manual Abbreviations and acronyms are spelled out in the glossary The glossary also contains definitions of important terms Push button navigation in the LHMI menu structure is presented by using the push button icons To navigate between the options use and Menu paths are presented in bold Select Main menu Set...

Страница 17: ...ection high stage EFHPTOC1 Io 1 51N 2 1 Non directional earth fault protection instantaneous stage EFIPTOC1 Io 1 50N 51N 1 Directional earth fault protection low stage DEFLPDEF1 Io 1 67N 1 1 DEFLPDEF2 Io 2 67N 1 2 Directional earth fault protection high stage DEFHPDEF1 Io 1 67N 2 1 Admittance based earth fault protection EFPADM1 Yo 1 21YN 1 EFPADM2 Yo 2 21YN 2 EFPADM3 Yo 3 21YN 3 Wattmetric based ...

Страница 18: ...eders cables and distribution transformers T1PTTR1 3Ith F 1 49F 1 High impedance based restricted earth fault protection HREFPDIF1 dIoHi 1 87NH 1 High impedance differential protection for phase A HIAPDIF1 dHi_A 1 87A 1 High impedance differential protection for phase B HIBPDIF1 dHi_B 1 87B 1 High impedance differential protection for phase C HICPDIF1 dHi_C 1 87C 1 Circuit breaker failure protecti...

Страница 19: ... 1 32R 32O 1 DOPPDPR2 P Q 2 32R 32O 2 Multifrequency admittance based earth fault protection MFADPSDE1 Io Y 1 67YN 1 Interconnection functions Directional reactive power undervoltage protection DQPTUV1 Q 3U 1 32Q 27 1 Low voltage ride through protection LVRTPTUV1 U RT 1 27RT 1 LVRTPTUV2 U RT 2 27RT 2 LVRTPTUV3 U RT 3 27RT 3 Voltage vector shift protection VVSPPAM1 VS 1 78V 1 Power quality Current ...

Страница 20: ...impedance protection scheme for phase B HZCCBSPVC1 MCS I_B 1 MCS I_B 1 Current transformer supervision for high impedance protection scheme for phase C HZCCCSPVC1 MCS I_C 1 MCS I_C 1 Fuse failure supervision SEQSPVC1 FUSEF 1 60 1 Runtime counter for machines and devices MDSOPT1 OPTS 1 OPTM 1 Measurement Disturbance recorder RDRE1 DR 1 DFR 1 Load profile record LDPRLRC1 LOADPROF 1 LOADPROF 1 Fault ...

Страница 21: ...1 TPM 1 Pulse timer 8 pcs PTGAPC1 PT 1 PT 1 PTGAPC2 PT 2 PT 2 Time delay off 8 pcs TOFGAPC1 TOF 1 TOF 1 TOFGAPC2 TOF 2 TOF 2 TOFGAPC3 TOF 3 TOF 3 TOFGAPC4 TOF 4 TOF 4 Time delay on 8 pcs TONGAPC1 TON 1 TON 1 TONGAPC2 TON 2 TON 2 TONGAPC3 TON 3 TON 3 TONGAPC4 TON 4 TON 4 Set reset 8 pcs SRGAPC1 SR 1 SR 1 SRGAPC2 SR 2 SR 2 SRGAPC3 SR 3 SR 3 SRGAPC4 SR 4 SR 4 Move 8 pcs MVGAPC1 MV 1 MV 1 MVGAPC2 MV 2...

Страница 22: ...16 ...

Страница 23: ...ion devices The relay provides main protection for overhead lines and cable feeders in distribution networks The relay is also used as back up protection in applications where an independent and redundant protection system is required Depending on the chosen standard configuration the relay is adapted for the protection of overhead line and cable feeders in isolated neutral resistance earthed comp...

Страница 24: ... configurability support Analog GOOSE support Large display with single line diagram Enhanced mechanical design Increased maximum amount of events and fault records Admittance based earth fault protection Frequency measurement and protection Synchronism and energizing check Combi sensor inputs Multi port Ethernet option 4 0 New configuration J Additions changes for configurations A H Dual fiber op...

Страница 25: ...port for synchronism and energizing check with IEC 61850 9 2 LE Support for configuration migration starting from Ver 3 0 to Ver 5 0 FP1 Software closable Ethernet ports Chinese language support Report summary via WHMI Multifrequency admittance based E F Support for high impedance differential protection Voltage unbalance power quality option Interconnection protection option Reverse power directi...

Страница 26: ... only Wattmetric based earth fault protection configurations A B E F G J L and N only Harmonics based earth fault protection configurations B D F J L and N only Interconnection protection configurations L and N only Power quality functions configurations J K L and N only Fault locator configurations K L and N only RTD mA measurement configurations B D E F H J and N only IEC 61850 9 2 LE configurat...

Страница 27: ...act X110 BIO module Only with configurations B D E F G H J K L and N 8 binary inputs 4 SO contacts Only with configurations B D E F G H J K L and N 8 binary inputs 3 HSO contacts X120 AI BI module Only with configurations A and B 3 phase current inputs 1 5 A 1 residual current input 1 5 A or 0 2 1 A 1 1 residual voltage input 60 210 V 3 binary inputs Only with configurations C D E F H J and N 3 ph...

Страница 28: ...e Optional for configurations B and D 6 binary inputs 3 SO contacts Optional RTD mA module Optional for configurations B and D 2 generic mA inputs 6 RTD sensor inputs X000 Optional communication module See the technical manual for details about different types of communication modules 1 The 0 2 1 A input is normally used in applications requiring sensitive earth fault protection and featuring core...

Страница 29: ... HSO FA FB AC 4 1 11 4 PO 6 SO 6 2 FG 4 1 11 4 PO 2 SO 3 HSO C AC AD AB 4 4 4 PO 2 SO D AC AD AF 4 18 4 PO 9 SO FB 4 18 4 PO 5 SO 3 HSO FC FD AD 4 12 4 PO 6 SO 6 2 FE 4 12 4 PO 2 SO 3 HSO E F H J N AE AF AG 4 5 16 4 PO 6 SO FC 4 5 16 4 PO 2 SO 3 HSO FE FF AG 4 5 12 4 PO 6 SO 2 1 FC 4 5 12 4 PO 2 SO 3 HSO 2 1 Table continues on next page 1MRS756378 S Section 2 REF615 overview REF615 23 Application ...

Страница 30: ...ting monitoring and controlling the protection relay The LHMI comprises the display buttons LED indicators and communication port REF615 Overcurrent Dir earth fault Voltage protection Phase unbalance Thermal overload Breaker failure Disturb rec Triggered CB condition monitoring Supervision Arc detected Autoreclose shot in progr A070704 V4 EN Figure 2 Example of the LHMI Section 2 1MRS756378 S REF6...

Страница 31: ...12 pixels 5 20 Large variable width 13 14 pixels 3 8 or more 1 Depending on the selected language Table 5 Large display Character size1 Rows in the view Characters per row Small mono spaced 6 12 pixels 10 20 Large variable width 13 14 pixels 7 8 or more 1 Depending on the selected language The display view is divided into four basic areas 1 2 3 4 A070705 V3 EN Figure 3 Display layout 1 Header 2 Ic...

Страница 32: ... disconnector The push buttons are also used to acknowledge alarms reset indications provide help and switch between local and remote control mode A071176 V1 EN Figure 4 LHMI keypad with object control navigation and command push buttons and RJ 45 communication port 2 5 Web HMI The WHMI allows secure access to the protection relay via a Web browser When the Secure Communication parameter in the pr...

Страница 33: ...ng Exporting parameters Report summary The menu tree structure on the WHMI is almost identical to the one on the LHMI A070754 V6 EN Figure 5 Example view of the WHMI The WHMI can be accessed locally and remotely Locally by connecting the laptop to the protection relay via the front communication port Remotely over LAN WAN 1MRS756378 S Section 2 REF615 overview REF615 27 Application Manual ...

Страница 34: ...sturbance recorder settings Setting the protection relay to test mode Selecting language ADMINISTRATOR All listed above Changing password Factory default activation For user authorization for PCM600 see PCM600 documentation 2 6 1 Audit trail The protection relay offers a large set of event logging functions Critical system and protection relay security related events are logged to a separate nonvo...

Страница 35: ...roup remotely Setting group local User changed setting group locally Control remote DPC object control remote Control local DPC object control local Test on Test mode on Test off Test mode off Reset trips Reset latched trips TRPPTRC Setting commit Settings have been changed Time change Time changed directly by the user Note that this is not used when the protection relay is synchronised properly b...

Страница 36: ...g level None Configurati on change Setting group Setting group control Settings edit All Configuration change Firmware change Firmware change fail Attached to retrofit test case Removed from retrofit test case Setting group remote Setting group local Control remote Control local Test on Test off Reset trips Setting commit Time change View audit log Login Logout Password change Firmware reset Viola...

Страница 37: ... are left for example for IEC 61850 and Modbus All communication connectors except for the front port connector are placed on integrated optional communication modules The protection relay can be connected to Ethernet based communication systems via the RJ 45 connector 100Base TX or the fiber optic LC connector 100Base FX An optional serial interface is available for RS 232 RS 485 communication 2 ...

Страница 38: ... based on two complementary protocols defined in the IEC 62439 3 2012 standard parallel redundancy protocol PRP 1 and high availability seamless redundancy HSR protocol Both protocols rely on the duplication of all transmitted information via two Ethernet ports for one logical network connection Therefore both are able to overcome the failure of a link or switch with a zero switchover time thus fu...

Страница 39: ...r attached to one network only and can therefore communicate only with DANs and SANs attached to the same network or are attached through a redundancy box a device that behaves like a DAN Ethernet switch IEC 61850 PRP Ethernet switch REF615 REF620 RET620 REM620 REF615 SCADA COM600 GUID 334D26B1 C3BD 47B6 BD9D 2301190A5E9D V1 EN Figure 7 PRP solution In case a laptop or a PC workstation is connecte...

Страница 40: ...such as laptops and printers must be attached through a redundancy box that acts as a ring element For example a 615 or 620 series protection relay with HSR support can be used as a redundancy box GUID 207430A7 3AEC 42B2 BC4D 3083B3225990 V1 EN Figure 8 HSR solution 2 7 3 Process bus Process bus IEC 61850 9 2 defines the transmission of Sampled Measured Values within the substation automation syst...

Страница 41: ...V GOOSE GOOSE SMV GOOSE SMV SMV GOOSE SMV GOOSE GUID 2371EFA7 4369 4F1A A23F CF0CE2D474D3 V4 EN Figure 9 Process bus application of voltage sharing and synchrocheck The 615 series supports IEC 61850 process bus with sampled values of analog currents and voltages The measured values are transferred as sampled values using the IEC 61850 9 2 LE protocol which uses the same physical Ethernet network a...

Страница 42: ...EEE 1588 v2 support COM0031 COM0037 However RED615 supports this option only with the communication card variant having fiber optic station bus ports See the IEC 61850 engineering guide for detailed system requirements and configuration details 2 7 4 Secure communication The protection relay supports secure communication for WHMI and file transfer protocol If the Secure Communication parameter is ...

Страница 43: ...nal overcurrent and directional earth fault protection A Non directional overcurrent and directional earth fault protection and circuit breaker condition monitoring RTD option B Non directional overcurrent and earth fault protection C Non directional overcurrent and earth fault protection and circuit breaker condition monitoring RTD option D Non directional overcurrent and directional earth fault ...

Страница 44: ...Three phase non directional overcurrent protection high stage PHHPTOC 2 2 2 2 2 2 1 1 1 Three phase non directional overcurrent protection instantaneous stage PHIPTOC 1 1 1 1 1 1 1 1 1 1 1 1 Three phase directional overcurrent protection low stage DPHLPDOC 2 2 2 1 2 2 Three phase directional overcurrent protection high stage DPHHPDOC 1 1 1 1 1 1 Non directional earth fault protection low stage EFL...

Страница 45: ...ircuit breaker failure protection CCBRBRF 1 1 1 1 1 1 1 1 1 1 1 1 Three phase inrush detector INRPHAR 1 1 1 1 1 1 1 1 1 1 1 1 Switch onto fault CBPSOF 1 1 1 1 1 1 1 1 1 1 1 1 Master trip TRPPTRC 2 2 3 6 2 2 3 6 2 3 6 2 3 6 2 3 6 2 3 6 2 3 6 2 3 6 2 3 6 2 3 6 Arc protection ARCSARC 3 3 3 3 3 3 3 3 3 3 3 3 Multipurpose protection MAPGAPC 18 18 18 18 18 18 18 18 18 18 18 18 Fault locator SCEFRFLO 1 1...

Страница 46: ... for phase B HZCCBSPVC 1 Current transformer supervision for high impedance protection scheme for phase C HZCCCSPVC 1 Fuse failure supervision SEQSPVC 1 1 1 1 1 1 1 1 Runtime counter for machines and devices MDSOPT 1 1 1 1 1 1 1 1 1 1 1 1 Measurement Disturbance recorder RDRE 1 1 1 1 1 1 1 1 1 1 1 1 Load profile record LDPRLRC 1 1 1 1 1 1 1 1 1 1 Fault record FLTRFRC 1 1 1 1 1 1 1 1 1 1 1 1 Three ...

Страница 47: ...ncluded and connected to the corresponding HSO in the configuration only when the BIO0007 module is used If additionally the ARC option is selected ARCSARC is connected in the configuration to the corresponding master trip input 7 Power quality option includes current total demand distortion voltage total harmonic distortion voltage variation and voltage unbalance 8 Available only with IEC 61850 9...

Страница 48: ...ontrol should be carefully verified for example make and carry and breaking capacity If the requirements for the primary device control circuit are not met using external auxiliary relays should be considered Section 3 1MRS756378 S REF615 standard configurations 42 REF615 Application Manual ...

Страница 49: ... PO4 SO1 TCS1 PO3 PO2 PO1 IRF Uaux 20 X130 1 2 3 4 5 6 BI 4 BI 3 BI 2 BI 1 BI 6 BI 5 8 9 7 X130 12 10 11 15 13 14 18 16 17 SO3 SO2 SO1 1 4 L1 L2 L3 da dn S1 S2 P1 P2 P2 P1 S1 S2 X110 3 4 5 6 7 8 9 10 BI 6 BI 5 BI 4 BI 3 BI 2 BI 8 BI 7 12 13 11 BI 1 1 2 X110 16 14 15 19 17 18 22 20 21 SO3 SO2 SO1 23 SO4 24 A N 2 Positive Current Direction X120 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Io IL1 IL2 BI 3 BI 2 B...

Страница 50: ...Current Direction 2 1 Optional X130 module optional in REF615 conf D 2 The IED features an automatic short circuit mechanism in the CT connector when plug in unit is detached 3 REF615 conf D BIO0005 module 8BI 4BO Alternative module BIO0007 8BI 3HSO 4 REF615 conf D BIO0006 module 6BI 3BO Alternative module RTD0001 6RTD 2mA X120 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Io IL1 IL2 BI 4 BI 3 BI 2 BI 1 IL3 1 ...

Страница 51: ...GUID F7601942 ACF2 47E2 8F21 CD9C1D2BC1F0 V4 EN Figure 13 Connection diagram for the E and F configurations 1MRS756378 S Section 3 REF615 standard configurations REF615 45 Application Manual ...

Страница 52: ...4 5 IL1 7 8 U1 X132 4 5 IL2 7 8 U2 X133 4 5 IL3 7 8 U3 Io 0 2 1A N X13 Light sensor input 1 1 X14 Light sensor input 2 1 X15 Light sensor input 3 1 1 Optional 2 BIO0005 Module 8BI 4BO Alternative Module BIO0007 8BI 3HSO P2 P1 S1 S2 Positive Current Direction L1 L2 L3 2 2 GUID B70F0C14 52B2 4213 8781 5A7CA1E40451 V2 EN Figure 14 Connection diagram for the G and L configurations Section 3 1MRS756378...

Страница 53: ...GUID E8E2F79F 3DD8 46BD 8DE7 87A30133A7AE V1 EN Figure 15 Connection diagram for the H J and N configurations 1MRS756378 S Section 3 REF615 standard configurations REF615 47 Application Manual ...

Страница 54: ...I 3 BI 2 BI 8 BI 7 12 13 11 BI 1 1 2 X110 16 14 15 19 17 18 22 20 21 SO3 SO2 SO1 23 SO4 24 2 Positive Current Direction X120 1 2 3 4 5 6 7 8 9 10 11 12 13 14 not in use 1 5A N not in use IoB for HREFPDIF1 IL1 IL2 IL3 Io 1 5A N 1 5A N 1 5A N 1 5A N 1 5A N 1 5A N da dn a n N A X130 1 2 3 4 5 6 BI 4 BI 3 BI 2 BI 1 8 7 9 10 11 12 U12B for SECRSYN1 13 14 U1 15 16 U2 17 18 U3 Uo N N N N 60 N 210V 60 210...

Страница 55: ...g earth fault protection based on admittance or wattmetric based principles The IED with a standard configuration is delivered from the factory with default settings and parameters The end user flexibility for incoming outgoing and internal signal designation within the IED enables this configuration to be further adapted to different primary circuit layouts and the related functionality needs by ...

Страница 56: ... Current transformer Voltage transformer 1 Conventional transformer inputs ALSO AVAILABLE Disturbance and fault recorders Event log and recorded data Local Remote push button on LHMI Self supervision Time synchronization IEEE 1588 v2 SNTP IRIG B User management Web HMI 2 TCS TCM O I 79 2 I2 46 I2 I1 46PD 3Ith F 49F 3I 50P 51P 3 ARC 50L 50NL 2 Master Trip Lockout relay 94 86 2 Io 67N 1 Io 67N 2 Io ...

Страница 57: ...nt operate 2 Directional or intermittent earth fault operate 3 Double cross country earth fault or residual overvoltage operate 4 Negative sequence overcurrent or phase discontinuity operate 5 Thermal overload alarm 6 Breaker failure operate 7 Disturbance recorder triggered 8 9 Trip circuit supervision alarm 10 Arc protection operate 11 Autoreclose in progress 3 3 2 2 Default disturbance recorder ...

Страница 58: ...g 11 EFHPTOC1 start Positive or Rising 12 PDNSPTOC1 start Positive or Rising 13 T1PTTR1 start Positive or Rising 14 ROVPTOV1 start Positive or Rising 15 ROVPTOV2 start Positive or Rising 16 ROVPTOV3 start Positive or Rising 17 CCBRBRF1 trret Level trigger off 18 CCBRBRF1 trbu Level trigger off 19 PHIPTOC1 operate Level trigger off PHHPTOC1 operate PHHPTOC2 operate PHLPTOC1 operate 20 NSPTOC1 opera...

Страница 59: ...tput alarm LED and function to function connections The default connections can be viewed and changed with PCM600 according to the application requirements The analog channels have fixed connections to the different function blocks inside the IED s standard configuration However the 12 analog channels available for the disturbance recorder function are freely selectable as a part of the disturbanc...

Страница 60: ...OC2 BLOCK ENA_MULT OPERATE START OR6 B1 B2 B3 B4 B5 B6 O PHIPTOC1_OPERATE PHIPTOC1_OPERATE PHLPTOC1_OPERATE PHLPTOC1_OPERATE PHHPTOC1_OPERATE PHHPTOC1_OPERATE PHHPTOC2_OPERATE PHHPTOC2_OPERATE PHLPTOC1_START PHHPTOC1_START PHHPTOC2_START PHIPTOC1_START X120_BI1_EXT_OC_BLOCKING PHxPTOC_OPERATE GUID 55B40D0D C4B2 4997 B3D0 934CCCFF1FB7 V1 EN Figure 18 Overcurrent protection functions The output INRP...

Страница 61: ... sequence overcurrent protection function Three stages are provided for directional earth fault protection According to the IED s order code the directional earth fault protection method is based on conventional directional earth fault DEFxPDEF only or used alternatively together with admittance based earth fault protection EFPADM or wattmetric based earth fault protection WPWDE In addition there ...

Страница 62: ...LPDEF1_OPERATE DEFLPDEF2_OPERATE DEFHPDEF1_START DEFLPDEF2_START DEFLPDEF1_START GUID 3499F814 CAB8 4310 9428 D3B72A9BEAF3 V1 EN Figure 21 Directional earth fault protection functions INTRPTEF1 BLOCK OPERATE START BLK_EF INTRPTEF1_OPERATE INTRPTEF1_START GUID 99B9BCD7 90A1 4259 A475 8DFCA244F32C V1 EN Figure 22 Transient or intermittent earth fault protection functions Section 3 1MRS756378 S REF61...

Страница 63: ...EN Figure 23 Wattmetric protection function EFPADM1 BLOCK RELEASE OPERATE START EFPADM2 BLOCK RELEASE OPERATE START EFPADM3 BLOCK RELEASE OPERATE START OR6 B1 B2 B3 B4 B5 B6 O EFPADM1_OPERATE EFPADM1_OPERATE EFPADM2_OPERATE EFPADM2_OPERATE EFPADM3_OPERATE EFPADM3_OPERATE EFPADM1_START EFPADM2_START EFPADM3_START EFPADM_OPERATE GUID AE7BA7DD 60E7 4D48 8F98 2605BEB424FA V1 EN Figure 24 Admittance ba...

Страница 64: ...nsformers T1PTTR1 detects overloads under varying load conditions T1PTTR1 BLK_OPR ENA_MULT TEMP_AMB OPERATE START ALARM BLK_CLOSE T1PTTR1_START T1PTTR1_OPERATE T1PTTR1_ALARM GUID 4DD81601 4C74 4305 A280 EB0DD2A7D958 V1 EN Figure 27 Thermal overcurrent protection function Circuit breaker failure protection CCBRBRF1 is initiated via the START input by number of different protection functions availab...

Страница 65: ...IED Each arc protection function block has two different operation modes that is with or without the phase and residual current check The operate signals from ARCSARC1 3 are connected to both trip logic TRPPTRC1 and TRPPTRC2 ARCSARC1 BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET ARCSARC2 BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET ARCSARC3 BLOCK REM_FLT_ARC OPR_MODE OPERATE ARC_FLT_DET OR6 B1 ...

Страница 66: ...is connected directly to binary output X100 PO1 Set the parameters for DARREC1 properly Check the initialization signals of DARREC1 DARREC1 INIT_1 INIT_2 INIT_3 INIT_4 INIT_5 INIT_6 DEL_INIT_2 DEL_INIT_3 DEL_INIT_4 BLK_RECL_T BLK_RCLM_T BLK_THERM CB_POS CB_READY INC_SHOTP INHIBIT_RECL RECL_ON SYNC OPEN_CB CLOSE_CB CMD_WAIT INPRO LOCKED PROT_CRD UNSUC_RECL AR_ON READY ACTIVE OR6 B1 B2 B3 B4 B5 B6 O...

Страница 67: ...B5 B6 O ROVPTOV1_OPERATE ROVPTOV1_OPERATE ROVPTOV2_OPERATE ROVPTOV2_OPERATE ROVPTOV3_OPERATE ROVPTOV3_OPERATE ROVPTOV1_START ROVPTOV2_START ROVPTOV3_START ROVPTOV_OPERATE GUID 57D2326C BF0D 4A76 B414 828A0FAFE035 V1 EN Figure 31 Residual voltage protection function General start and operate from all the functions are connected to minimum pulse timer TPGAPC1 for setting the minimum pulse length for...

Страница 68: ...OC1_START PDNSPTOC1_START ROVPTOV1_START ROVPTOV2_START ROVPTOV3_START DEFHPDEF1_START DEFLPDEF2_START DEFLPDEF1_START GUID 5473CE1D D794 485C B2E2 D4F702603427 V1 EN Figure 32 General start and operate signals The operate signals from the protection functions are connected to the two trip logics TRPPTRC1 and TRPPTRC2 The output of these trip logic functions are available at binary outputs X100 PO...

Страница 69: ...2_OPERATE EFPADM1_OPERATE EFPADM2_OPERATE EFPADM3_OPERATE INTRPTEF1_OPERATE PDNSPTOC1_OPERATE ROVPTOV1_OPERATE ROVPTOV2_OPERATE ROVPTOV3_OPERATE DEFHPDEF1_OPERATE DEFLPDEF1_OPERATE DEFLPDEF2_OPERATE EFHPTOC1_OPERATE WPWDE1_OPERATE WPWDE2_OPERATE WPWDE3_OPERATE ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE GUID 74DA3CAA F877 4C2E 9390 F444EA6B5F6C V1 EN Figure 33 Trip logic TRPPTRC1 1MRS756378...

Страница 70: ..._OPERATE EFHPTOC1_OPERATE WPWDE1_OPERATE WPWDE2_OPERATE WPWDE3_OPERATE ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE CCBRBRF1_TRRET GUID AF276C39 F671 459C 9472 7243985B578A V1 EN Figure 34 Trip logic TRPPTRC2 3 3 3 2 Functional diagrams for disturbance recorder The START and OPERATE outputs from the protection stages are routed to trigger the disturbance recorder or alternatively only to be ...

Страница 71: ...E CCBRBRF1_TRRET PHLPTOC1_START PHHPTOC1_START PHHPTOC2_START PHIPTOC1_START NSPTOC1_START NSPTOC2_START INTRPTEF1_START EFHPTOC1_START PDNSPTOC1_START ROVPTOV1_START ROVPTOV2_START ROVPTOV3_START DEFHPDEF1_START DEFLPDEF2_START DEFLPDEF1_START X120_BI1_EXT_OC_BLOCKING WPWDE1_START EFPADM1_START EFPADM2_START EFPADM3_START WPWDE2_START WPWDE3_START T1PTTR1_START INRPHAR1_BLK2H T1PTTR1_OPERATE DARR...

Страница 72: ...logics However other signals can be connected based on the application needs The SYNC_ITL_BYP input can be used for example to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position SYNC_ITL_BYP overrides for example active interlocking conditions when the circuit breaker truck is closed in service position CBXCBR1 POSOPEN POSCLOSE ENA_OPEN ENA_CLOS...

Страница 73: ... Circuit breaker close enable logic The configuration includes the logic for generating circuit breaker external closing and opening command with the IED in local or remote mode Check the logic for the external circuit breaker closing command and modify it according to the application AND B1 B2 O AND B1 B2 O OR B1 B2 O FALSE FALSE CBXCBR1_AU_CLOSE CONTROL_LOCAL CONTROL_REMOTE GUID 8657C398 3CE6 47...

Страница 74: ...ocks can generate low alarm or warning and high alarm or warning signals for the measured current values CMMXU1 BLOCK HIGH_ALARM HIGH_WARN LOW_WARN LOW_ALARM GUID C4DBF3EA C264 4F60 941B FAFDADD11315 V1 EN Figure 44 Current measurement Three phase current measurement CSMSQI1 GUID 57A365D0 D629 4DDC 9268 D5D427C6F5A8 V1 EN Figure 45 Current measurement Sequence current measurements RESCMMXU1 BLOCK ...

Страница 75: ... V1 EN Figure 49 Default binary inputs X120 CB_CLOSE_COMMAND CCBRBRF1_TRBU CB_OPEN_COMMAND TRPPTRC2_TRIP GENERAL_START_PULSE GENERAL_OPERATE_PULSE X100 PSM X100 PO1 X100 PSM X100 PO2 X100 PSM X100 SO1 X100 PSM X100 SO2 X100 PSM X100 PO3 X100 PSM X100 PO4 GUID B78100E6 F29B 4F6D 9035 56BA646E64FC V1 EN Figure 50 Default binary outputs X100 1MRS756378 S Section 3 REF615 standard configurations REF61...

Страница 76: ... B5 B6 O OR B1 B2 O OR B1 B2 O INTRPTEF1_OPERATE PDNSPTOC1_OPERATE EFHPTOC1_OPERATE DEF_OPERATE EFPADM_OPERATE WPWDE_OPERATE ROVPTOV_OPERATE T1PTTR1_ALARM PHxPTOC_OPERATE NSPTOC_OPERATE GUID E32FB298 A762 4D91 9134 2AD11BA1B12F V1 EN Section 3 1MRS756378 S REF615 standard configurations 70 REF615 Application Manual ...

Страница 77: ...ion but they can be added based on the system requirements 3 4 Standard configuration B 3 4 1 Applications The standard configuration for non directional overcurrent and directional earth fault protection is mainly intended for cable and overhead line feeder applications in isolated and resonant earthed distribution networks The configuration also includes additional options for selecting earth fa...

Страница 78: ... RS 232 Redundant protocols HSR PRP RSTP REF615 1 2 3 1 2 B I Io Uo Limit value supervision Load profile record RTD mA measurement optional Symmetrical components 4 1 Analog interface types 1 Current transformer Voltage transformer 1 Conventional transformer inputs ALSO AVAILABLE Disturbance and fault recorders Event log and recorded data High Speed Output module optional Local Remote push button o...

Страница 79: ...ream breaker X100 PO3 Open circuit breaker trip coil 1 X100 PO4 Open circuit breaker trip coil 2 X100 SO1 General start indication X100 SO2 General operate indication X110 SO1 Upstream overcurrent blocking X110 SO2 Overcurrent operate alarm X110 SO3 Earth fault operate alarm X110 HSO1 Arc protection instance 1 operate activated X110 HSO2 Arc protection instance 2 operate activated X110 HSO3 Arc pr...

Страница 80: ...ger mode 1 PHLPTOC1 start Positive or Rising 2 PHHPTOC1 start Positive or Rising 3 PHHPTOC2 start Positive or Rising 4 PHIPTOC1 start Positive or Rising 5 NSPTOC1 start Positive or Rising 6 NSPTOC2 start Positive or Rising 7 DEFLPDEF1 start Positive or Rising EFPADM1 start WPWDE1 start 8 DEFLPDEF2 start Positive or Rising EFPADM2 start WPWDE2 start 9 EFPADM3 start Positive or Rising WPWDE3 start 1...

Страница 81: ...ate EFPADM1 operate EFPADM2 operate EFPADM3 operate WPWDE1 operate WPWDE2 operate WPWDE3 operate 22 INTRPTEF1 operate Level trigger off 23 EFHPTOC1 operate Level trigger off 24 PDNSPTOC1 operate Level trigger off 25 INRPHAR1 blk2h Level trigger off 26 T1PTTR1 operate Level trigger off 27 ROVPTOV1 operate Level trigger off ROVPTOV2 operate ROVPTOV3 operate 28 ARCSARC1 ARC flt det Level trigger off ...

Страница 82: ...o the IED is fed from either residually connected CTs an external core balance CT neutral CT or internally calculated The residual voltage to the IED is fed from either the residually connected VTs or an open delta connected VT The IED offers six different settings groups which can be set based on individual needs Each group can be activated or deactivated using the setting group settings availabl...

Страница 83: ...tream blocking from the start of the second high stage of three phase non directional overcurrent protection PHHPTOC2 is connected to the binary output X110 SO1 This output can be used for sending a blocking signal to the relevant overcurrent protection stage of the IED at the infeeding bay OR6 B1 B2 B3 B4 B5 B6 O UPSTEAM_OC_BLOCKING PHHPTOC2_START GUID 2A6B241E 751B 4FA1 8D4C 93B5470ADE90 V1 EN F...

Страница 84: ...l earth fault protection According to the IED s order code the directional earth fault protection method can be based on conventional directional earth fault DEFxPDEF only or alternatively used together with admittance based earth fault protection EFPADM or wattmetric based earth fault protection WPWDE or harmonics based earth fault protection HAEFPTOC1 In addition there is a dedicated protection ...

Страница 85: ...110_BI2_RCA_CONTROL OR6 B1 B2 B3 B4 B5 B6 O DEFHPDEF1_OPERATE DEFLPDEF1_OPERATE DEFLPDEF2_OPERATE DEFxPDEF_OPERATE GUID 27CCBD30 6092 47C7 B753 18A7413E4B77 V1 EN Figure 57 Directional earth fault protection functions INTRPTEF1 BLOCK OPERATE START BLK_EF INTRPTEF1_OPERATE INTRPTEF1_START GUID 8D6E91C3 C468 487F 8CBA C02AABCB7B1F V1 EN Figure 58 Transient or intermittent earth fault protection func...

Страница 86: ...EN Figure 59 Wattmetric protection function EFPADM1 BLOCK RELEASE OPERATE START EFPADM2 BLOCK RELEASE OPERATE START EFPADM3 BLOCK RELEASE OPERATE START OR6 B1 B2 B3 B4 B5 B6 O EFPADM1_OPERATE EFPADM1_OPERATE EFPADM2_OPERATE EFPADM2_OPERATE EFPADM3_OPERATE EFPADM3_OPERATE EFPADM1_START EFPADM2_START EFPADM3_START EFPADM_OPERATE GUID 47970D0E B770 43BE 8848 2B156E31D274 V1 EN Figure 60 Admittance ba...

Страница 87: ...rent protection function Circuit breaker failure protection CCBRBRF1 is initiated via the START input by number of different protection functions available in the IED The breaker failure protection function offers different operating modes associated with the circuit breaker position and the measured phase and residual currents The circuit breaker failure protection function has two operating outp...

Страница 88: ...t the phase and residual current check The operate signals from ARCSARC1 3 are connected to both trip logic TRPPTRC1 and TRPPTRC2 If the IED has been ordered with high speed binary outputs the individual operate signals from ARCSARC1 3 are connected to dedicated trip logic TRPPTRC3 5 The outputs of TRPPTRC3 5 are available at high speed outputs X110 HSO1 X110 HSO2 and X110 HSO3 respectively Sectio...

Страница 89: ...3_TRIP TRPPTRC4_TRIP TRPPTRC5_TRIP ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE GUID 706BD2A2 4F97 4CFD B3D7 CAE40BFBB820 V1 EN Figure 65 Arc protection with dedicated HSO The optional autoreclosing function is configured to be initiated by operate signals from a number of protection stages through the INIT_1 5 inputs It is possible to create individual autoreclose sequences for each input T...

Страница 90: ... B1 B2 B3 B4 B5 B6 O OR6 B1 B2 B3 B4 B5 B6 O OR B1 B2 O X120_BI3_CB_OPENED DARREC1_CLOSE_CB DARREC1_OPEN_CB X110_BI3_GAS_PRESSURE_ALARM X110_BI4_CB_SPRING_CHARGED PHIPTOC1_OPERATE PHHPTOC1_OPERATE NSPTOC1_OPERATE PHHPTOC2_OPERATE NSPTOC2_OPERATE EFPADM2_OPERATE EFPADM3_OPERATE INTRPTEF1_OPERATE PDNSPTOC1_OPERATE DEFHPDEF1_OPERATE DEFLPDEF2_OPERATE WPWDE2_OPERATE WPWDE3_OPERATE ARCSARC1_OPERATE ARC...

Страница 91: ...ADM1_OPERATE EFPADM2_OPERATE EFPADM3_OPERATE INTRPTEF1_OPERATE PDNSPTOC1_OPERATE ROVPTOV1_OPERATE ROVPTOV2_OPERATE ROVPTOV3_OPERATE DEFHPDEF1_OPERATE DEFLPDEF1_OPERATE DEFLPDEF2_OPERATE EFHPTOC1_OPERATE WPWDE1_OPERATE WPWDE2_OPERATE WPWDE3_OPERATE ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE PHLPTOC1_START PHHPTOC1_START PHHPTOC2_START PHIPTOC1_START NSPTOC1_START NSPTOC2_START INTRPTEF1_STA...

Страница 92: ... EN Figure 69 Trip logic TRPPTRC1 OR6 B1 B2 B3 B4 B5 B6 O TRPPTRC2 BLOCK OPERATE RST_LKOUT TRIP CL_LKOUT OR6 B1 B2 B3 B4 B5 B6 O OR6 B1 B2 B3 B4 B5 B6 O OR6 B1 B2 B3 B4 B5 B6 O OR6 B1 B2 B3 B4 B5 B6 O OR6 B1 B2 B3 B4 B5 B6 O TRPPTRC2_TRIP PHIPTOC1_OPERATE PHLPTOC1_OPERATE PHHPTOC1_OPERATE NSPTOC1_OPERATE PHHPTOC2_OPERATE NSPTOC2_OPERATE EFPADM1_OPERATE EFPADM2_OPERATE EFPADM3_OPERATE INTRPTEF1_OPE...

Страница 93: ...DEFHPDEF1_START DEFLPDEF2_START DEFLPDEF1_START EFPADM1_START EFPADM2_START EFPADM3_START WPWDE1_START WPWDE2_START WPWDE3_START X120_BI1_EXT_OC_BLOCKING T1PTTR1_START INRPHAR1_BLK2H T1PTTR1_OPERATE DARREC1_INPRO ARCSARC1_ARC_FLT_DET ARCSARC2_ARC_FLT_DET ARCSARC3_ARC_FLT_DET DARREC1_UNSUC_RECL DISTURB_RECORD_TRIGGERED GUID 9490DCA4 54F2 4490 990B F9CB5419CACD V2 EN Figure 71 Disturbance recorder 3...

Страница 94: ...ARGED GUID 7B9FF17E 827E 40A4 B1D2 F13E236D0381 V1 EN Figure 74 Logic for start of circuit breaker spring charging Two separate trip circuit supervision functions are included TCSSCBR1 for power output X100 PO3 and TCSSCBR2 for power output X100 PO4 Both the functions are blocked by the master trip TRPPTRC1 and TRPPTRC2 and the circuit breaker open signal It is assumed that there is no external re...

Страница 95: ...are controllable type By default the status only blocks are connected in standard configuration The disconnector CB truck and line side earthing switch status information are connected to DCSXSWI1 and ESSXSI1 respectively DCSXSWI1 POSOPEN POSCLOSE OPENPOS CLOSEPOS OKPOS DCSXSWI1_OKPOS X110_BI6_CB_TRUCK_IN_TEST X110_BI5_CB_TRUCK_IN_SERVICE GUID 04F8826B 9EF7 4249 8BD9 9FA85114918C V1 EN Figure 77 D...

Страница 96: ...E ENA_OPEN ENA_CLOSE BLK_OPEN BLK_CLOSE AU_OPEN AU_CLOSE TRIP SYNC_OK SYNC_ITL_BYP SELECTED EXE_OP EXE_CL OP_REQ CL_REQ OPENPOS CLOSEPOS OKPOS OPEN_ENAD CLOSE_ENAD TRUE X120_BI3_CB_OPENED X120_BI2_CB_CLOSED CBXCBR1_ENA_CLOSE CBXCBR1_EXE_CL CBXCBR1_EXE_OP FALSE CBXCBR1_AU_OPEN CBXCBR1_AU_CLOSE CBXCBR1_SELECTED GUID 54C9EDF5 8EE3 4C65 85A8 D098A2EC7326 V2 EN Figure 79 Circuit breaker control logic C...

Страница 97: ...tion AND B1 B2 O AND B1 B2 O OR B1 B2 O FALSE FALSE CBXBCR1_AU_OPEN CONTROL_LOCAL CONTROL_REMOTE GUID 73713DC3 F7C8 4821 AF9D 2A7568AFE963 V1 EN Figure 83 External opening command for circuit breaker AND B1 B2 O AND B1 B2 O OR B1 B2 O FALSE FALSE CBXCBR1_AU_CLOSE CONTROL_LOCAL CONTROL_REMOTE GUID 5BED9700 F389 4A3E AE41 6854954D5819 V1 EN Figure 84 External closing command for circuit breaker 3 4 ...

Страница 98: ...9 9ED9 B9EF3AF4D941 V1 EN Figure 85 Current measurement Three phase current measurement CSMSQI1 GUID 55E03474 FC5C 4A69 8018 2E80D64228FE V1 EN Figure 86 Current measurement Sequence current measurements RESCMMXU1 BLOCK HIGH_ALARM HIGH_WARN GUID D547C128 B4B7 42B0 AA05 2565E19D2EFD V1 EN Figure 87 Current measurement Residual current measurements RESVMMXU1 BLOCK HIGH_ALARM HIGH_WARN GUID C392DC8A ...

Страница 99: ...Input 2 X110 BIO X110 Input 8 X110 BIO X110 Input 3 X110 BIO X110 Input 6 X110 BIO H X110 Input 7 X110 BIO H X110 Input 8 X110 BIO H X110 Input 4 X110 BIO X110 Input 5 X110 BIO X110 Input 2 X110 BIO H X110 Input 5 GUID C68E8E24 23B4 414D 8D6A 57C0D7A11076 V2 EN Figure 91 Binary inputs X110 terminal block X120_BI3_CB_OPENED X120_BI2_CB_CLOSED X120_BI1_EXT_OC_BLOCKING X120 AIM X120 Input 1 X120 AIM ...

Страница 100: ...6B2 894775BBEEE5 V2 EN Figure 93 Default binary outputs X110 CB_CLOSE_COMMAND CCBRBRF1_TRBU CB_OPEN_COMMAND TRPPTRC2_TRIP GENERAL_START_PULSE GENERAL_OPERATE_PULSE X100 PSM X100 PO1 X100 PSM X100 PO2 X100 PSM X100 SO1 X100 PSM X100 SO2 X100 PSM X100 PO3 X100 PSM X100 PO4 GUID C51C47D5 DD89 4F9E 8B91 9A8794033464 V1 EN Figure 94 Default binary outputs X100 Section 3 1MRS756378 S REF615 standard con...

Страница 101: ... B5 B6 O OR B1 B2 O OR B1 B2 O INTRPTEF1_OPERATE PDNSPTOC1_OPERATE EFHPTOC1_OPERATE DEF_OPERATE EFPADM_OPERATE WPWDE_OPERATE ROVPTOV_OPERATE T1PTTR1_ALARM PHxPTOC_OPERATE NSPTOC_OPERATE GUID CD2C4F23 C15B 4A9A 8DB8 A7B862A221D7 V1 EN 1MRS756378 S Section 3 REF615 standard configurations REF615 95 Application Manual ...

Страница 102: ...ate and earth fault operate logic The operate logics are connected to the minimum pulse timer TPGAPC2 for setting the minimum pulse length for the outputs The output from TPGAPC2 is connected to binary outputs TPGAPC2 IN1 IN2 OUT1 OUT2 OR6 B1 B2 B3 B4 B5 B6 O OC_OPERATE_PULSE EF_OPERATE_PULSE INTRPTEF1_OPERATE EFHPTOC1_OPERATE PHxPTOC_OPERATE DEFxPDEF_OPERATE EFPADM_OPERATE ROVPTOV_OPERATE WPWDE_O...

Страница 103: ... non directional overcurrent and non directional earth fault protection is mainly intended for cable and overhead line feeder applications in directly or resistance earthed distribution networks The IED with a standard configuration is delivered from the factory with default settings and parameters The end user flexibility for incoming outgoing and internal signal designation within the IED enable...

Страница 104: ...T RS 485 RS 232 Redundant protocols HSR PRP RSTP REF615 1 C I Io Limit value supervision Symmetrical components 4 Analog interface types 1 Current transformer Voltage transformer 1 Conventional transformer inputs 2 TCS TCM O I 79 2 I2 46 I2 I1 46PD 3Ith F 49F 3I 50P 51P 3 ARC 50L 50NL 2 Master Trip Lockout relay 94 86 3I Io BF 51BF 51NBF 3I2f 68 3I 51P 1 2 3I 51P 2 Io 51N 2 Io 50N 51N 2 Io 51N 1 O...

Страница 105: ...1 General start indication X100 SO2 General operate indication Table 23 Default connections for LEDs LED Description 1 Non directional overcurrent operate 2 Non directional earth fault operate 3 Sensitive earth fault operate 4 Negative sequence overcurrent or phase discontinuity operate 5 Thermal overload alarm 6 Breaker failure operate 7 Disturbance recorder triggered 8 9 Trip circuit supervision...

Страница 106: ...t Positive or Rising 10 EFLPTOC2 start Positive or Rising 11 12 PDNSPTOC1 start Positive or Rising 13 T1PTTR1 start Positive or Rising 14 CCBRBRF1 trret Level trigger off 15 CCBRBRF1 trbu Level trigger off 16 PHIPTOC1 operate Level trigger off PHHPTOC1 operate PHHPTOC2 operate PHLPTOC1 operate 17 NSPTOC1 operate Level trigger off NSPTOC2 operate 18 EFLPTOC1 operate Level trigger off EFHPTOC1 opera...

Страница 107: ...els available for the disturbance recorder function are freely selectable as a part of the disturbance recorder s parameter settings The phase currents to the IED are fed from a current transformer The residual current to the IED is fed from either residually connected CTs an external core balance CT neutral CT or internally calculated The IED offers six different settings groups which can be set ...

Страница 108: ...6D289F7EBA V1 EN Figure 98 Overcurrent protection functions The output BLK2H of three phase inrush detector INRPHAR1 enables either blocking the function or multiplying the active settings for any of the available overcurrent or earth fault function blocks INRPHAR1 BLOCK BLK2H INRPHAR1_BLK2H GUID D54BF44E 9EBD 4C83 ABDD 49BB5BB6373E V1 EN Figure 99 Inrush detector function Two negative sequence ov...

Страница 109: ...TOC1 BLOCK ENA_MULT OPERATE START EFLPTOC1 BLOCK ENA_MULT OPERATE START EFIPTOC1 BLOCK ENA_MULT OPERATE START OR6 B1 B2 B3 B4 B5 B6 O EFLPTOC1_OPERATE EFLPTOC1_OPERATE EFHPTOC1_OPERATE EFHPTOC1_OPERATE EFIPTOC1_OPERATE EFIPTOC1_OPERATE EFLPTOC1_START EFIPTOC1_START EFHPTOC1_START EFxPTOC_OPERATE GUID 2540474C 37D6 4706 A740 2D0334DA26C2 V1 EN Figure 101 Earth fault protection functions EFLPTOC2 BL...

Страница 110: ...erating outputs TRRET and TRBU The TRRET operate output is used for retripping its own breaker through TRPPTRC2_TRIP The TRBU output is used to give a backup trip to the breaker feeding upstream For this purpose the TRBU operate output signal is connected to the binary output X100 PO2 CCBRBRF1 BLOCK START POSCLOSE CB_FAULT CB_FAULT_AL TRBU TRRET OR6 B1 B2 B3 B4 B5 B6 O OR6 B1 B2 B3 B4 B5 B6 O OR6 ...

Страница 111: ...ividual autoreclose sequences for each input The autoreclosing function can be inhibited with the INHIBIT_RECL input By default few selected protection function operations are connected to this input A control command to the circuit breaker either local or remote also blocks the autoreclosing function via the CBXCBR1 SELECTED signal The circuit breaker availability for the autoreclosing sequence i...

Страница 112: ...6 O OR6 B1 B2 B3 B4 B5 B6 O OR6 B1 B2 B3 B4 B5 B6 O TPGAPC1 IN1 IN2 OUT1 OUT2 GENERAL_START GENERAL_OPERATE PHIPTOC1_OPERATE PHLPTOC1_OPERATE PHHPTOC1_OPERATE NSPTOC1_OPERATE PHHPTOC2_OPERATE NSPTOC2_OPERATE EFLPTOC1_OPERATE EFHPTOC1_OPERATE EFIPTOC1_OPERATE EFLPTOC2_OPERATE PDNSPTOC1_OPERATE ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE PHLPTOC1_START PHHPTOC1_START PHHPTOC2_START PHIPTOC1_S...

Страница 113: ...TRPPTRC2_TRIP PHIPTOC1_OPERATE PHLPTOC1_OPERATE PHHPTOC1_OPERATE NSPTOC1_OPERATE PHHPTOC2_OPERATE NSPTOC2_OPERATE EFLPTOC1_OPERATE EFHPTOC1_OPERATE EFIPTOC1_OPERATE EFLPTOC2_OPERATE PDNSPTOC1_OPERATE X120_BI4_RST_LOCKOUT ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE CCBRBRF1_TRRET GUID 0E184AB6 326B 4311 8022 CE8733342975 V1 EN Figure 110 Trip logic TRPPTRC2 3 5 3 2 Functional diagrams for di...

Страница 114: ...OC2_START EFLPTOC1_START EFLPTOC2_START EFIPTOC1_START EFHPTOC1_START PDNSPTOC1_START X120_BI1_EXT_OC_BLOCKING T1PTTR1_START ARCSARC1_ARC_FLT_DET ARCSARC2_ARC_FLT_DET ARCSARC3_ARC_FLT_DET INRPHAR1_BLK2H T1PTTR1_OPERATE DARREC1_INPRO DARREC1_UNSUC_RECL DISTURB_RECORD_TRIGGERED GUID 8F5ACED1 E0E7 46A6 A35B FCA6B69D5722 V2 EN Figure 111 Disturbance recorder 3 5 3 3 Functional diagrams for condition m...

Страница 115: ...breaker closing is enabled when the ENA_CLOSE input is activated The input can be activated using the configuration logic which is based on the status of the trip logics However other signals can be connected based on the application needs The SYNC_ITL_BYP input can be used for example to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position SYNC_I...

Страница 116: ...2 B3 B4 B5 B6 O CB_OPEN_COMMAND CBXCBR1_EXE_OP TRPPTRC1_TRIP DARREC1_OPEN_CB GUID DEB21767 B0D9 4A3B 8601 8C108AE0B706 V1 EN Figure 116 Circuit breaker control logic Signal for opening of circuit breaker 1 AND B1 B2 O NOT IN OUT NOT IN OUT TRPPTRC2_TRIP CBXCBR1_ENA_CLOSE TRPPTRC1_TRIP GUID 860F40F5 18B2 48E3 B38F 7225A5F04449 V1 EN Figure 117 Circuit breaker close enable logic The configuration in...

Страница 117: ...measures the sequence current and the residual current measurement RESCMMXU1 measures the residual current The measurements can be seen from the LHMI and they are available under the measurement option in the menu selection Based on the settings function blocks can generate low alarm or warning and high alarm or warning signals for the measured current values CMMXU1 BLOCK HIGH_ALARM HIGH_WARN LOW_...

Страница 118: ...120 AIM X120 Input 3 X120 AIM X120 Input 4 GUID 33C33CE1 9EB3 437B BA4B AE67E2820C55 V1 EN Figure 124 Default binary inputs X120 CB_CLOSE_COMMAND CCBRBRF1_TRBU CB_OPEN_COMMAND TRPPTRC2_TRIP GENERAL_START GENERAL_OPERATE X100 PSM X100 PO1 X100 PSM X100 PO2 X100 PSM X100 SO1 X100 PSM X100 SO2 X100 PSM X100 PO3 X100 PSM X100 PO4 GUID CF4349F6 CCF5 4A1E A1BE BCC323C21F34 V1 EN Figure 125 Default binar...

Страница 119: ...ALARM RESET LED5 OK ALARM RESET OR B1 B2 O EFLPTOC2_OPERATE PDNSPTOC1_OPERATE T1PTTR1_ALARM PHxPTOC_OPERATE EFxPTOC_OPERATE NSPTOC_OPERATE GUID 39C29981 E86D 4570 B841 CF19A89767CF V1 EN 1MRS756378 S Section 3 REF615 standard configurations REF615 113 Application Manual ...

Страница 120: ...er functions These functions are not included in application configuration but they can be added based on the system requirements 3 6 Standard configuration D 3 6 1 Applications The standard configuration for non directional overcurrent and non directional earth fault protection is mainly intended for cable and overhead line feeder applications in directly or resistance earthed distribution networ...

Страница 121: ...thernet TX RJ45 FX LC Serial Serial glass fiber ST RS 485 RS 232 Redundant protocols HSR PRP RSTP REF615 D I Io Limit value supervision Load profile record RTD mA measurement optional Symmetrical components 4 Analog interface types 1 Current transformer Voltage transformer 1 Conventional transformer inputs OPTS OPTM 2 TCS TCM O I 79 2 I2 46 I2 I1 46PD 3Ith F 49F 3I 50P 51P 3 ARC 50L 50NL Io 51N 2 3I...

Страница 122: ...ailure protection trip to upstream breaker X100 PO3 Open circuit breaker trip coil 1 X100 PO4 Open circuit breaker trip coil 2 X100 SO1 General start indication X100 SO2 General operate indication X110 SO1 Upstream overcurrent blocking X110 SO2 Overcurrent operate alarm X110 SO3 Earth fault operate alarm X110 HSO1 Arc protection instance 1 operate activated X110 HSO2 Arc protection instance 2 oper...

Страница 123: ...ing 2 PHHPTOC1 start Positive or Rising 3 PHHPTOC2 start Positive or Rising 4 PHIPTOC1 start Positive or Rising 5 NSPTOC1 start Positive or Rising 6 NSPTOC2 start Positive or Rising 7 EFLPTOC1 start Positive or Rising 8 EFHPTOC1 start Positive or Rising 9 EFIPTOC1 start Positive or Rising 10 EFLPTOC2 start Positive or Rising 11 12 PDNSPTOC1 start Positive or Rising 13 T1PTTR1 start Positive or Ris...

Страница 124: ...ecl Level trigger off 31 X120BI1 ext OC blocking Level trigger off 32 X120BI2 CB closed Level trigger off 33 X120BI3 CB opened Level trigger off 3 6 3 Functional diagrams The functional diagrams describe the default input output alarm LED and function to function connections The default connections can be viewed and changed with PCM600 according to the application requirements The analog channels ...

Страница 125: ... X120 BI1 PHIPTOC1 BLOCK ENA_MULT OPERATE START PHLPTOC1 BLOCK ENA_MULT OPERATE START PHHPTOC1 BLOCK ENA_MULT OPERATE START PHHPTOC2 BLOCK ENA_MULT OPERATE START OR6 B1 B2 B3 B4 B5 B6 O PHIPTOC1_OPERATE PHIPTOC1_OPERATE PHLPTOC1_OPERATE PHLPTOC1_OPERATE PHHPTOC1_OPERATE PHHPTOC1_OPERATE PHHPTOC2_OPERATE PHHPTOC2_OPERATE PHLPTOC1_START PHHPTOC1_START PHHPTOC2_START PHIPTOC1_START X120_BI1_EXT_OC_BL...

Страница 126: ...ided for phase unbalance protection These functions are used to protect the feeder against phase unbalance NSPTOC1 BLOCK ENA_MULT OPERATE START NSPTOC2 BLOCK ENA_MULT OPERATE START OR B1 B2 O NSPTOC1_OPERATE NSPTOC1_OPERATE NSPTOC2_OPERATE NSPTOC2_OPERATE NSPTOC1_START NSPTOC2_START NSPTOC_OPERATE GUID 042DF7F0 BC45 4B9F 8F1B 301314789714 V1 EN Figure 131 Negative sequence overcurrent protection f...

Страница 127: ...rotection PDNSPTOC1 protects from interruptions in the normal three phase load supply for example in downed conductor situations PDNSPTOC1 BLOCK OPERATE START PDNSPTOC1_OPERATE PDNSPTOC1_START GUID E1FF7992 706A 417E 8944 AF34E8E729FB V1 EN Figure 134 Phase discontinuity protection Three phase thermal protection for feeders cables and distribution transformers T1PTTR1 detects overloads under varyi...

Страница 128: ...X120_BI2_CB_CLOSED PHIPTOC1_OPERATE PHHPTOC1_OPERATE PHHPTOC2_OPERATE EFLPTOC1_OPERATE EFHPTOC1_OPERATE EFIPTOC1_OPERATE ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE CCBRBRF1_TRRET GUID E1FC0B19 FE08 4BD1 88F2 5AC7E8249ACF V1 EN Figure 136 Circuit breaker failure protection function Three protection S1 3 stages are included as an optional function The protection offers individual function bl...

Страница 129: ...PPTRC5 BLOCK OPERATE RST_LKOUT TRIP CL_LKOUT TRPPTRC3_TRIP TRPPTRC4_TRIP TRPPTRC5_TRIP X120_BI4_RST_LOCKOUT X120_BI4_RST_LOCKOUT X120_BI4_RST_LOCKOUT ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE GUID 075DA511 6800 4425 85CE 2B1BD69661FC V1 EN Figure 138 Arc protection with dedicated HSO The optional autoreclosing function is configured to be initiated by operate signals from a number of prot...

Страница 130: ...ECL_T BLK_RCLM_T BLK_THERM CB_POS CB_READY INC_SHOTP INHIBIT_RECL RECL_ON SYNC OPEN_CB CLOSE_CB CMD_WAIT INPRO LOCKED PROT_CRD UNSUC_RECL AR_ON READY ACTIVE OR6 B1 B2 B3 B4 B5 B6 O OR6 B1 B2 B3 B4 B5 B6 O OR B1 B2 O X120_BI3_CB_OPENED DARREC1_OPEN_CB DARREC1_CLOSE_CB X110_BI3_GAS_PRESSURE_ALARM X110_BI4_CB_SPRING_CHARGED PHIPTOC1_OPERATE PHHPTOC1_OPERATE NSPTOC1_OPERATE PHHPTOC2_OPERATE NSPTOC2_OP...

Страница 131: ...TART PDNSPTOC1_START GUID 7CC700C6 F5D5 45EF 986A 9F279A0837C7 V1 EN Figure 140 General start and operate signals The operate signals from the protection functions are connected to the two trip logics TRPPTRC1 and TRPPTRC2 The output of these trip logic functions is available at binary outputs X100 PO3 and X100 PO4 The trip logic functions are provided with a lockout and latching function event ge...

Страница 132: ...PPTRC2_TRIP PHIPTOC1_OPERATE PHLPTOC1_OPERATE PHHPTOC1_OPERATE NSPTOC1_OPERATE PHHPTOC2_OPERATE NSPTOC2_OPERATE EFLPTOC1_OPERATE EFHPTOC1_OPERATE EFIPTOC1_OPERATE EFLPTOC2_OPERATE PDNSPTOC1_OPERATE X120_BI4_RST_LOCKOUT ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE CCBRBRF1_TRRET GUID ADA381AF 87B3 43A6 8A39 7856F999FD28 V1 EN Figure 142 Trip logic TRPPTRC2 3 6 3 2 Functional diagrams for dist...

Страница 133: ...CCBRBRF1_TRRET PHLPTOC1_START PHHPTOC1_START PHHPTOC2_START PHIPTOC1_START NSPTOC1_START NSPTOC2_START EFLPTOC1_START EFLPTOC2_START EFIPTOC1_START EFHPTOC1_START PDNSPTOC1_START X120_BI1_EXT_OC_BLOCKING X110_BI2_EXT_START_AUTORECLOSE T1PTTR1_START ARCSARC1_ARC_FLT_DET ARCSARC2_ARC_FLT_DET ARCSARC3_ARC_FLT_DET INRPHAR1_BLK2H T1PTTR1_OPERATE DARREC1_INPRO DARREC1_UNSUC_RECL DISTURB_RECORD_TRIGGERED...

Страница 134: ...condition monitoring function OR B1 B2 O OR6 B1 B2 B3 B4 B5 B6 O OR6 B1 B2 B3 B4 B5 B6 O SSCBR1_TRV_T_OP_ALM SSCBR1_TRV_T_CL_ALM SSCBR1_SPR_CHR_ALM SSCBR1_OPR_ALM SSCBR1_OPR_LO SSCBR1_IPOW_ALM SSCBR1_IPOW_LO SSCBR1_CB_LIFE_ALM SSCBR1_MON_ALM SSCBR1_PRES_ALM SSCBR1_PRES_LO SSCBR1_ALARMS GUID 28045DB5 20C4 46F5 B7FA 9ADA8FEF4098 V1 EN Figure 145 Logic for circuit breaker monitoring alarm NOT IN OUT ...

Страница 135: ...0B 4157 925D B11E192D689E V1 EN Figure 148 Logic for blocking of trip circuit supervision 3 6 3 4 Functional diagrams for control and interlocking Two types of disconnector and earthing switch function blocks are available DCSXSWI1 3 and ESSXSWI1 2 are status only type and DCXSWI1 2 and ESXSWI1arecontrollabletype Bydefault thestatusonlyblocksareconnectedinthe standard configuration The disconnecto...

Страница 136: ...bled The SYNC_ITL_BYP input can be used for example to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position SYNC_ITL_BYP overrides for example active interlocking conditions when the circuit breaker truck is closed in service position CBXCBR1 POSOPEN POSCLOSE ENA_OPEN ENA_CLOSE BLK_OPEN BLK_CLOSE AU_OPEN AU_CLOSE TRIP SYNC_OK SYNC_ITL_BYP SELECTED...

Страница 137: ... command with the IED in local or remote mode Check the logic for the external circuit breaker closing command and modify it according to the application Connect additional signals for opening and closing of circuit breaker in local or remote mode if it is applicable for the configuration AND B1 B2 O AND B1 B2 O OR B1 B2 O FALSE FALSE CBXCBR1_AU_CLOSE CONTROL_LOCAL CONTROL_REMOTE GUID 2BAE22BC 81C...

Страница 138: ...n the measurements sheet LDPRLRC1 offers the ability to observe the loading history of the corresponding feeder CMMXU1 BLOCK HIGH_ALARM HIGH_WARN LOW_WARN LOW_ALARM GUID 05BA9BEE 064A 4C7C B486 F82231CB43CF V1 EN Figure 157 Current measurement Three phase current measurement CSMSQI1 GUID 7F0D54B4 B973 4A6D A6F8 AAB376A1351F V1 EN Figure 158 Current measurement Sequence current measurement RESCMMXU...

Страница 139: ...110 Input 3 X110 BIO X110 Input 6 X110 BIO H X110 Input 2 X110 BIO H X110 Input 4 X110 BIO X110 Input 2 X110 BIO H X110 Input 8 X110 BIO H X110 Input 5 X110 BIO X110 Input 7 X110 BIO X110 Input 3 GUID CF4CBBC0 9B2F 4974 958C 8BFEC57A6673 V1 EN Figure 162 Binary inputs X110 terminal block X120_BI3_CB_OPENED X120_BI2_CB_CLOSED X120_BI4_RST_LOCKOUT X120_BI1_EXT_OC_BLOCKING X120 AIM X120 Input 1 X120 ...

Страница 140: ...CD94B21 V1 EN Figure 164 Binary outputs X110 terminal block CB_CLOSE_COMMAND CCBRBRF1_TRBU GENERAL_START_PULSE GENERAL_OPERATE_PULSE CB_OPEN_COMMAND TRPPTRC2_TRIP X100 PSM X100 PO1 X100 PSM X100 PO2 X100 PSM X100 SO1 X100 PSM X100 SO2 X100 PSM X100 PO3 X100 PSM X100 PO4 GUID A4CF2AA3 1FCD 44A9 91C4 482C9FBFB588 V1 EN Figure 165 Binary outputs X100 terminal block Section 3 1MRS756378 S REF615 stand...

Страница 141: ...ALARM RESET LED5 OK ALARM RESET OR B1 B2 O EFLPTOC2_OPERATE PDNSPTOC1_OPERATE PHxPTOC_OPERATE EFxPTOC_OPERATE T1PTTR1_ALARM NSPTOC_OPERATE GUID B26BBB64 D189 4246 A5A7 DB8FC8E86445 V1 EN 1MRS756378 S Section 3 REF615 standard configurations REF615 135 Application Manual ...

Страница 142: ...tion also includes overcurrent operate and earth fault operate logic The operate logics are connected to the minimum pulse timer TPGAPC for setting the minimum pulse length for the outputs The output from TPGAPC is connected to the binary outputs TPGAPC2 IN1 IN2 OUT1 OUT2 OR B1 B2 O OC_OPERATE_PULSE EF_OPERATE_PULSE EFLPTOC2_OPERATE PHxPTOC_OPERATE EFxPTOC_OPERATE GUID F6BA3876 6A37 464E 9FAB F5DC...

Страница 143: ...tended for cable and overhead line feeder applications in isolated and resonant earthed distribution networks The configuration also includes additional options for selecting earth fault protection based on admittance or wattmetric based principles The IED with a standard configuration is delivered from the factory with default settings and parameters The end user flexibility for incoming outgoing...

Страница 144: ...measurement optional Symmetrical components 4 5 Analog interface types 1 Current transformer Voltage transformer 1 Conventional transformer inputs FUSEF 60 CBCM CBCM MCS 3I MCS 3I O I 79 2 I2 46 I2 I1 46PD 3Ith F 49F 3I 50P 51P 3 ARC 50L 50NL Master Trip Lockout relay 94 86 2 Io 67N 1 Io 67N 2 Io IEF 67NIEF 3 Yo 21YN 3 Po 32N 3I Io BF 51BF 51NBF 3I2f 68 OR 3I 51P 1 2 3I 51P 2 3 Uo 59G 2 TCS TCM OP...

Страница 145: ...am breaker X100 SO1 General start indication X100 SO2 General operate indication X100 PO3 Open circuit breaker trip coil 1 X100 PO4 Open circuit breaker trip coil 2 X110 SO1 Upstream overcurrent blocking X110 SO2 Overcurrent operate alarm X110 SO3 Earth fault operate alarm X110 HSO1 Arc protection instance 1 operate activated X110 HSO2 Arc protection instance 2 operate activated X110 HSO3 Arc prot...

Страница 146: ...y channels Channel ID text Level trigger mode 1 PHLPTOC1 start Positive or Rising 2 PHHPTOC1 start Positive or Rising 3 PHHPTOC2 start Positive or Rising 4 PHIPTOC1 start Positive or Rising 5 NSPTOC1 start Positive or Rising 6 NSPTOC2 start Positive or Rising 7 DEFLPDEF1 start Positive or Rising EFPADM1 start WPWDE1 start 8 DEFLPDEF2 start Positive or Rising EFPADM2 start WPWDE2 start 9 EFPADM3 st...

Страница 147: ...rate Level trigger off DEFLPDEF1 operate DEFLPDEF2 operate EFPADM1 operate EFPADM2 operate EFPADM3 operate WPWDE1 operate WPWDE2 operate WPWDE3 operate 22 INTRPTEF1 operate Level trigger off 23 EFHPTOC1 operate Level trigger off 24 PDNSPTOC1 operate Level trigger off 25 INRPHAR1 blk2h Level trigger off 26 T1PTTR1 operate Level trigger off 27 ROVPTOV1 operate Level trigger off ROVPTOV2 operate ROVP...

Страница 148: ...ent transformer The residual current to the IED is fed from either residually connected CTs an external core balance CT neutral CT or internally calculated The phase voltages to the IED are fed from a voltage transformer The residual voltage to the IED is fed from either residually connected VTs an open delta connected VT or internally calculated The IED offers six different settings groups which ...

Страница 149: ...tream blocking from the start of the second high stage of three phase non directional overcurrent protection PHHPTOC2 is connected to the binary output X110 SO1 This output can be used for sending a blocking signal to the relevant overcurrent protection stage of the IED at the infeeding bay OR6 B1 B2 B3 B4 B5 B6 O UPSTEAM_OC_BLOCKING PHHPTOC2_START GUID 135C8785 4AA1 4D9B B100 EB7D2CA57163 V1 EN F...

Страница 150: ...V2 EN Figure 172 Negative sequence overcurrent protection function Three stages are provided for directional earth fault protection According to the IED s order code the directional earth fault protection method can be based on conventional directional earth fault DEFxPDEF only or alternatively used together with admittance based earth fault protection EFPADM or wattmetric based earth fault protec...

Страница 151: ...T DEFLPDEF2_START DEFLPDEF1_START X110_BI2_RCA_CONTROL X110_BI2_RCA_CONTROL X110_BI2_RCA_CONTROL DEFxPDEF_OPERATE GUID 887F7AE7 59D2 474B B5B8 4466B6741D35 V1 EN Figure 173 Directional earth fault protection function INTRPTEF1 BLOCK OPERATE START BLK_EF INTRPTEF1_OPERATE INTRPTEF1_START GUID BD1AFA42 4050 4B0C 823E EDDEAF7A9A58 V1 EN Figure 174 Transient or intermittent earth fault protection func...

Страница 152: ...081 4D34 AB17 CD86173B20AA V1 EN Figure 175 Wattmetric protection function EFPADM1 BLOCK RELEASE OPERATE START EFPADM2 BLOCK RELEASE OPERATE START EFPADM3 BLOCK RELEASE OPERATE START OR6 B1 B2 B3 B4 B5 B6 O EFPADM1_OPERATE EFPADM1_OPERATE EFPADM2_OPERATE EFPADM2_OPERATE EFPADM3_OPERATE EFPADM3_OPERATE EFPADM1_START EFPADM2_START EFPADM3_START EFPADM_OPERATE GUID E530E87B 85F6 421E BC3F C750132D305...

Страница 153: ...ection for feeders cables and distribution transformers T1PTTR1 detects overloads under varying load conditions The BLK_CLOSE output of the function is used to block the closing operation of circuit breaker T1PTTR1 BLK_OPR ENA_MULT TEMP_AMB OPERATE START ALARM BLK_CLOSE T1PTTR1_BLK_CLOSE T1PTTR1_START T1PTTR1_OPERATE T1PTTR1_ALARM GUID 0BC59D0E F0E3 4F46 A4EF A8D392971CF2 V1 EN Figure 179 Thermal ...

Страница 154: ...hat is with or without the phase and residual current check The operate signals from ARCSARC1 3 are connected to both trip logic TRPPTRC1 and TRPPTRC2 If the IED has been ordered with high speed binary outputs the individual operate signals from ARCSARC1 3 are connected to dedicated trip logic TRPPTRC3 5 The output of TRPPTRC3 5 are available at high speed outputs X110 HSO1 X110 HSO2 and X110 HSO3...

Страница 155: ...tion can be inhibited with the INHIBIT_RECL input By default few selected protection function operations are connected to this input A control command to the circuit breaker either local or remote also blocks the autoreclosing function via the CBXCBR1 SELECTED signal The circuit breaker availability for the autoreclosing sequence is expressed with the CB_READY input in DARREC1 DARREC1 The signal a...

Страница 156: ...PTOC1_OPERATE PHHPTOC2_OPERATE NSPTOC2_OPERATE EFPADM2_OPERATE EFPADM3_OPERATE INTRPTEF1_OPERATE PDNSPTOC1_OPERATE DEFHPDEF1_OPERATE DEFLPDEF2_OPERATE WPWDE2_OPERATE WPWDE3_OPERATE ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE CBXCBR1_SELECTED DARREC1_INPRO DARREC1_UNSUC_RECL GUID E7F8FD5B 32F7 45EA B6AF 9F840A1EA709 V1 EN Figure 183 Autoreclosing function The residual overvoltage protection ...

Страница 157: ...OPERATE PHHPTOC1_OPERATE NSPTOC1_OPERATE PHHPTOC2_OPERATE NSPTOC2_OPERATE INTRPTEF1_OPERATE PDNSPTOC1_OPERATE ROVPTOV1_OPERATE ROVPTOV2_OPERATE ROVPTOV3_OPERATE DEFHPDEF1_OPERATE DEFLPDEF1_OPERATE DEFLPDEF2_OPERATE EFHPTOC1_OPERATE EFPADM1_OPERATE EFPADM2_OPERATE EFPADM3_OPERATE WPWDE1_OPERATE WPWDE2_OPERATE WPWDE3_OPERATE ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE PHLPTOC1_START PHHPTOC1_...

Страница 158: ...B1 B2 B3 B4 B5 B6 O OR6 B1 B2 B3 B4 B5 B6 O OR6 B1 B2 B3 B4 B5 B6 O TRPPTRC1_TRIP PHIPTOC1_OPERATE PHLPTOC1_OPERATE PHHPTOC1_OPERATE NSPTOC1_OPERATE PHHPTOC2_OPERATE NSPTOC2_OPERATE INTRPTEF1_OPERATE PDNSPTOC1_OPERATE ROVPTOV1_OPERATE ROVPTOV2_OPERATE ROVPTOV3_OPERATE DEFHPDEF1_OPERATE DEFLPDEF1_OPERATE DEFLPDEF2_OPERATE EFHPTOC1_OPERATE EFPADM1_OPERATE EFPADM2_OPERATE EFPADM3_OPERATE WPWDE1_OPERA...

Страница 159: ...DM3_OPERATE WPWDE1_OPERATE WPWDE2_OPERATE WPWDE3_OPERATE ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE X120_BI4_RST_LOCKOUT CCBRBRF1_TRRET GUID 4E3A24AF 2263 4DA6 9D9B 2646177DA782 V1 EN Figure 187 Trip logic TRPPTRC2 3 7 3 2 Functional diagrams for disturbance recorder The START and the OPERATE outputs from the protection stages are routed to trigger the disturbance recorder or alternatively...

Страница 160: ...DEF2_START DEFLPDEF1_START X120_BI1_EXT_OC_BLOCKING CCSPVC1_FAIL T1PTTR1_START INRPHAR1_BLK2H T1PTTR1_OPERATE ARCSARC1_ARC_FLT_DET ARCSARC2_ARC_FLT_DET ARCSARC3_ARC_FLT_DET DARREC1_UNSUC_RECL DARREC1_INPRO SEQSPVC1_FUSEF_3PH SEQSPVC1_FUSEF_U DISTURB_RECORD_TRIGGERED GUID 9B480C8C BE93 44AF 8875 E05758D8ADEF V3 EN Figure 188 Disturbance recorder 3 7 3 3 Functional diagrams for condition monitoring ...

Страница 161: ..._IPOW_LO SSCBR1_CB_LIFE_ALM SSCBR1_MON_ALM SSCBR1_PRES_ALM SSCBR1_PRES_LO GUID FA39D0B3 73EC 4CE0 924C C09E47645694 V1 EN Figure 191 Circuit breaker condition monitoring function OR B1 B2 O OR6 B1 B2 B3 B4 B5 B6 O OR6 B1 B2 B3 B4 B5 B6 O SSCBR1_TRV_T_OP_ALM SSCBR1_TRV_T_CL_ALM SSCBR1_SPR_CHR_ALM SSCBR1_OPR_ALM SSCBR1_OPR_LO SSCBR1_IPOW_ALM SSCBR1_IPOW_LO SSCBR1_CB_LIFE_ALM SSCBR1_MON_ALM SSCBR1_PR...

Страница 162: ...ID 551738DE 408E 4244 861F 335A3D86A8DA V1 EN Figure 195 Logic for blocking of trip circuit supervision function 3 7 3 4 Functional diagrams for control and interlocking Two types of disconnector and earthing switch function blocks are available DCSXSWI1 3 and ESSXSWI1 2 are status only type and DCXSWI1 2 and ESXSWI1 are controllable type By default the status only blocks are connected in standard...

Страница 163: ...ed for example to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position SYNC_ITL_BYP overrides for example active interlocking conditions when the circuit breaker truck is closed in service position CBXCBR1 POSOPEN POSCLOSE ENA_OPEN ENA_CLOSE BLK_OPEN BLK_CLOSE AU_OPEN AU_CLOSE TRIP SYNC_OK SYNC_ITL_BYP SELECTED EXE_OP EXE_CL OP_REQ CL_REQ OPENPOS ...

Страница 164: ...must be set before enabling the closing of circuit breaker These conditions cannot be bypassed using bypass feature of the function OR6 B1 B2 B3 B4 B5 B6 O CBXCBR1_BLK_CLOSE T1PTTR1_BLK_CLOSE GUID 02C2AAA3 BF48 4645 AA7E F951054AC78A V1 EN Figure 202 Circuit breaker close blocking logic The configuration includes the logic for generating circuit breaker external closing and opening commands with t...

Страница 165: ...d by three phase voltage measurement VMMXU1 The voltage input is connected to the X130 card in the back panel The sequence voltage measurement VSMSQI1 measures the sequence voltage and the residual voltage measurement RESVMMXU1 measures the residual voltage The measurements can be seen from the LHMI and they are available under the measurement option in the menu selection Based on the settings fun...

Страница 166: ... 88B55A5D5A60 V1 EN Figure 209 Voltage measurement Sequence voltage measurement RESVMMXU1 BLOCK HIGH_ALARM HIGH_WARN GUID 8885E482 DAB8 4B05 8B7F 939A6887DE6A V1 EN Figure 210 Voltage measurement Residual voltage measurement FMMXU1 GUID 931EB287 D786 48A3 ABD5 816D18251871 V1 EN Figure 211 Other measurement Frequency measurement PEMMXU1 RSTACM GUID BC19323E D87F 44E4 9931 07947BA99D7B V1 EN Figure...

Страница 167: ...110_BI7_ES1_CLOSED X110_BI2_RCA_CONTROL X110_BI1_MCB_OPENED X110 BIO H X110 Input 4 X110 BIO H X110 Input 7 X110 BIO X110 Input 8 X110 BIO H X110 Input 3 X110 BIO H X110 Input 5 X110 BIO X110 Input 7 X110 BIO X110 Input 1 X110 BIO H X110 Input 2 X110 BIO X110 Input 5 X110 BIO H X110 Input 6 X110 BIO H X110 Input 1 X110 BIO X110 Input 3 X110 BIO H X110 Input 8 X110 BIO X110 Input 6 X110 BIO X110 In...

Страница 168: ... X110 SO2 X110 BIO X110 SO3 X110 BIO H X110 HSO1 X110 BIO H X110 HSO2 X110 BIO H X110 HSO3 GUID CBC32DCC 0DC7 4C6A B3F5 B0CC5FAE5ABA V1 EN Figure 217 Default binary outputs X110 terminal block CB_CLOSE_COMMAND CCBRBRF1_TRBU GENERAL_START_PULSE GENERAL_OPERATE_PULSE CB_OPEN_COMMAND TRPPTRC2_TRIP X100 PSM X100 PO1 X100 PSM X100 PO2 X100 PSM X100 SO1 X100 PSM X100 SO2 X100 PSM X100 PO3 X100 PSM X100 ...

Страница 169: ... B1 B2 B3 B4 B5 B6 O OR B1 B2 O OR B1 B2 O INTRPTEF1_OPERATE PDNSPTOC1_OPERATE EFHPTOC1_OPERATE DEFxPDEF_OPERATE ROVPTOV_OPERATE PHxPTOC_OPERATE T1PTTR1_ALARM NSPTOC_OPERATE GUID C8CFA43B 974D 4635 BBD3 6EE8F9846A72 V2 EN 1MRS756378 S Section 3 REF615 standard configurations REF615 163 Application Manual ...

Страница 170: ...tion also includes overcurrent operate and earth fault operate logic The operate logics are connected to minimum pulse timer TPGAPC for setting the minimum pulse length for the outputs The output from TPGAPC is connected to the binary outputs TPGAPC2 IN1 IN2 OUT1 OUT2 OR6 B1 B2 B3 B4 B5 B6 O OC_OPERATE_PULSE EF_OPERATE_PULSE INTRPTEF1_OPERATE EFHPTOC1_OPERATE PHxPTOC_OPERATE DEFxPDEF_OPERATE WPWDE...

Страница 171: ...ion and measurement function The configuration is mainly intended for cable and overhead line feeder applications in directly or resistance earthed distribution networks The configuration also includes additional options for selecting earth fault protection based on admittance wattmetric or harmonic based principles The IED with a standard configuration is delivered from the factory with default s...

Страница 172: ...trical components 4 5 Analog interface types 1 Current transformer Voltage transformer 1 Conventional transformer inputs ALSO AVAILABLE Disturbance and fault recorders Event log and recorded data High Speed Output module optional Local Remote push button on LHMI Self supervision Time synchronization IEEE 1588 v2 SNTP IRIG B User management Web HMI 2 3I 67 1 O I 79 2 I2 46 I2 I1 46PD 3Ith F 49F 3I ...

Страница 173: ...Breaker failure backup trip to upstream breaker X100 SO1 General start indication X100 SO2 General operate indication X100 PO3 Open circuit breaker trip coil 1 X100 PO4 Open circuit breaker trip coil 2 X110 SO1 Upstream overcurrent blocking X110 SO2 Overcurrent operate alarm X110 SO3 Earth fault operate alarm X110 SO4 Voltage protection operate alarm X110 HSO1 Arc protection instance 1 operate act...

Страница 174: ...e 40 Default disturbance recorder binary channels Channel ID text Level trigger mode 1 DPHLPDOC1 start Positive or Rising 2 DPHLPDOC2 start Positive or Rising 3 DPHHPDOC1 start Positive or Rising 4 PHIPTOC1 start Positive or Rising 5 NSPTOC1 start Positive or Rising 6 NSPTOC2 start Positive or Rising 7 DEFLPDEF1 start Positive or Rising EFPADM1 start WPWDE1 start 8 DEFLPDEF2 start Positive or Risi...

Страница 175: ...3 ROVPTOV2 start Positive or Rising 24 ROVPTOV3 start Positive or Rising 25 CCBRBRF1 trret Level trigger off 26 CCBRBRF1 trbu Level trigger off 27 PHIPTOC1 operate Level trigger off DPHHPDOC1 operate DPHLPDOC1 operate DPHLPDOC2 operate 28 NSPTOC1 operate Level trigger off NSPTOC2 operate 29 DEFHPDEF1 operate Level trigger off DEFLPDEF1 operate DEFLPDEF2 operate EFPADM1 operate EFPADM2 operate EFPA...

Страница 176: ...2 operate Positive or Rising 48 ARCSARC3 operate Positive or Rising 49 DARREC1 inpro Level trigger off 3 8 3 Functional diagrams The functional diagrams describe the default input output alarm LED and function to function connections The default connections can be viewed and changed with PCM600 according to the application requirements The analog channels have fixed connections to the different fu...

Страница 177: ...tional diagrams for protection The functional diagrams describe protection functionality of the IEDs in detail and according to the factory set default connections Four overcurrent stages are offered for overcurrent and short circuit protection Three of them include directional functionality DPHxPDOC Three phase non directional overcurrent protection instantaneous stage PHIPTOC1 can be blocked by ...

Страница 178: ...can be used for sending a blocking signal to the relevant overcurrent protection stage of the IED at the infeeding bay OR6 B1 B2 B3 B4 B5 B6 O UPSTEAM_OC_BLOCKING DPHLPDOC2_START GUID 5EFA1CBD DC1F 46F0 ABF2 D42054BB7BD7 V1 EN Figure 224 Upstream blocking logic The output BLK2H of three phase inrush detector INRPHAR1 enables either blocking the function or multiplying the active settings for any o...

Страница 179: ...rder code the directional earth fault protection method can be based on conventional directional earth fault DEFxPDEF only or alternatively used together with admittance based earth fault protection EFPADM or wattmetric based earth fault protection WPWDE or harmonics based earth fault protection HAEFPTOC A dedicated protection stage INTRPTEF is used either for transient based earth fault protectio...

Страница 180: ...T DEFLPDEF2_START DEFHPDEF1_START X110_BI2_RCA_CONTROL X110_BI2_RCA_CONTROL X110_BI2_RCA_CONTROL DEFxPDEF_OPERATE GUID 8C13FB21 2ECA 48BC A73D CA66853C1E3E V1 EN Figure 227 Directional earth fault protection function INTRPTEF1 BLOCK OPERATE START BLK_EF INTRPTEF1_OPERATE INTRPTEF1_START GUID D6626AFF 571A 49AC 82A0 10740638CA38 V1 EN Figure 228 Transient or intermittent earth fault protection func...

Страница 181: ...8A7 47D1 902D FF03338D0A95 V1 EN Figure 229 Wattmetric protection function EFPADM1 BLOCK RELEASE OPERATE START EFPADM2 BLOCK RELEASE OPERATE START EFPADM3 BLOCK RELEASE OPERATE START OR6 B1 B2 B3 B4 B5 B6 O EFPADM1_OPERATE EFPADM1_OPERATE EFPADM2_OPERATE EFPADM2_OPERATE EFPADM3_OPERATE EFPADM3_OPERATE EFPADM1_START EFPADM2_START EFPADM3_START EFPADM_OPERATE GUID 5DB4A853 DF00 466B 9358 00E320CA00C...

Страница 182: ... thermal protection for feeders cables and distribution transformers T1PTTR1 detects overloads under varying load conditions The BLK_CLOSE output of the function is used to block the closing operation of circuit breaker T1PTTR1 BLK_OPR ENA_MULT TEMP_AMB OPERATE START ALARM BLK_CLOSE T1PTTR1_BLK_CLOSE T1PTTR1_START T1PTTR1_OPERATE T1PTTR1_ALARM GUID D139F760 E980 4005 A357 84775C585A0A V1 EN Figure...

Страница 183: ...es ARCSARC1 3 are included as an optional function The arc protection offers individual function blocks for three arc sensors that can be connected to the IED Each arc protection function block has two different operation modes that is with or without the phase and residual current check The operate signals from ARCSARC1 3 are connected to both trip logic TRPPTRC1 and TRPPTRC2 If the IED has been ...

Страница 184: ...TE RST_LKOUT TRIP CL_LKOUT TRPPTRC3_TRIP TRPPTRC4_TRIP TRPPTRC5_TRIP ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE X120_BI4_RST_LOCKOUT X120_BI4_RST_LOCKOUT X120_BI4_RST_LOCKOUT GUID DD707ABE A698 47F0 8891 034B35A02E20 V1 EN Figure 235 Arc protection with dedicated HSO The optional autoreclosing function is configured to be initiated by operate signals from a number of protection stages thro...

Страница 185: ... B2 B3 B4 B5 B6 O OR B1 B2 O X120_BI3_CB_OPENED DARREC1_OPEN_CB DARREC1_CLOSE_CB X110_BI3_GAS_PRESSURE_ALARM X110_BI4_CB_SPRING_CHARGED PHIPTOC1_OPERATE DPHLPDOC2_OPERATE DPHHPDOC1_OPERATE NSPTOC1_OPERATE NSPTOC2_OPERATE EFPADM2_OPERATE EFPADM3_OPERATE INTRPTEF1_OPERATE PDNSPTOC1_OPERATE DEFHPDEF1_OPERATE DEFLPDEF2_OPERATE WPWDE2_OPERATE WPWDE3_OPERATE ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OP...

Страница 186: ... Overvoltage protection function PHPTUV1 BLOCK OPERATE START PHPTUV2 BLOCK OPERATE START PHPTUV3 BLOCK OPERATE START OR6 B1 B2 B3 B4 B5 B6 O PHPTUV1_OPERATE PHPTUV1_OPERATE PHPTUV2_OPERATE PHPTUV2_OPERATE PHPTUV3_OPERATE PHPTUV3_OPERATE PHPTUV1_START PHPTUV2_START PHPTUV3_START SEQSPVC1_FUSEF_U SEQSPVC1_FUSEF_U SEQSPVC1_FUSEF_U PHPTUV_OPERATE GUID 54CEBBC3 C767 4439 8B2E 77B3D78E79AB V2 EN Figure ...

Страница 187: ...age protection function NSPTOV1 BLOCK OPERATE START NSPTOV1_OPERATE NSPTOV1_START SEQSPVC1_FUSEF_U GUID 4CDD5E93 A445 40B2 9613 904A3ADFB339 V2 EN Figure 240 Negative sequence overvoltage protection function PSPTUV1 BLOCK OPERATE START PSPTUV1_OPERATE PSPTUV1_START SEQSPVC1_FUSEF_U GUID 4D2257BB 0968 4E93 9124 BCBBE323AC4B V2 EN Figure 241 Positive sequence undervoltage protection function General...

Страница 188: ...IPTOC1_START NSPTOC1_START NSPTOC2_START DEFLPDEF1_START DEFLPDEF2_START DEFHPDEF1_START INTRPTEF1_START EFHPTOC1_START PDNSPTOC1_START PHPTOV1_START PHPTOV2_START PHPTOV3_START PSPTUV1_START NSPTOV1_START PHPTUV1_START PHPTUV2_START PHPTUV3_START ROVPTOV1_START ROVPTOV2_START ROVPTOV3_START EFPADM1_START EFPADM2_START EFPADM3_START WPWDE1_START WPWDE2_START WPWDE3_START GUID 2F8D1A94 63C3 49BF 86...

Страница 189: ...OPERATE INTRPTEF1_OPERATE PDNSPTOC1_OPERATE ROVPTOV1_OPERATE ROVPTOV2_OPERATE ROVPTOV3_OPERATE DEFHPDEF1_OPERATE DEFLPDEF1_OPERATE DEFLPDEF2_OPERATE EFHPTOC1_OPERATE WPWDE1_OPERATE WPWDE2_OPERATE WPWDE3_OPERATE PHPTOV1_OPERATE PHPTOV2_OPERATE PHPTOV3_OPERATE PHPTUV1_OPERATE PSPTUV1_OPERATE NSPTOV1_OPERATE PHPTUV2_OPERATE PHPTUV3_OPERATE ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE X120_BI4_R...

Страница 190: ...3_OPERATE ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE X120_BI4_RST_LOCKOUT CCBRBRF1_TRRET GUID 910DA8E9 69B1 433E 8A29 0AA327F579AE V1 EN Figure 244 Trip logic TRPPTRC2 3 8 3 2 Functional diagrams for disturbance recorder The START and the OPERATE outputs from the protection stages are routed to trigger the disturbance recorder or alternatively only to be recorded by the disturbance recorde...

Страница 191: ...TART PHPTUV1_START PHPTUV2_START PHPTUV3_START ROVPTOV1_START ROVPTOV2_START ROVPTOV3_START EFPADM1_START EFPADM2_START EFPADM3_START WPWDE1_START WPWDE2_START WPWDE3_START X120_BI1_EXT_OC_BLOCKING CCSPVC1_FAIL SEQSPVC1_FUSEF_U T1PTTR1_START INRPHAR1_BLK2H SEQSPVC1_FUSEF_3PH DARREC1_INPRO T1PTTR1_OPERATE ARCSARC1_ARC_FLT_DET ARCSARC2_ARC_FLT_DET ARCSARC3_ARC_FLT_DET DARREC1_UNSUC_RECL DISTURB_RECO...

Страница 192: ..._ALM SSCBR1_SPR_CHR_ALM SSCBR1_OPR_ALM SSCBR1_OPR_LO SSCBR1_IPOW_ALM SSCBR1_IPOW_LO SSCBR1_CB_LIFE_ALM SSCBR1_MON_ALM SSCBR1_PRES_ALM SSCBR1_PRES_LO GUID C4E153AD BD5F 429A BE5F 9E16ED24BF87 V1 EN Figure 248 Circuit breaker condition monitoring function OR B1 B2 O OR6 B1 B2 B3 B4 B5 B6 O OR6 B1 B2 B3 B4 B5 B6 O SSCBR1_TRV_T_OP_ALM SSCBR1_TRV_T_CL_ALM SSCBR1_SPR_CHR_ALM SSCBR1_OPR_ALM SSCBR1_OPR_LO...

Страница 193: ... circuit breaker open signal It is assumed that there is no external resistor in the circuit breaker tripping coil circuit connected in parallel with the circuit breaker normally open auxiliary contact Set the parameters for TCSSCBR1 properly TCSSCBR1 BLOCK ALARM TCSSCBR2 BLOCK ALARM OR B1 B2 O TCSSCBR1_ALARM TCSSCBR1_ALARM TCSSCBR2_ALARM TCSSCBR2_ALARM TCSSCBR_BLOCKING TCSSCBR_BLOCKING TCSSCBR_AL...

Страница 194: ... 254 Earth switch control logic The circuit breaker closing is enabled when the ENA_CLOSE input is activated The input can be activated by the configuration logic which is a combination of the disconnector or breaker truck and earth switch position status status of the trip logics gas pressure alarm and the circuit breaker spring charging status The OKPOS output from DCSXSWI defines if the disconn...

Страница 195: ...Signal for closing coil of circuit breaker 1 OR6 B1 B2 B3 B4 B5 B6 O CB_OPEN_COMMAND CBXCBR1_EXE_OP TRPPTRC1_TRIP DARREC1_OPEN_CB GUID 5A234526 696C 4CC5 B39C 387D1AF6D3EB V1 EN Figure 257 Signal for opening coil of circuit breaker 1 NOT IN OUT AND6 B1 B2 B3 B4 B5 B6 O NOT IN OUT NOT IN OUT TRPPTRC2_TRIP CBXCBR1_ENA_CLOSE TRPPTRC1_TRIP X110_BI3_GAS_PRESSURE_ALARM DCSXSWI1_OKPOS X110_BI4_CB_SPRING_...

Страница 196: ...d for circuit breaker 1 AND B1 B2 O AND B1 B2 O OR B1 B2 O FALSE FALSE CBXBCR1_AU_OPEN CONTROL_LOCAL CONTROL_REMOTE GUID D12A66F5 D434 4C12 93C8 6C855C32EBC6 V1 EN Figure 261 External opening command for circuit breaker 1 3 8 3 5 Functional diagrams for measurement functions The phase current inputs to the IED are measured by the three phase current measurement function CMMXU1 The current input is...

Страница 197: ...W_WARN LOW_ALARM GUID F102851D B189 4394 9FD3 C3ED4A1343D7 V1 EN Figure 262 Current measurement Three phase current measurement CSMSQI1 GUID C9B80BF2 0589 4041 BE46 D7DC69A33AD3 V1 EN Figure 263 Current measurement Sequence current measurement RESCMMXU1 BLOCK HIGH_ALARM HIGH_WARN GUID 11B50582 C98D 4B8B 8981 45B34A38CC7D V1 EN Figure 264 Current measurement Residual current measurement VMMXU1 BLOC...

Страница 198: ...t FLTRFRC1 BLOCK CB_CLRD GUID 848C6501 5E08 40FD 823D 11DC11FFAC29 V2 EN Figure 269 Other measurement Data monitoring LDPRLRC1 RSTMEM MEM_WARN MEM_ALARM GUID 54D8F3DB 4BF4 4C5D 8FD2 D0C99684F934 V2 EN Figure 270 Other measurement Load profile record Section 3 1MRS756378 S REF615 standard configurations 192 REF615 Application Manual ...

Страница 199: ...0 BIO H X110 Input 4 X110 BIO H X110 Input 7 X110 BIO X110 Input 8 X110 BIO H X110 Input 3 X110 BIO H X110 Input 5 X110 BIO X110 Input 7 X110 BIO X110 Input 1 X110 BIO H X110 Input 2 X110 BIO X110 Input 5 X110 BIO H X110 Input 6 X110 BIO H X110 Input 1 X110 BIO X110 Input 3 X110 BIO H X110 Input 8 X110 BIO X110 Input 6 X110 BIO X110 Input 2 X110 BIO X110 Input 4 GUID 7DC22F9C E131 4AC9 A977 BF120C...

Страница 200: ... SO1 X110 BIO X110 SO2 X110 BIO X110 SO3 X110 BIO X110 SO4 X110 BIO H X110 HSO1 X110 BIO H X110 HSO2 X110 BIO H X110 HSO3 GUID B782B1DC 8E73 4E90 8158 193EDA3C3853 V1 EN Figure 273 Default binary outputs X110 CB_CLOSE_COMMAND CCBRBRF1_TRBU GENERAL_START_PULSE GENERAL_OPERATE_PULSE CB_OPEN_COMMAND TRPPTRC2_TRIP X100 PSM X100 PO1 X100 PSM X100 PO2 X100 PSM X100 SO1 X100 PSM X100 SO2 X100 PSM X100 PO...

Страница 201: ...PHIPTOC1_OPERATE INTRPTEF1_OPERATE PDNSPTOC1_OPERATE EFHPTOC1_OPERATE PSPTUV1_OPERATE NSPTOV1_OPERATE PHPTUV_OPERATE PHPTOV_OPERATE DEFxPDEF_OPERATE DEFxPDEF_OPERATE EFPADM_OPERATE ROVPTOV_OPERATE WPWDE_OPERATE T1PTTR1_ALARM NSPTOC_OPERATE GUID B77B4CBB 88A8 4250 AACE 22612AF0DC0F V2 EN 1MRS756378 S Section 3 REF615 standard configurations REF615 195 Application Manual ...

Страница 202: ... GUID CBB0DDAA 908A 4246 89A5 2DC455656D3C V2 EN Figure 275 Default LED connection 3 8 3 7 Functional diagrams for other timer logics The configuration also includes overcurrent operate earth fault operate and voltage operate logic The operate logics are connected to the minimum pulse timer TPGAPC for setting the minimum pulse length for the outputs The output from TPGAPC is connected to the binar...

Страница 203: ...pplication configuration but they can be added based on the system requirements 3 9 Standard configuration G 3 9 1 Applications The standard configuration includes directional overcurrent and directional earth fault protection undervoltage and overvoltage protection frequency protection and measurement function The configuration is mainly intended for cable and overhead line feeder applications in...

Страница 204: ...nterface types 1 Current sensor 3 Voltage sensor 3 Current transformer 1 1 Combi sensor inputs with conventional Io input CONTROL AND INDICATION 1 Object Ctrl 2 Ind 3 CB DC ES 1 Check availability of binary inputs outputs from technical documentation 2 Control and indication function for primary object 3 Status indication function for primary object 1 2 3 1 2 2 3I 67 1 O I 79 2 I2 46 I2 I1 46PD 3I...

Страница 205: ...breaker trip coil 1 X100 PO4 Open circuit breaker trip coil 2 X110 SO1 Upstream overcurrent blocking X110 SO2 Overcurrent operate alarm X110 SO3 Earth fault operate alarm X110 SO4 Voltage protection operate alarm X110 HSO1 Arc protection instance 1 operate activated X110 HSO2 Arc protection instance 2 operate activated X110 HSO3 Arc protection instance 3 operate activated Table 43 Default connecti...

Страница 206: ...NSPTOC1 start Positive or Rising 6 NSPTOC2 start Positive or Rising 7 DEFLPDEF1 start Positive or Rising EFPADM1 start WPWDE1 start 8 DEFLPDEF2 start Positive or Rising EFPADM2 start WPWDE2 start 9 EFPADM3 start Positive or Rising WPWDE3 start 10 EFHPTOC1 start Positive or Rising 11 PDNSPTOC1 start Positive or Rising 12 T1PTTR1 start Positive or Rising 13 PHPTOV1 start Positive or Rising 14 PHPTOV...

Страница 207: ... NSPTOC2 operate 28 DEFHPDEF1 operate Level trigger off DEFLPDEF1 operate DEFLPDEF2 operate EFPADM1 operate EFPADM2 operate EFPADM3 operate WPWDE1 operate WPWDE2 operate WPWDE3 operate 29 EFHPTOC1 operate Level trigger off 30 PDNSPTOC1 operate Level trigger off 31 INRPHAR1 blk2h Level trigger off 32 T1PTTR1 operate Level trigger off 33 PHPTOV1 operate Level trigger off PHPTOV2 operate PHPTOV3 oper...

Страница 208: ...D s standard configuration However the 12 analog channels available for the disturbance recorder function are freely selectable as a part of the disturbance recorder s parameter settings The phase currents to the IED are fed from Rogowski or Combi sensors The residual current to the IED is fed from either residually connected CTs an external core balance CT neutral CT or internally calculated The ...

Страница 209: ...ERATE DPHLPDOC1_OPERATE DPHLPDOC1_OPERATE DPHLPDOC1_START DPHLPDOC2_START DPHHPDOC1_START DPHxPDOC_OPERATE GUID C39AC382 EF6F 42D4 9F57 A295796FE592 V1 EN Figure 280 Directional overcurrent protection function The upstream blocking from the start of the second low stage of three phase directional overcurrent protection DPHLPDOC2 is connected to the binary output X110 SO1 This output can be used fo...

Страница 210: ...ilure in secondary circuit of sensor NSPTOC1 BLOCK ENA_MULT OPERATE START NSPTOC2 BLOCK ENA_MULT OPERATE START OR B1 B2 O NSPTOC1_OPERATE NSPTOC1_OPERATE NSPTOC2_OPERATE NSPTOC2_OPERATE NSPTOC1_START NSPTOC2_START CCSPVC1_FAIL CCSPVC1_FAIL NSPTOC_OPERATE GUID 863218A0 49A4 400F A05E 8E9954E4B722 V2 EN Figure 283 Negative sequence overcurrent protection function Three stages are provided for direct...

Страница 211: ...E9F9F318 12D1 498E AAE8 31E3EF90FA40 V1 EN Figure 284 Directional earth fault protection functions WPWDE1 BLOCK RCA_CTL OPERATE START WPWDE2 BLOCK RCA_CTL OPERATE START WPWDE3 BLOCK RCA_CTL OPERATE START OR6 B1 B2 B3 B4 B5 B6 O WPWDE1_OPERATE WPWDE1_OPERATE WPWDE2_OPERATE WPWDE2_OPERATE WPWDE3_OPERATE WPWDE3_OPERATE WPWDE1_START WPWDE2_START WPWDE3_START WPWDE_OPERATE GUID E3BBF010 632D 4742 A8D0 ...

Страница 212: ...y circuit of sensor EFHPTOC1 BLOCK ENA_MULT OPERATE START EFHPTOC1_OPERATE EFHPTOC1_START CCSPVC1_FAIL GUID AD3B6BA3 857E 44BF 9739 2F1D1AADA63B V2 EN Figure 287 Earth fault protection function Phase discontinuity protection PDNSPTOC1 protects for interruptions in the normal three phase load supply for example in downed conductor situations The function is blocked in case of detection of a failure...

Страница 213: ... B1 B2 B3 B4 B5 B6 O OR6 B1 B2 B3 B4 B5 B6 O CCBRBRF1_TRBU X110_BI1_CB_CLOSED PHIPTOC1_OPERATE DPHLPDOC2_OPERATE DPHHPDOC1_OPERATE DPHLPDOC1_OPERATE EFPADM2_OPERATE EFPADM3_OPERATE DEFHPDEF1_OPERATE DEFLPDEF2_OPERATE WPWDE2_OPERATE WPWDE3_OPERATE ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE CCBRBRF1_TRRET GUID 89971B6B 6846 4ADA B9D0 D0130A01832F V1 EN Figure 290 Circuit breaker failure prot...

Страница 214: ...P CL_LKOUT TRPPTRC5 BLOCK OPERATE RST_LKOUT TRIP CL_LKOUT TRPPTRC3_TRIP TRPPTRC4_TRIP TRPPTRC5_TRIP ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE GUID A416CC7A EB4B 46CE 9700 BFDD3ECC6C40 V1 EN Figure 291 Arc protection with dedicated HSO The optional autoreclosing function is configured to be initiated by operate signals from a number of protection stages through the INIT_1 5 inputs It is po...

Страница 215: ... O OR6 B1 B2 B3 B4 B5 B6 O OR B1 B2 O X110_BI2_CB_OPENED DARREC1_OPEN_CB DARREC1_CLOSE_CB X110_BI3_GAS_PRESSURE_ALARM X110_BI4_CB_SPRING_CHARGED PHIPTOC1_OPERATE DPHLPDOC2_OPERATE DPHHPDOC1_OPERATE NSPTOC1_OPERATE NSPTOC2_OPERATE EFPADM2_OPERATE EFPADM3_OPERATE PDNSPTOC1_OPERATE DEFHPDEF1_OPERATE DEFLPDEF2_OPERATE WPWDE2_OPERATE WPWDE3_OPERATE ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE CBX...

Страница 216: ... Overvoltage protection function PHPTUV1 BLOCK OPERATE START PHPTUV2 BLOCK OPERATE START PHPTUV3 BLOCK OPERATE START OR6 B1 B2 B3 B4 B5 B6 O PHPTUV1_OPERATE PHPTUV1_OPERATE PHPTUV2_OPERATE PHPTUV2_OPERATE PHPTUV3_OPERATE PHPTUV3_OPERATE PHPTUV1_START PHPTUV2_START PHPTUV3_START SEQSPVC1_FUSEF_U SEQSPVC1_FUSEF_U SEQSPVC1_FUSEF_U PHPTUV_OPERATE GUID 6E332AB0 7555 45A7 B622 BA1061C18D0B V2 EN Figure ...

Страница 217: ...rotection function NSPTOV1 BLOCK OPERATE START NSPTOV1_OPERATE NSPTOV1_START SEQSPVC1_FUSEF_U GUID 385727B9 A09E 40C1 A51D 630C0400338D V2 EN Figure 296 Negative sequence overvoltage protection function PSPTUV1 BLOCK OPERATE START PSPTUV1_OPERATE PSPTUV1_START SEQSPVC1_FUSEF_U GUID 656C28DB 7231 45CD 8864 15F39FF2C6A4 V2 EN Figure 297 Positive sequence undervoltage protection function General star...

Страница 218: ...T PHIPTOC1_START NSPTOC1_START NSPTOC2_START DEFLPDEF1_START DEFLPDEF2_START DEFHPDEF1_START EFHPTOC1_START PDNSPTOC1_START PHPTOV1_START PHPTOV2_START PHPTOV3_START PSPTUV1_START NSPTOV1_START PHPTUV1_START PHPTUV2_START PHPTUV3_START ROVPTOV1_START ROVPTOV2_START ROVPTOV3_START EFPADM1_START EFPADM2_START EFPADM3_START WPWDE1_START WPWDE2_START WPWDE3_START GUID B801C8EA 74F0 432F A115 E882F4A6D...

Страница 219: ...DM2_OPERATE EFPADM3_OPERATE PDNSPTOC1_OPERATE ROVPTOV1_OPERATE ROVPTOV2_OPERATE ROVPTOV3_OPERATE DEFHPDEF1_OPERATE DEFLPDEF1_OPERATE DEFLPDEF2_OPERATE EFHPTOC1_OPERATE WPWDE1_OPERATE WPWDE2_OPERATE WPWDE3_OPERATE PHPTOV1_OPERATE PHPTOV2_OPERATE PHPTOV3_OPERATE PHPTUV1_OPERATE PSPTUV1_OPERATE NSPTOV1_OPERATE PHPTUV2_OPERATE PHPTUV3_OPERATE ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE GUID BC0...

Страница 220: ...UV3_OPERATE ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE CCBRBRF1_TRRET GUID C616460D 0D6B 426B 8222 C8058AAF8332 V1 EN Figure 300 Trip logic TRPPTRC2 3 9 3 2 Functional diagrams for disturbance recorder The START and the OPERATE outputs from the protection stages are routed to trigger the disturbance recorder or alternatively only to be recorded by the disturbance recorder depending on the ...

Страница 221: ...RT PHPTOV2_START PHPTOV3_START PSPTUV1_START NSPTOV1_START PHPTUV1_START PHPTUV2_START PHPTUV3_START ROVPTOV1_START ROVPTOV2_START ROVPTOV3_START DEFLPDEF1_START DEFLPDEF2_START DEFHPDEF1_START PDNSPTOC1_START EFPADM1_START EFPADM2_START EFPADM3_START WPWDE3_START WPWDE2_START CCSPVC1_FAIL SEQSPVC1_FUSEF_U T1PTTR1_START INRPHAR1_BLK2H T1PTTR1_OPERATE SEQSPVC1_FUSEF_3PH DARREC1_INPRO DARREC1_UNSUC_...

Страница 222: ...BR1_MON_ALM SSCBR1_PRES_ALM SSCBR1_PRES_LO GUID 1EC6CBD8 1531 47A1 811C A5BCA7136B96 V1 EN Figure 304 Circuit breaker conditioning monitoring function OR B1 B2 O OR6 B1 B2 B3 B4 B5 B6 O OR6 B1 B2 B3 B4 B5 B6 O SSCBR1_TRV_T_OP_ALM SSCBR1_TRV_T_CL_ALM SSCBR1_SPR_CHR_ALM SSCBR1_OPR_ALM SSCBR1_OPR_LO SSCBR1_IPOW_ALM SSCBR1_IPOW_LO SSCBR1_CB_LIFE_ALM SSCBR1_MON_ALM SSCBR1_PRES_ALM SSCBR1_PRES_LO SSCBR1...

Страница 223: ...90 7A0049C425F1 V1 EN Figure 308 Logic for blocking of trip circuit supervision 3 9 3 4 Functional diagrams for control and interlocking Two types of disconnector and earthing switch function blocks are available DCSXSWI1 3 and ESSXSWI1 2 are status only type and DCXSWI1 2 and ESXSWI1 are controllable type By default the status only blocks are connected in a standard configuration The disconnector...

Страница 224: ... The SYNC_ITL_BYP input can be used for example to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position SYNC_ITL_BYP overrides for example active interlocking conditions when the circuit breaker truck is closed in service position Connect the additional signals required for the application for closing and opening of circuit breaker CBXCBR1 POSOPEN...

Страница 225: ...ing the closing of circuit breaker These conditions cannot be bypassed using bypass feature of the function OR6 B1 B2 B3 B4 B5 B6 O CBXCBR1_BLK_CLOSE T1PTTR1_BLK_CLOSE GUID 3E75311B A42A 4A5D 9122 D93FBD773BB3 V1 EN Figure 315 Circuit breaker 1 close blocking logic The configuration includes the logic for generating circuit breaker external closing and opening command with the IED in local or remo...

Страница 226: ...voltage inputs to the IED are measured by three phase voltage measurement VMMXU1 The three phase current input is connected to the X131 X132 and X133 card in the back panel for three phases The sequence voltage measurement VSMSQI1 measures the sequence voltage and the residual voltage measurement RESVMMXU1 measures the residual voltage The measurements can be seen in the LHMI and they are availabl...

Страница 227: ...9 AF57 8327612D3032 V1 EN Figure 322 Voltage measurement Sequence voltage measurement FMMXU1 GUID A5958CA9 4CAF 4518 B84C 6F3E5817D46A V1 EN Figure 323 Other measurement Frequency measurement PEMMXU1 RSTACM GUID EC25EDC8 164C 498D A5D0 C60FB8898060 V1 EN Figure 324 Other measurement Three phase power and energy measurement FLTRFRC1 BLOCK CB_CLRD GUID 72ACB664 009C 4165 9C87 8CBC45ABCF9E V2 EN Figu...

Страница 228: ... BIO H X110 Input 1 X110 BIO X110 Input 3 X110 BIO H X110 Input 2 X110 BIO H X110 Input 7 X110 BIO X110 Input 1 X110 BIO X110 Input 2 X110 BIO H X110 Input 5 X110 BIO H X110 Input 3 X110 BIO H X110 Input 8 X110 BIO X110 Input 5 X110 BIO X110 Input 8 X110 BIO X110 Input 6 X110 BIO H X110 Input 4 X110 BIO H X110 Input 6 X110 BIO X110 Input 7 X110 BIO X110 Input 4 GUID A2B1E62C 7697 4D30 8D2A D05174C...

Страница 229: ...5F194C9 0208 467C A115 6BF12F28FDA5 V1 EN Figure 328 Default binary output X110 CCBRBRF1_TRBU TRPPTRC2_TRIP CB_CLOSE_COMMAND CB_OPEN_COMMAND GENERAL_START_PULSE GENERAL_OPERATE_PULSE X100 PSM X100 PO1 X100 PSM X100 PO2 X100 PSM X100 SO1 X100 PSM X100 SO2 X100 PSM X100 PO3 X100 PSM X100 PO4 GUID 6A66701A 488B 4A27 8447 3F325B846D43 V1 EN Figure 329 Default binary output X100 1MRS756378 S Section 3 ...

Страница 230: ... B1 B2 O PHIPTOC1_OPERATE EFHPTOC1_OPERATE PSPTUV1_OPERATE NSPTOV1_OPERATE PDNSPTOC1_OPERATE PHPTOV_OPERATE PHPTUV_OPERATE DPHxPDOC_OPERATE ROVPTOV_OPERATE DEFxPDEF_OPERATE EFPADM_OPERATE WPWDE_OPERATE T1PTTR1_ALARM NSPTOC_OPERATE GUID 5B504FC4 612E 4D4C 8762 154A53926CD7 V2 EN Section 3 1MRS756378 S REF615 standard configurations 224 REF615 Application Manual ...

Страница 231: ...ludes overcurrent operate earth fault operate and voltage operate logic The operate logics are connected to minimum pulse timer TPGAPC for setting the minimum pulse length for the outputs The output from TPGAPC is connected to the binary outputs TPGAPC2 IN1 IN2 OUT1 OUT2 OR6 B1 B2 B3 B4 B5 B6 O OR B1 B2 O OC_OPERATE_PULSE EF_OPERATE_PULSE PHIPTOC1_OPERATE EFHPTOC1_OPERATE DPHxPDOC_OPERATE DEFxPDEF...

Страница 232: ... Applications The standard configuration for non directional overcurrent and non directional earth fault protection with phase voltage based measurements undervoltage and overvoltage protection frequency protection and measurement functions is mainly intended for cable and overhead line feeder applications in directly or resistance earthed distribution networks The IED with a standard configuratio...

Страница 233: ...l Symmetrical components 4 5 Analog interface types 1 Current transformer Voltage transformer 1 Conventional transformer inputs ALSO AVAILABLE Disturbance and fault recorders Event log and recorded data High Speed Output module optional Local Remote push button on LHMI Self supervision Time synchronization IEEE 1588 v2 SNTP IRIG B User management Web HMI 1 2 3 1 2 3I 51P 1 2 3I 51P 2 SYNC 25 O I 7...

Страница 234: ...X100 PO2 Breaker failure backup trip to upstream breaker X100 SO1 General start indication X100 SO2 General operate indication X100 PO3 Open circuit breaker trip coil 1 X100 PO4 Open circuit breaker trip coil 2 X110 SO1 Upstream overcurrent blocking X110 SO2 Overcurrent operate alarm X110 SO3 Earth fault operate alarm X110 SO4 Voltage protection operate alarm X110 HSO1 Arc protection instance 1 op...

Страница 235: ...D text Level trigger mode 1 PHLPTOC1 start Positive or Rising 2 PHHPTOC1 start Positive or Rising 3 PHHPTOC2 start Positive or Rising 4 PHIPTOC1 start Positive or Rising 5 NSPTOC1 start Positive or Rising 6 NSPTOC2 start Positive or Rising 7 EFLPTOC1 start Positive or Rising 8 EFLPTOC2 start Positive or Rising 9 EFHPTOC1 start Positive or Rising 10 EFIPTOC1 start Positive or Rising 11 PDNSPTOC1 st...

Страница 236: ...e PHLPTOC1 operate 27 NSPTOC1 operate Level trigger off NSPTOC2 operate 28 EFLPTOC1 operate Level trigger off EFLPTOC2 operate EFHPTOC1 operate EFIPTOC1 operate 29 EFHPTOC1 operate Level trigger off 30 PDNSPTOC1 operate Level trigger off 31 INRPHAR1 blk2h Level trigger off 32 PHPTOV1 operate Level trigger off PHPTOV2 operate PHPTOV3 operate 33 PHPTUV1 operate Level trigger off PHPTUV2 operate PHPT...

Страница 237: ...application requirements The analog channels have fixed connections to the different function blocks inside the IED s standard configuration However the 12 analog channels available for the disturbance recorder function are freely selectable as a part of the disturbance recorder s parameter settings The phase currents to the IED are fed from a current transformer The residual current to the IED is...

Страница 238: ...PHLPTOC1_OPERATE PHLPTOC1_OPERATE PHHPTOC1_OPERATE PHHPTOC1_OPERATE PHHPTOC2_OPERATE PHHPTOC2_OPERATE PHLPTOC1_START PHHPTOC1_START PHHPTOC2_START PHIPTOC1_START X120_BI1_EXT_OC_BLOCKING PHxPTOC_OPERATE GUID 4418FE50 A21E 4DA3 B13C 97D408EB4CFA V1 EN Figure 334 Overcurrent protection function The upstream blocking from the start of the second high stage of three phase non directional overcurrent p...

Страница 239: ...phase unbalance Both negative sequence overcurrent protections are blocked in case of detection of a failure in secondary circuit of current transformer NSPTOC1 BLOCK ENA_MULT OPERATE START NSPTOC2 BLOCK ENA_MULT OPERATE START OR B1 B2 O NSPTOC1_OPERATE NSPTOC1_OPERATE NSPTOC2_OPERATE NSPTOC2_OPERATE NSPTOC1_START NSPTOC2_START CCSPVC1_FAIL CCSPVC1_FAIL NSPTOC_OPERATE GUID 7C84F97A 94E1 4D1F 87CD ...

Страница 240: ...transformer PDNSPTOC1 BLOCK OPERATE START PDNSPTOC1_OPERATE PDNSPTOC1_START CCSPVC1_FAIL GUID 816DE51C 0F1F 4CD9 AA1B 8D88BB8490D7 V2 EN Figure 339 Phase discontinuity protection function Circuit breaker failure protection CCBRBRF1 is initiated via the START input by number of different protection functions available in the IED The breaker failure protection function offers different operating mod...

Страница 241: ...re included as an optional function The arc protection offers individual function blocks for three arc sensors that can be connected to the IED Each arc protection function block has two different operation modes that is with or without the phase and residual current check The operate signals from ARCSARC1 3 are connected to both trip logic TRPPTRC1 and TRPPTRC2 If the IED has been ordered with hi...

Страница 242: ...TE RST_LKOUT TRIP CL_LKOUT TRPPTRC3_TRIP TRPPTRC4_TRIP TRPPTRC5_TRIP ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE X120_BI4_RST_LOCKOUT X120_BI4_RST_LOCKOUT X120_BI4_RST_LOCKOUT GUID F549336F F636 4F32 8619 BC69E5A53259 V1 EN Figure 341 Arc protection with dedicated HSO The optional autoreclosing function is configured to be initiated by operate signals from a number of protection stages thro...

Страница 243: ...EN_CB CLOSE_CB CMD_WAIT INPRO LOCKED PROT_CRD UNSUC_RECL AR_ON READY ACTIVE OR6 B1 B2 B3 B4 B5 B6 O OR6 B1 B2 B3 B4 B5 B6 O OR B1 B2 O X120_BI3_CB_OPENED DARREC1_OPEN_CB DARREC1_CLOSE_CB X110_BI3_GAS_PRESSURE_ALARM X110_BI4_CB_SPRING_CHARGED SECRSYN1_SYNC_OK PHIPTOC1_OPERATE PHHPTOC1_OPERATE NSPTOC1_OPERATE PHHPTOC2_OPERATE NSPTOC2_OPERATE EFLPTOC1_OPERATE EFHPTOC1_OPERATE PDNSPTOC1_OPERATE ARCSAR...

Страница 244: ... Overvoltage protection function PHPTUV1 BLOCK OPERATE START PHPTUV2 BLOCK OPERATE START PHPTUV3 BLOCK OPERATE START OR6 B1 B2 B3 B4 B5 B6 O PHPTUV1_OPERATE PHPTUV1_OPERATE PHPTUV2_OPERATE PHPTUV2_OPERATE PHPTUV3_OPERATE PHPTUV3_OPERATE PHPTUV1_START PHPTUV2_START PHPTUV3_START SEQSPVC1_FUSEF_U SEQSPVC1_FUSEF_U SEQSPVC1_FUSEF_U PHPTUV_OPERATE GUID 98D35F8A 6408 467E 88C2 15475BC6574E V2 EN Figure ...

Страница 245: ...TE ROVPTOV1_START ROVPTOV2_START ROVPTOV3_START ROVPTOV_OPERATE GUID 521EA0D0 2332 4E90 A1FE C405463CDBCF V1 EN Figure 345 Residual overvoltage protection function The selectable underfrequency or overfrequency protection FRPFRQ prevents damage to network components under unwanted frequency conditions The function also contains a selectable rate of change of the frequency gradient protection to de...

Страница 246: ...PERATE FRPFRQ2_OPERATE FRPFRQ1_OPERATE FRPFRQ1_OPERATE FRPFRQ1_START FRPFRQ2_START FRPFRQ3_START FREQUENCY_OPERATE GUID 9C73EAD7 5797 4E5A BDBB D3734BF1D8DB V1 EN Figure 346 Frequency protection function General start and operate signals from all the functions are connected to minimum pulse timer TPGAPC1 for setting the minimum pulse length for the outputs The output from TPGAPC1 is connected to b...

Страница 247: ...2_START EFLPTOC1_START EFLPTOC2_START EFHPTOC1_START EFIPTOC1_START PDNSPTOC1_START PHPTOV1_START PHPTOV2_START PHPTOV3_START PHPTUV1_START PHPTUV2_START PHPTUV3_START ROVPTOV1_START ROVPTOV2_START ROVPTOV3_START FRPFRQ1_START FRPFRQ2_START FRPFRQ3_START GUID 71B45E9A 077E 45BD 8306 8D6DDCCE745A V1 EN Figure 347 General start and operate signals The operate signals from the protection functions ar...

Страница 248: ...TOC1_OPERATE EFHPTOC1_OPERATE EFIPTOC1_OPERATE EFLPTOC2_OPERATE PDNSPTOC1_OPERATE X120_BI4_RST_LOCKOUT ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE FRPFRQ3_OPERATE FRPFRQ2_OPERATE FRPFRQ1_OPERATE PHPTOV2_OPERATE PHPTOV3_OPERATE PHPTOV1_OPERATE PHPTUV1_OPERATE PHPTUV3_OPERATE PHPTUV2_OPERATE ROVPTOV1_OPERATE ROVPTOV2_OPERATE ROVPTOV3_OPERATE GUID 640AC68E 4932 4ACF 9AF1 CC6D640F0F7D V1 EN Fig...

Страница 249: ...TOV2_OPERATE PHPTOV3_OPERATE PHPTOV1_OPERATE PHPTUV1_OPERATE PHPTUV3_OPERATE PHPTUV2_OPERATE ROVPTOV1_OPERATE ROVPTOV2_OPERATE ROVPTOV3_OPERATE CCBRBRF1_TRRET GUID 724B2B2B C697 47F3 84DC 5D244CC8725F V1 EN Figure 349 Trip logic TRPPTRC1 3 10 3 2 Functional diagrams for disturbance recorder The START and the OPERATE outputs from the protection stages are routed to trigger the disturbance recorder ...

Страница 250: ...RT EFLPTOC1_START EFLPTOC2_START EFHPTOC1_START EFIPTOC1_START PDNSPTOC1_START PHPTOV1_START PHPTOV2_START PHPTOV3_START PHPTUV1_START PHPTUV2_START PHPTUV3_START ROVPTOV1_START ROVPTOV2_START ROVPTOV3_START FRPFRQ1_START FRPFRQ2_START FRPFRQ3_START X120_BI1_EXT_OC_BLOCKING CCSPVC1_FAIL SEQSPVC1_FUSEF_U ARCSARC1_ARC_FLT_DET ARCSARC2_ARC_FLT_DET ARCSARC3_ARC_FLT_DET INRPHAR1_BLK2H SEQSPVC1_FUSEF_3P...

Страница 251: ...RES_LO OPENPOS INVALIDPOS CLOSEPOS CB_CLOSE_COMMAND CB_OPEN_COMMAND X120_BI3_CB_OPENED X120_BI2_CB_CLOSED X110_BI3_GAS_PRESSURE_ALARM X110_BI4_CB_SPRING_CHARGED CB_SPRING_DISCHARGED SSCBR1_TRV_T_OP_ALM SSCBR1_TRV_T_CL_ALM SSCBR1_SPR_CHR_ALM SSCBR1_OPR_ALM SSCBR1_OPR_LO SSCBR1_IPOW_ALM SSCBR1_IPOW_LO SSCBR1_CB_LIFE_ALM SSCBR1_MON_ALM SSCBR1_PRES_ALM SSCBR1_PRES_LO GUID 3E1BA906 5D1B 4FAC AA2A F6C70...

Страница 252: ... circuit breaker open signal It is assumed that there is no external resistor in the circuit breaker tripping coil circuit connected in parallel with the circuit breaker normally open auxiliary contact Set the parameters for TCSSCBR1 properly TCSSCBR1 BLOCK ALARM TCSSCBR2 BLOCK ALARM OR B1 B2 O TCSSCBR1_ALARM TCSSCBR1_ALARM TCSSCBR2_ALARM TCSSCBR2_ALARM TCSSCBR_BLOCKING TCSSCBR_BLOCKING TCSSCBR_AL...

Страница 253: ...ontrol logic The function is block in case of line side or bus side MCB is open SECRSYN1 BLOCK CL_COMMAND BYPASS SYNC_INPRO SYNC_OK CL_FAIL_AL CMD_FAIL_AL LLDB LLLB DLLB DLDB SECRSYN1_SYNC_OK BLOCK_SECRSYN1 SECRSYN1_SYNC_INPRO SECRSYN1_CL_FAIL_AL SECRSYN1_CMD_FAIL_AL OR B1 B2 O X110_BI1_BUS_VT_MCB_OPEN X110_BI2_LINE_VT_MCB_OPEN BLOCK_SECRSYN1 GUID 1054A5E9 E611 4D4B 82B5 5FD0AFE8CF66 V1 EN Figure ...

Страница 254: ... enabled The SYNC_ITL_BYP input can be used for example to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position SYNC_ITL_BYP overrides for example active interlocking conditions when the circuit breaker truck is closed in service position Connect the additional signals required for the application for closing and opening of circuit breaker CBXCBR1...

Страница 255: ...opening command with the IED in local or remote mode Check the logic for the external circuit breaker closing command and modify it according to the application Connect additional signals for opening and closing of circuit breaker in local or remote mode if applicable for the configuration AND B1 B2 O AND B1 B2 O OR B1 B2 O FALSE FALSE CBXCBR1_AU_CLOSE CONTROL_LOCAL CONTROL_REMOTE GUID 10E8EE71 A6...

Страница 256: ...the settings function blocks can generate low alarm or warning and high alarm or warning signals for the measured current values The frequency measurement FMMXU1 of the power system and the three phase power and energy measurement PEMMXU1 are available Load profile record LDPRLRC1 is included in the measurements sheet LDPRLRC1 offers the ability to observe the loading history of the corresponding ...

Страница 257: ...e phase voltage measurement FMMXU1 GUID C3BCC8EA 4599 44E6 B243 477458BCFD0A V1 EN Figure 374 Other measurement Frequency measurement PEMMXU1 RSTACM GUID FF640519 F00C 4B5E 940A 116E9FDB242B V1 EN Figure 375 Other measurement Three phase power and energy measurement FLTRFRC1 BLOCK CB_CLRD GUID 6EC9DC3E 40D6 4CBE 934E 54413CF6CC00 V2 EN Figure 376 Other measurement Data monitoring LDPRLRC1 RSTMEM M...

Страница 258: ...EN X110 BIO H X110 Input 2 X110 BIO H X110 Input 8 X110 BIO H X110 Input 4 X110 BIO X110 Input 1 X110 BIO X110 Input 2 X110 BIO H X110 Input 5 X110 BIO H X110 Input 7 X110 BIO X110 Input 5 X110 BIO X110 Input 7 X110 BIO H X110 Input 6 X110 BIO X110 Input 3 X110 BIO H X110 Input 1 X110 BIO X110 Input 6 X110 BIO X110 Input 8 X110 BIO X110 Input 4 X110 BIO H X110 Input 3 GUID 02227A18 A1C5 4974 AA2E ...

Страница 259: ... X110 SO1 X110 BIO X110 SO2 X110 BIO X110 SO3 X110 BIO X110 SO4 X110 BIO H X110 HSO1 X110 BIO H X110 HSO2 X110 BIO H X110 HSO3 GUID 971007B0 0D89 4D4A 927A 82E43C25BD24 V1 EN Figure 380 Default binary outputs X110 CB_CLOSE_COMMAND CCBRBRF1_TRBU CB_OPEN_COMMAND TRPPTRC2_TRIP GENERAL_START_PULSE GENERAL_OPERATE_PULSE X100 PSM X100 PO1 X100 PSM X100 PO2 X100 PSM X100 SO1 X100 PSM X100 SO2 X100 PSM X1...

Страница 260: ... O OR B1 B2 O AND B1 B2 O X120_BI3_CB_OPENED SECRSYN1_SYNC_OK PDNSPTOC1_OPERATE PHPTOV_OPERATE PHPTUV_OPERATE FREQUENCY_OPERATE EFxPTOC_OPERATE ROVPTOV_OPERATE PHxPTOC_OPERATE NSPTOC_OPERATE GUID C6926FBC 66DB 4EF0 BFA9 26D9D24FC3DA V2 EN Section 3 1MRS756378 S REF615 standard configurations 254 REF615 Application Manual ...

Страница 261: ...gics The configuration also includes overcurrent operate earth fault operate and combined voltage and frequency operate logic The operate logics are connected to the minimum pulse timer TPGAPC for setting the minimum pulse length for the outputs The output from TPGAPC is connected to the binary outputs TPGAPC2 IN1 IN2 OUT1 OUT2 OR B1 B2 O OC_OPERATE_PULSE EF_OPERATE_PULSE PHxPTOC_OPERATE EFxPTOC_O...

Страница 262: ...rent and directional earth fault protection with phase voltage based measurements undervoltage and overvoltage protection frequency protection and measurement functions is mainly intended for cable and overhead line feeder applications in isolated or resonant earthed distribution networks The configuration also includes additional options for selecting earth fault protection based on admittance wa...

Страница 263: ...nt transformer Voltage transformer 1 Conventional transformer inputs ALSO AVAILABLE Disturbance and fault recorders Event log and recorded data High Speed Output module optional Local Remote push button on LHMI Self supervision Time synchronization IEEE 1588 v2 SNTP IRIG B User management Web HMI 1 2 3 1 2 SYNC 25 O I 79 2 I2 46 3Ith F 49F 3I 50P 51P 3 ARC 50L 50NL Master Trip Lockout relay 94 86 ...

Страница 264: ...X100 PO2 Breaker failure backup trip to upstream breaker X100 SO1 General start indication X100 SO2 General operate indication X100 PO3 Open circuit breaker trip coil 1 X100 PO4 Open circuit breaker trip coil 2 X110 SO1 Upstream overcurrent blocking X110 SO2 Overcurrent operate alarm X110 SO3 Earth fault operate alarm X110 SO4 Voltage protection operate alarm X110 HSO1 Arc protection instance 1 op...

Страница 265: ...mode 1 DPHLPDOC1 start Positive or Rising 2 DPHLPDOC2 start Positive or Rising 3 DPHHPDOC1 start Positive or Rising 4 PHIPTOC1 start Positive or Rising 5 NSPTOC1 start Positive or Rising 6 NSPTOC2 start Positive or Rising 7 DEFLPDEF1 start Positive or Rising 8 DEFLPDEF2 start Positive or Rising 9 DEFHPDEF1 start Positive or Rising 10 INTRPTEF1 start Positive or Rising 11 EFHPTOC1 start Positive or...

Страница 266: ...perate 28 NSPTOC1 operate Level trigger off NSPTOC2 operate 29 DEFHPDEF1 operate Level trigger off DEFLPDEF1 operate DEFLPDEF2 operate 30 INTRPTEF1 operate Level trigger off 31 EFHPTOC1 operate Level trigger off 32 PDNSPTOC1 operate Level trigger off 33 INRPHAR1 blk2h Level trigger off 34 T1PTTR1 operate Level trigger off 35 PHPTOV1 operate Level trigger off PHPTOV2 operate PHPTOV3 operate 36 PHPT...

Страница 267: ...Level trigger off 3 11 3 Functional diagrams The functional diagrams describe the default input output alarm LED and function to function connections The default connections can be viewed and changed with PCM600 according to the application requirements The analog channels have fixed connections to the different function blocks inside the IED s standard configuration However the 12 analog channels...

Страница 268: ...directional overcurrent protection instantaneous stage PHIPTOC1 can be blocked by energizing the binary input X120 BI1 PHIPTOC1 BLOCK ENA_MULT OPERATE START PHIPTOC1_OPERATE PHIPTOC1_START X120_BI1_EXT_OC_BLOCKING GUID B16AE694 A1BF 450D AFA8 BE6CDEC14F31 V1 EN Figure 386 Overcurrent protection function DPHHPDOC1 BLOCK ENA_MULT NON_DIR OPERATE START DPHLPDOC1 BLOCK ENA_MULT NON_DIR OPERATE START D...

Страница 269: ...tages NSPTOC1 and NSPTOC2 are provided for phase unbalance protection These functions are used to protect the feeder against phase unbalance NSPTOC1 BLOCK ENA_MULT OPERATE START NSPTOC2 BLOCK ENA_MULT OPERATE START OR B1 B2 O NSPTOC1_OPERATE NSPTOC1_OPERATE NSPTOC2_OPERATE NSPTOC2_OPERATE NSPTOC1_START NSPTOC2_START NSPTOC_OPERATE GUID 7196E7DF D646 46E6 926E 736FA68E1350 V1 EN Figure 390 Negative...

Страница 270: ...ART DEFLPDEF2_START DEFHPDEF1_START OR6 B1 B2 B3 B4 B5 B6 O DEFHPDEF1_OPERATE DEFLPDEF1_OPERATE DEFLPDEF2_OPERATE DEFxPDEF_OPERATE GUID 935D2178 A838 4D7B BB64 98F1AEB3150A V1 EN Figure 391 Directional earth fault protection function INTRPTEF1 BLOCK OPERATE START BLK_EF INTRPTEF1_OPERATE INTRPTEF1_START GUID D4BE5EE6 0CD3 417E 99C6 88CE3B942A73 V1 EN Figure 392 Transient or intermittent earth faul...

Страница 271: ...N Figure 393 Wattmetric protection function EFPADM1 BLOCK RELEASE OPERATE START EFPADM2 BLOCK RELEASE OPERATE START EFPADM3 BLOCK RELEASE OPERATE START OR6 B1 B2 B3 B4 B5 B6 O EFPADM1_OPERATE EFPADM1_OPERATE EFPADM2_OPERATE EFPADM2_OPERATE EFPADM3_OPERATE EFPADM3_OPERATE EFPADM1_START EFPADM2_START EFPADM3_START EFPADM_OPERATE GUID 02FD43E2 5135 4D7C BFBB C12381B6FAA1 V1 EN Figure 394 Admittance b...

Страница 272: ...conditions The BLK_CLOSE output of the function is used to block the closing operation of circuit breaker T1PTTR1 BLK_OPR ENA_MULT TEMP_AMB OPERATE START ALARM BLK_CLOSE T1PTTR1_BLK_CLOSE T1PTTR1_START T1PTTR1_OPERATE T1PTTR1_ALARM GUID 52DD9079 0F13 411A 8C7E B5A89065765E V1 EN Figure 397 Thermal overcurrent protection function Circuit breaker failure protection CCBRBRF1 is initiated via the STAR...

Страница 273: ...RC1 3 stages are included as an optional function The arc protection offers individual function blocks for three arc sensors that can be connected to the IED Each arc protection function block has two different operation modes that is with or without the phase and residual current check The operate signals from ARCSARC1 3 are connected to both trip logic TRPPTRC1 and TRPPTRC2 If the IED has been o...

Страница 274: ...TE RST_LKOUT TRIP CL_LKOUT TRPPTRC3_TRIP TRPPTRC4_TRIP TRPPTRC5_TRIP ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE X120_BI4_RST_LOCKOUT X120_BI4_RST_LOCKOUT X120_BI4_RST_LOCKOUT GUID B7398C9F D767 4749 8AC2 149EEE9F478D V1 EN Figure 399 ARC protection with dedicated HSO The optional autoreclosing function is configured to be initiated by operate signals from a number of protection stages thro...

Страница 275: ... B4 B5 B6 O OR B1 B2 O X120_BI3_CB_OPENED DARREC1_OPEN_CB DARREC1_CLOSE_CB X110_BI3_GAS_PRESSURE_ALARM X110_BI4_CB_SPRING_CHARGED SECRSYN1_SYNC_OK PHIPTOC1_OPERATE DPHLPDOC2_OPERATE DPHHPDOC1_OPERATE NSPTOC1_OPERATE NSPTOC2_OPERATE EFPADM2_OPERATE EFPADM3_OPERATE INTRPTEF1_OPERATE PDNSPTOC1_OPERATE DEFHPDEF1_OPERATE DEFLPDEF2_OPERATE WPWDE2_OPERATE WPWDE3_OPERATE ARCSARC1_OPERATE ARCSARC2_OPERATE ...

Страница 276: ... Overvoltage protection function PHPTUV1 BLOCK OPERATE START PHPTUV2 BLOCK OPERATE START PHPTUV3 BLOCK OPERATE START OR6 B1 B2 B3 B4 B5 B6 O PHPTUV1_OPERATE PHPTUV1_OPERATE PHPTUV2_OPERATE PHPTUV2_OPERATE PHPTUV3_OPERATE PHPTUV3_OPERATE PHPTUV1_START PHPTUV2_START PHPTUV3_START SEQSPVC1_FUSEF_U SEQSPVC1_FUSEF_U SEQSPVC1_FUSEF_U PHPTUV_OPERATE GUID 1FD21003 8B8B 4C27 8C36 6E6B7785DCA7 V2 EN Figure ...

Страница 277: ...CK OPERATE START NSPTOV1_OPERATE NSPTOV1_START SEQSPVC1_FUSEF_U GUID C1F46B39 F8B7 410A 8EB2 3002D4DC009D V2 EN Figure 404 Negative sequence overvoltage protection function PSPTUV1 BLOCK OPERATE START PSPTUV1_OPERATE PSPTUV1_START SEQSPVC1_FUSEF_U GUID 8D6416CF 9503 48F1 8B0E 82AFB0C0828B V2 EN Figure 405 Positive sequence undervoltage protection function The selectable under frequency or over fre...

Страница 278: ...PERATE FRPFRQ2_OPERATE FRPFRQ1_OPERATE FRPFRQ1_OPERATE FRPFRQ1_START FRPFRQ2_START FRPFRQ3_START FREQUENCY_OPERATE GUID A37BDC66 1D13 4782 8EDA B6A0E6BF51AF V1 EN Figure 406 Frequency protection function General start and operate signals from all the functions are connected to minimum pulse timer TPGAPC1 for setting the minimum pulse length for the outputs The output from TPGAPC1 is connected to b...

Страница 279: ...HPDOC1_START PHIPTOC1_START NSPTOC1_START NSPTOC2_START DEFLPDEF1_START DEFLPDEF2_START DEFHPDEF1_START INTRPTEF1_START EFHPTOC1_START PDNSPTOC1_START PHPTOV1_START PHPTOV2_START PHPTOV3_START PSPTUV1_START NSPTOV1_START PHPTUV1_START PHPTUV2_START PHPTUV3_START ROVPTOV1_START ROVPTOV2_START ROVPTOV3_START EFPADM1_START EFPADM2_START EFPADM3_START WPWDE1_START WPWDE2_START WPWDE3_START FRPFRQ1_STA...

Страница 280: ...E PDNSPTOC1_OPERATE ROVPTOV1_OPERATE ROVPTOV2_OPERATE ROVPTOV3_OPERATE DEFHPDEF1_OPERATE DEFLPDEF1_OPERATE DEFLPDEF2_OPERATE EFHPTOC1_OPERATE WPWDE1_OPERATE WPWDE2_OPERATE WPWDE3_OPERATE PHPTOV1_OPERATE PHPTOV2_OPERATE PHPTOV3_OPERATE PHPTUV1_OPERATE PSPTUV1_OPERATE NSPTOV1_OPERATE PHPTUV2_OPERATE PHPTUV3_OPERATE ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE FRPFRQ1_OPERATE FRPFRQ2_OPERATE FR...

Страница 281: ... ARCSARC2_OPERATE ARCSARC3_OPERATE FRPFRQ1_OPERATE FRPFRQ2_OPERATE FRPFRQ3_OPERATE X120_BI4_RST_LOCKOUT CCBRBRF1_TRRET GUID F96CA689 B27A 4743 B3FF 9622054B771F V1 EN Figure 409 Trip logic TRPPTRC1 3 11 3 2 Functional diagrams for disturbance recorder The START and the OPERATE outputs from the protection stages are routed to trigger the disturbance recorder or alternatively only to be recorded by ...

Страница 282: ...START NSPTOC2_START DEFLPDEF1_START DEFLPDEF2_START DEFHPDEF1_START INTRPTEF1_START EFHPTOC1_START PDNSPTOC1_START PHPTOV1_START PHPTOV2_START PHPTOV3_START PSPTUV1_START NSPTOV1_START PHPTUV1_START PHPTUV2_START PHPTUV3_START ROVPTOV1_START ROVPTOV2_START ROVPTOV3_START FRPFRQ1_START FRPFRQ2_START FRPFRQ3_START X120_BI1_EXT_OC_BLOCKING SEQSPVC1_FUSEF_U T1PTTR1_START INRPHAR1_BLK2H SEQSPVC1_FUSEF_...

Страница 283: ... PRES_LO OPENPOS INVALIDPOS CLOSEPOS CB_CLOSE_COMMAND CB_OPEN_COMMAND X120_BI3_CB_OPENED X120_BI2_CB_CLOSED X110_BI3_GAS_PRESSURE_ALARM X110_BI4_CB_SPRING_CHARGED CB_SPRING_DISCHARGED SSCBR1_TRV_T_OP_ALM SSCBR1_TRV_T_CL_ALM SSCBR1_SPR_CHR_ALM SSCBR1_OPR_ALM SSCBR1_OPR_LO SSCBR1_IPOW_ALM SSCBR1_IPOW_LO SSCBR1_CB_LIFE_ALM SSCBR1_MON_ALM SSCBR1_PRES_ALM SSCBR1_PRES_LO GUID A891CCB2 2E51 4E87 9F7E E0A...

Страница 284: ... circuit breaker open signal It is assumed that there is no external resistor in the circuit breaker tripping coil circuit connected in parallel with the circuit breaker normally open auxiliary contact Set the parameters for TCSSCBR1 properly TCSSCBR1 BLOCK ALARM TCSSCBR2 BLOCK ALARM OR B1 B2 O TCSSCBR1_ALARM TCSSCBR1_ALARM TCSSCBR2_ALARM TCSSCBR2_ALARM TCSSCBR_BLOCKING TCSSCBR_BLOCKING TCSSCBR_AL...

Страница 285: ... logic The function is blocked in case if line side or bus side MCB is open SECRSYN1 BLOCK CL_COMMAND BYPASS SYNC_INPRO SYNC_OK CL_FAIL_AL CMD_FAIL_AL LLDB LLLB DLLB DLDB SECRSYN1_SYNC_OK BLOCK_SECRSYN1 SECRSYN1_SYNC_INPRO SECRSYN1_CL_FAIL_AL SECRSYN1_CMD_FAIL_AL OR B1 B2 O X110_BI1_BUS_VT_MCB_OPEN X110_BI2_LINE_VT_MCB_OPEN BLOCK_SECRSYN1 GUID 48E8F4CC 1F3E 43F5 AC2A FBB39A7AF789 V1 EN Figure 418 ...

Страница 286: ...ple to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position SYNC_ITL_BYP overrides for example active interlocking conditions when the circuit breaker truck is closed in service position CBXCBR1 POSOPEN POSCLOSE ENA_OPEN ENA_CLOSE BLK_OPEN BLK_CLOSE AU_OPEN AU_CLOSE TRIP SYNC_OK SYNC_ITL_BYP SELECTED EXE_OP EXE_CL OP_REQ CL_REQ OPENPOS CLOSEPOS OK...

Страница 287: ...ese conditions cannot be bypassed using bypass feature of the function OR6 B1 B2 B3 B4 B5 B6 O CBXCBR1_BLK_CLOSE T1PTTR1_BLK_CLOSE GUID 2B6B90C1 0B92 4F9F B391 FDB2B58C31CE V1 EN Figure 425 Circuit breaker 1 close blocking logic The configuration includes logic for generating circuit breaker external closing and opening command with the IED in local or remote mode Check the logic for the external ...

Страница 288: ...ard in the back panel The sequence voltage measurement VSMSQI1 measures the sequence voltage and the residual voltage measurement RESVMMXU1 measures the residual voltage The measurements can be seen from the LHMI and they are available under the measurement option in the menu selection Based on the settings function blocks can generate low alarm or warning and high alarm or warning signals for the...

Страница 289: ... HIGH_WARN LOW_WARN LOW_ALARM GUID D77A125E DEFF 46DA 8A1B 26E8E0A01888 V1 EN Figure 431 Voltage measurement Three phase voltage measurement VSMSQI1 GUID 058480EF 6AA8 4109 ABF4 843B260EAB37 V1 EN Figure 432 Voltage measurement Sequence voltage measurement RESVMMXU1 BLOCK HIGH_ALARM HIGH_WARN GUID 9581AEE9 F675 455C AA48 63283CB8C97C V1 EN Figure 433 Voltage measurement Residual voltage measuremen...

Страница 290: ...r measurement Three phase power and energy measurement FLTRFRC1 BLOCK CB_CLRD GUID 114B06B5 7D33 47B0 9907 7F19931CBA43 V2 EN Figure 437 Other measurement Data monitoring LDPRLRC1 RSTMEM MEM_WARN MEM_ALARM GUID 6906C86B 8A41 453A B2AF E24B37B288BF V2 EN Figure 438 Other measurement Load profile record Section 3 1MRS756378 S REF615 standard configurations 284 REF615 Application Manual ...

Страница 291: ...EN X110 BIO X110 Input 4 X110 BIO H X110 Input 8 X110 BIO H X110 Input 5 X110 BIO X110 Input 7 X110 BIO X110 Input 6 X110 BIO X110 Input 8 X110 BIO H X110 Input 6 X110 BIO X110 Input 1 X110 BIO X110 Input 5 X110 BIO H X110 Input 2 X110 BIO H X110 Input 7 X110 BIO H X110 Input 4 X110 BIO H X110 Input 3 X110 BIO X110 Input 3 X110 BIO H X110 Input 1 X110 BIO X110 Input 2 GUID 61427C3B 4892 4EB7 843C ...

Страница 292: ... X110 SO1 X110 BIO X110 SO2 X110 BIO X110 SO3 X110 BIO X110 SO4 X110 BIO H X110 HSO1 X110 BIO H X110 HSO2 X110 BIO H X110 HSO3 GUID 33084EAB 5DF1 4A70 BF4D 95AE4156AA4E V1 EN Figure 441 Default binary outputs X110 CB_CLOSE_COMMAND CCBRBRF1_TRBU CB_OPEN_COMMAND TRPPTRC2_TRIP GENERAL_START_PULSE GENERAL_OPERATE_PULSE X100 PSM X100 PO1 X100 PSM X100 PO2 X100 PSM X100 SO1 X100 PSM X100 SO2 X100 PSM X1...

Страница 293: ...heet contains programmable LED function blocks with initialization logic If any LED function block is missing insert it from the object library 1MRS756378 S Section 3 REF615 standard configurations REF615 287 Application Manual ...

Страница 294: ...I3_CB_OPENED SECRSYN1_SYNC_OK PHIPTOC1_OPERATE INTRPTEF1_OPERATE PDNSPTOC1_OPERATE EFHPTOC1_OPERATE PSPTUV1_OPERATE NSPTOV1_OPERATE DPHxPDOC_OPERATE DEFxPDEF_OPERATE ROVPTOV_OPERATE PHPTUV_OPERATE PHPTOV_OPERATE FREQUENCY_OPERATE T1PTTR1_ALARM NSPTOC_OPERATE GUID 895A1F18 B4D8 473A 9B7F 4E8348D4A8FB V2 EN Section 3 1MRS756378 S REF615 standard configurations 288 REF615 Application Manual ...

Страница 295: ...ate earth fault operate and combined voltage and frequency operate logic The operate logics are connected to the minimum pulse timer TPGAPC for setting the minimum pulse length for the outputs The output from TPGAPC is connected to the binary outputs OR B1 B2 O OR6 B1 B2 B3 B4 B5 B6 O TPGAPC2 IN1 IN2 OUT1 OUT2 OC_OPERATE_PULSE EF_OPERATE_PULSE PHIPTOC1_OPERATE INTRPTEF1_OPERATE EFHPTOC1_OPERATE DP...

Страница 296: ...fault protection with phase voltage based measurements high impendance restricted earth fault protection undervoltage and overvoltage protection frequency protection and measurement functions is mainly intended for cable and overhead line feeder applications in isolated or resonant earthed distribution networks The configuration also includes additional options for selecting earth fault protection...

Страница 297: ... interface types 1 Current transformer Voltage transformer 1 Conventional transformer inputs ALSO AVAILABLE Disturbance and fault recorders Event log and recorded data High Speed Output module optional Local Remote push button on LHMI Self supervision Time synchronization IEEE 1588 v2 SNTP IRIG B User management Web HMI 1 2 3 1 2 3I 51P 1 3I 51P 2 SYNC 25 O I 79 2 I2 46 3I 50P 51P 3 ARC 50L 50NL M...

Страница 298: ...uit breaker X100 PO2 Breaker failure backup trip to upstream breaker X100 SO1 General start indication X100 SO2 General operate indication X100 PO3 Open circuit breaker trip coil 1 X100 PO4 Open circuit breaker trip coil 2 or EFLPTOC2 operated X110 SO1 X110 SO2 Overcurrent operate alarm X110 SO3 Earth fault operate alarm X110 SO4 Voltage or frequency protection operate alarm X110 HSO1 Arc protecti...

Страница 299: ...Channel ID text Level trigger mode 1 PHLPTOC1 start Positive or Rising 2 PHHPTOC1 start Positive or Rising 3 PHIPTOC1 start Positive or Rising 4 DPHLPDOC1 start Positive or Rising 5 DPHHPDOC1 start Positive or Rising 6 NSPTOC1 start Positive or Rising 7 NSPTOC2 start Positive or Rising 8 EFLPTOC1 start Positive or Rising 9 EFLPTOC2 start Positive or Rising 10 EFHPTOC1 start Positive or Rising 11 E...

Страница 300: ...e Level trigger off DPHHPDOC1 operate 29 NSPTOC1 operate Level trigger off NSPTOC2 operate 30 EFLPTOC1 operate Level trigger off EFLPTOC2 operate EFHPTOC1 operate EFIPTOC1 operate 31 DEFLPDEF1 operate Level trigger off DEFHPDEF1 operate 32 T1PTTR1 operate Level trigger off 33 INRPHAR1 blk2h Level trigger off 34 PHPTOV1 operate Level trigger off PHPTOV2 operate 35 PHPTUV1 operate Level trigger off ...

Страница 301: ...rements The analog channels have fixed connections to the different function blocks inside the IED s standard configuration However the 12 analog channels available for the disturbance recorder function are freely selectable as a part of the disturbance recorder s parameter settings The phase currents to the IED are fed from a current transformer The residual current to the IED is fed from either ...

Страница 302: ..._MULT OPERATE START PHLPTOC1_OPERATE PHLPTOC1_START OR6 B1 B2 B3 B4 B5 B6 O PHIPTOC1_OPERATE PHLPTOC1_OPERATE PHHPTOC1_OPERATE PHxPTOC_OPERATE PHIPTOC1 BLOCK ENA_MULT OPERATE START PHIPTOC1_OPERATE PHIPTOC1_START X130_BI1_EXT_OC_BLOCKING GUID BD0A9F06 B0A0 4DA9 B6C7 FDED4A790786 V1 EN Figure 447 Overcurrent protection function DPHHPDOC1 BLOCK ENA_MULT NON_DIR OPERATE START DPHLPDOC1 BLOCK ENA_MULT...

Страница 303: ...e blocked in case of detection in failure in secondary circuit of current transformer NSPTOC1 BLOCK ENA_MULT OPERATE START NSPTOC2 BLOCK ENA_MULT OPERATE START OR B1 B2 O NSPTOC1_OPERATE NSPTOC1_OPERATE NSPTOC2_OPERATE NSPTOC2_OPERATE NSPTOC1_START NSPTOC2_START CCSPVC1_FAIL CCSPVC1_FAIL NSPTOC_OPERATE GUID 6143300A A295 45FC A14A D0F05747F5E5 V2 EN Figure 450 Negative sequence overcurrent protect...

Страница 304: ...PTOC1_START EFIPTOC1_START EFxPTOC_OPERATE GUID 352E2951 3663 401F BC95 B122314EFA0C V1 EN Figure 451 Earth fault protection function DEFLPDEF1 BLOCK ENA_MULT RCA_CTL OPERATE START DEFLPDEF1_OPERATE DEFLPDEF1_START OR B1 B2 O DEFHPDEF1_OPERATE DEFLPDEF1_OPERATE DEFxPDEF_OPERATE DEFHPDEF1 BLOCK ENA_MULT RCA_CTL OPERATE START DEFHPDEF1_OPERATE DEFHPDEF1_START GUID 2075A819 3231 435A B225 58D2867B062...

Страница 305: ...d those needs to be connected as per application need SCEFRFLO1 BLOCK TRIGG TRIGG_XC0F ALARM OR6 B1 B2 B3 B4 B5 B6 O OR B1 B2 O EFLPTOC2_OPERATE PHIPTOC1_OPERATE PHLPTOC1_OPERATE PHHPTOC1_OPERATE EFLPTOC1_OPERATE EFHPTOC1_OPERATE EFIPTOC1_OPERATE GUID 129824AC 339E 453E A209 6C2D79259970 V1 EN Figure 455 Fault locator function Circuit breaker failure protection CCBRBRF1 is initiated via the START ...

Страница 306: ...E DEFLPDEF1_OPERATE CCBRBRF1_TRRET GUID A6BB61D9 2267 4355 866D 55408AF32653 V1 EN Figure 456 Circuit breaker failure protection function Three arc protection ARCSARC1 3 stages are included as an optional function The arc protection offers individual function blocks for three arc sensors that can be connected to the IED Each arc protection function block has two different operation modes that is w...

Страница 307: ...RATE RST_LKOUT TRIP CL_LKOUT TRPPTRC4 BLOCK OPERATE RST_LKOUT TRIP CL_LKOUT TRPPTRC5 BLOCK OPERATE RST_LKOUT TRIP CL_LKOUT TRPPTRC3_TRIP TRPPTRC4_TRIP TRPPTRC5_TRIP ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE X130_BI4_RST_LOCKOUT X130_BI4_RST_LOCKOUT X130_BI4_RST_LOCKOUT GUID AFC36F56 2F9B 4C33 8C04 2116CFD0297A V1 EN Figure 458 Arc protection with dedicated HSO The optional autoreclosing f...

Страница 308: ...IT_4 BLK_RECL_T BLK_RCLM_T BLK_THERM CB_POS CB_READY INC_SHOTP INHIBIT_RECL RECL_ON SYNC OPEN_CB CLOSE_CB CMD_WAIT INPRO LOCKED PROT_CRD UNSUC_RECL AR_ON READY ACTIVE OR6 B1 B2 B3 B4 B5 B6 O OR6 B1 B2 B3 B4 B5 B6 O OR B1 B2 O DARREC1_OPEN_CB DARREC1_CLOSE_CB X130_BI3_CB_OPENED X110_BI3_GAS_PRESSURE_ALARM X110_BI4_CB_SPRING_CHARGED SECRSYN1_SYNC_OK PHIPTOC1_OPERATE PHHPTOC1_OPERATE EFLPTOC1_OPERATE...

Страница 309: ...TR1_OPERATE CBXCBR1_SELECTED DARREC1_INPRO DARREC1_UNSUC_RECL GUID 873C22AC CAFC 429D AD5B A1CA03F9E526 V1 EN Figure 460 Overvoltage protection function PHPTUV1 BLOCK OPERATE START PHPTUV2 BLOCK OPERATE START OR B1 B2 O PHPTUV1_OPERATE PHPTUV1_OPERATE PHPTUV2_OPERATE PHPTUV2_OPERATE PHPTUV1_START PHPTUV2_START SEQSPVC1_FUSEF_U SEQSPVC1_FUSEF_U PHPTUV_OPERATE Grouped function operate GUID F2B553C3 ...

Страница 310: ...n function The selectable underfrequency or overfrequency protection FRPFRQ prevents damage to network components under unwanted frequency conditions The function also contains a selectable rate of change of the frequency gradient protection to detect an increase or decrease in the fast power system frequency at an early stage This can be used as an early indication of a disturbance in the system ...

Страница 311: ...PERATE FRPFRQ2_OPERATE FRPFRQ1_OPERATE FRPFRQ1_OPERATE FRPFRQ1_START FRPFRQ2_START FRPFRQ3_START FREQUENCY_OPERATE GUID 9DB8C268 09ED 4691 97DE 09B32356C078 V1 EN Figure 463 Frequency protection function General start and operate signals from all the functions are connected to minimum pulse timer TPGAPC1 for setting the minimum pulse length for the outputs The output from TPGAPC1 is connected to b...

Страница 312: ...OV1_START PHPTOV2_START PHPTUV1_START PHPTUV2_START ROVPTOV1_START ROVPTOV2_START FRPFRQ1_START FRPFRQ2_START FRPFRQ3_START HREFPDIF1_START PHIPTOC1_START DPHHPDOC1_START DPHLPDOC1_START EFIPTOC1_START DEFHPDEF1_START DEFLPDEF1_START T1PTTR1_START NSPTOC1_START NSPTOC2_START GUID 29DD10F3 A445 41EC 825E B0DDAF31F9EF V1 EN Figure 464 General start and operate signals The operate signals from the pr...

Страница 313: ...BI4_RST_LOCKOUT FRPFRQ3_OPERATE FRPFRQ2_OPERATE FRPFRQ1_OPERATE PHPTOV2_OPERATE PHPTOV1_OPERATE PHPTUV1_OPERATE PHPTUV2_OPERATE ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE NSPTOC1_OPERATE NSPTOC2_OPERATE DPHHPDOC1_OPERATE DPHLPDOC1_OPERATE T1PTTR1_OPERATE HREFPDIF1_OPERATE ROVPTOV2_OPERATE ROVPTOV1_OPERATE DEFHPDEF1_OPERATE DEFLPDEF1_OPERATE GUID 1BC54F36 8AC5 4EB7 AA07 F0067D846955 V1 EN F...

Страница 314: ...ERATE DPHHPDOC1_OPERATE DPHLPDOC1_OPERATE T1PTTR1_OPERATE HREFPDIF1_OPERATE ROVPTOV2_OPERATE ROVPTOV1_OPERATE DEFHPDEF1_OPERATE DEFLPDEF1_OPERATE CCBRBRF1_TRRET GUID 8F89045C 9F78 4696 AC8F 4B261C696B3E V1 EN Figure 466 Trip logic TRPPTRC2 3 12 3 2 Functional diagrams for disturbance recorder The START and the OPERATE outputs from the protection stages are routed to trigger the disturbance recorde...

Страница 315: ...TART PHPTUV2_START ROVPTOV1_START ROVPTOV2_START FRPFRQ1_START FRPFRQ2_START FRPFRQ3_START HREFPDIF1_START PHIPTOC1_START DPHHPDOC1_START DPHLPDOC1_START EFIPTOC1_START DEFHPDEF1_START DEFLPDEF1_START T1PTTR1_START NSPTOC1_START NSPTOC2_START X130_BI1_EXT_OC_BLOCKING CCSPVC1_FAIL SEQSPVC1_FUSEF_U ARCSARC1_ARC_FLT_DET ARCSARC2_ARC_FLT_DET ARCSARC3_ARC_FLT_DET INRPHAR1_BLK2H SEQSPVC1_FUSEF_3PH SECRS...

Страница 316: ...ED SSCBR1_TRV_T_OP_ALM SSCBR1_TRV_T_CL_ALM SSCBR1_SPR_CHR_ALM SSCBR1_OPR_ALM SSCBR1_OPR_LO SSCBR1_IPOW_ALM SSCBR1_IPOW_LO SSCBR1_CB_LIFE_ALM SSCBR1_MON_ALM SSCBR1_PRES_ALM SSCBR1_PRES_LO GUID 80C77788 4448 4D27 A555 09847AE3A849 V1 EN Figure 470 Circuit breaker condition monitoring function OR B1 B2 O OR6 B1 B2 B3 B4 B5 B6 O OR6 B1 B2 B3 B4 B5 B6 O SSCBR1_TRV_T_OP_ALM SSCBR1_TRV_T_CL_ALM SSCBR1_SP...

Страница 317: ...r blocking trip circuit supervision 3 12 3 4 Functional diagrams for control and interlocking The main purpose of the synchronism and energizing check SECRSYN is to provide control over the closing of the circuit breakers in power networks to prevent the closing if conditions for synchronism are not detected The energizing function allows closing for example when one side of the breaker is dead SE...

Страница 318: ...0_BI8_ES1_OPENED X110_BI7_ES1_CLOSED GUID E115D13F E322 49D5 BF4D C4ADE480305D V1 EN Figure 477 Earthing switch control logic The circuit breaker closing is enabled when the ENA_CLOSE input is activated The input can be activated by the configuration logic which is a combination of the disconnector or breaker truck and earth switch position status status of the trip logics gas pressure alarm circu...

Страница 319: ...for closing and opening coil of circuit breaker OR B1 B2 O CB_CLOSE_COMMAND CBXCBR1_EXE_CL DARREC1_CLOSE_CB GUID 84F9FA17 9CAC 4B05 9BBB 041DCB249220 V1 EN Figure 479 Circuit breaker control logic Signals for closing coil of circuit breaker 1 OR6 B1 B2 B3 B4 B5 B6 O CB_OPEN_COMMAND EFLPTOC2_OPERATE CBXCBR1_EXE_OP TRPPTRC1_TRIP DARREC1_OPEN_CB GUID C5BCF098 8F91 4484 B7C4 C737DF86A0B3 V1 EN Figure ...

Страница 320: ...ing logic The configuration includes logic for generating circuit breaker external closing and opening command with IED in local or remote mode Check the logic for the external circuit breaker closing command and modify it according to the application Connect the additional signals for opening and closing of circuit breaker in local or remote mode if applicable for the configuration AND B1 B2 O AN...

Страница 321: ...VMMXU1 measures the residual voltage The measurements can be seen from the LHMI and they are available under the measurement option in the menu selection Based on the settings function blocks can generate low alarm or warning and high alarm or warning signals for the measured current values The frequency measurement FMMXU1 of the power system and the three phase power and energy measurement PEMMXU...

Страница 322: ...N LOW_WARN LOW_ALARM GUID 7D60D10E C412 4031 A343 6A4BCE7810F8 V1 EN Figure 489 Voltage measurement Three phase voltage measurement VSMSQI1 GUID C3A052EA E5B0 471F 94E1 C49CB0174319 V1 EN Figure 490 Voltage measurement Sequence voltage measurement RESVMMXU1 BLOCK HIGH_ALARM HIGH_WARN GUID DC329C78 B66C 4730 BAE8 22AE407C758F V1 EN Figure 491 Voltage measurement Residual voltage measurement VMMXU2 ...

Страница 323: ...r measurement Three phase power and energy measurement FLTRFRC1 BLOCK CB_CLRD GUID E8A8CC10 4013 4CDD 8526 7BB04BF5F04C V2 EN Figure 495 Other measurement Data monitoring LDPRLRC1 RSTMEM MEM_WARN MEM_ALARM GUID A6EEC867 36F5 4D71 9024 7F71C97AA8B1 V2 EN Figure 496 Other measurement Load profile record 1MRS756378 S Section 3 REF615 standard configurations REF615 317 Application Manual ...

Страница 324: ...X110 BIO X110 Input 8 X110 BIO X110 Input 1 X110 BIO H X110 Input 1 X110 BIO X110 Input 5 X110 BIO X110 Input 4 X110 BIO H X110 Input 4 X110 BIO X110 Input 7 X110 BIO X110 Input 2 X110 BIO H X110 Input 6 X110 BIO H X110 Input 5 X110 BIO H X110 Input 8 X110 BIO X110 Input 3 X110 BIO H X110 Input 3 X110 BIO H X110 Input 7 X110 BIO X110 Input 6 X110 BIO H X110 Input 2 GUID BF5177A7 61AF 4AB5 A41D A11...

Страница 325: ... X110 SO3 X110 BIO X110 SO4 X110 BIO H X110 HSO1 X110 BIO H X110 HSO2 X110 BIO H X110 HSO3 GUID 913C45BD 2D0C 4190 8840 B583CC22480C V1 EN Figure 499 Binary output X110 terminal block OR B1 B2 O CCBRBRF1_TRBU GENERAL_START_PULSE GENERAL_OPERATE_PULSE CB_CLOSE_COMMAND CB_OPEN_COMMAND TRPPTRC2_TRIP EFLPTOC2_OPERATE X100 PSM X100 PO1 X100 PSM X100 PO2 X100 PSM X100 SO1 X100 PSM X100 SO2 X100 PSM X100...

Страница 326: ...T OR B1 B2 O DPHxPDOC_OPERATE PHxPTOC_OPERATE LED3 OK ALARM RESET OR6 B1 B2 B3 B4 B5 B6 O T1PTTR1_OPERATE PHPTOV_OPERATE PHPTUV_OPERATE NSPTOC_OPERATE LED4 OK ALARM RESET AND B1 B2 O X130_BI3_CB_OPENED SECRSYN1_SYNC_OK GUID 656238B5 B8BC 4D19 943B 661853C3E8FC V2 EN Section 3 1MRS756378 S REF615 standard configurations 320 REF615 Application Manual ...

Страница 327: ...ncludes overcurrent operate earth fault operate and combined voltage and frequency operate logic The operate logics are connected to the minimum pulse timer TPGAPC for setting the minimum pulse length for the outputs The output from TPGAPC is connected to the binary outputs OR6 B1 B2 B3 B4 B5 B6 O OR B1 B2 O TPGAPC2 IN1 IN2 OUT1 OUT2 OC_OPERATE_PULSE EF_OPERATE_PULSE HREFPDIF1_OPERATE DPHxPDOC_OPE...

Страница 328: ...ction based on admittance wattmetric or harmonic based principles The IED with a standard configuration is delivered from the factory with default settings and parameters The end user flexibility for incoming outgoing and internal signal designation within the IED enables this configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying ...

Страница 329: ...s with conventional Io input CONTROL AND INDICATION 1 Object Ctrl 2 Ind 3 CB DC ES 1 Check availability of binary inputs outputs from technical documentation 2 Control and indication function for primary object 3 Status indication function for primary object 1 2 3 1 2 O I 79 2 I2 46 3Ith F 49F 3I 50P 51P 3 ARC 50L 50NL Master Trip Lockout relay 94 86 Master Trip Lockout relay 94 86 3 2 Io 51N 2 3I...

Страница 330: ...cuit breaker tuck X100 SO2 Release for earthing switch X100 PO3 Circuit breaker open command X100 PO4 Breaker failure backup trip to upstream breaker X110 HSO1 Arc protection instance 1 operate activated X110 HSO2 Arc protection instance 2 operate activated X110 HSO3 Arc protection instance 3 operate activated Table 63 Default connections for LEDs LED Description 1 Circuit breaker close enabled 2 ...

Страница 331: ...SPTOC1 start Positive or Rising 6 NSPTOC2 start Positive or Rising 7 DEFLPDEF1 start Positive or Rising EFPADM1 start WPWDE1 start 8 DEFLPDEF2 start Positive or Rising EFPADM2 start WPWDE2 start 9 EFPADM3 start Positive or Rising WPWDE3 start 10 INTRPTEF1 start Positive or Rising 11 EFHPTOC1 start Positive or Rising 12 PDNSPTOC1 start Positive or Rising 13 T1PTTR1 start Positive or Rising 14 PHPTO...

Страница 332: ...NSPTOC1 operate Level trigger off NSPTOC2 operate 29 DEFHPDEF1 operate Level trigger off DEFLPDEF1 operate DEFLPDEF2 operate EFPADM1 operate EFPADM2 operate EFPADM3 operate WPWDE1 operate WPWDE2 operate WPWDE3 operate 30 INTRPTEF1 operate Level trigger off 31 EFHPTOC1 operate Level trigger off 32 PDNSPTOC1 operate Level trigger off 33 INRPHAR1 blk2h Level trigger off 34 T1PTTR1 operate Level trigg...

Страница 333: ...2 operate FRPFRQ3 operate 3 13 3 Functional diagrams The functional diagrams describe the default input output alarm LED and function to function connections The default connections can be viewed and changed with PCM600 according to the application requirements The analog channels have fixed connections to the different function blocks inside the IED s standard configuration However the 12 analog ...

Страница 334: ... ENA_MULT OPERATE START PHIPTOC1_OPERATE PHIPTOC1_START GUID BD8968B4 3161 4D6F 9B9D FD51C828C872 V1 EN Figure 505 Overcurrent protection function DPHHPDOC1 BLOCK ENA_MULT NON_DIR OPERATE START DPHLPDOC1 BLOCK ENA_MULT NON_DIR OPERATE START DPHLPDOC2 BLOCK ENA_MULT NON_DIR OPERATE START OR6 B1 B2 B3 B4 B5 B6 O DPHLPDOC2_OPERATE DPHLPDOC2_OPERATE DPHHPDOC1_OPERATE DPHHPDOC1_OPERATE DPHLPDOC1_OPERAT...

Страница 335: ...ions are used to protect the feeder against phase unbalance NSPTOC1 BLOCK ENA_MULT OPERATE START NSPTOC2 BLOCK ENA_MULT OPERATE START NSPTOC1_OPERATE NSPTOC2_OPERATE NSPTOC1_START NSPTOC2_START GUID 9F91B557 1412 4CB4 897C 9D4BEBCC31F4 V1 EN Figure 509 Negative sequence overcurrent protection function Three stages are provided for directional earth fault protection According to the IED s order cod...

Страница 336: ... DEFHPDEF1 BLOCK ENA_MULT RCA_CTL OPERATE START DEFHPDEF1_OPERATE DEFHPDEF1_START GUID 5DBE7FA7 715A 4972 99C1 D5D5B0E7DEF4 V1 EN Figure 510 Directional earth fault protection functions INTRPTEF1 BLOCK OPERATE START BLK_EF INTRPTEF1_OPERATE INTRPTEF1_START GUID C7EF270A B48D 4BC2 A108 0E1F0A22A24F V1 EN Figure 511 Transient or intermittent earth fault protection function Section 3 1MRS756378 S REF...

Страница 337: ...N Figure 512 Wattmetric protection function EFPADM1 BLOCK RELEASE OPERATE START EFPADM2 BLOCK RELEASE OPERATE START EFPADM3 BLOCK RELEASE OPERATE START OR6 B1 B2 B3 B4 B5 B6 O EFPADM1_OPERATE EFPADM1_OPERATE EFPADM2_OPERATE EFPADM2_OPERATE EFPADM3_OPERATE EFPADM3_OPERATE EFPADM1_START EFPADM2_START EFPADM3_START EFPADM_OPERATE GUID DB548625 AE6E 4629 80D7 65C17D2726B1 V1 EN Figure 513 Admittance b...

Страница 338: ...TTR1 detects overloads under varying load conditions The BLK_CLOSE output of the function is used to block the closing operation of circuit breaker T1PTTR1 BLK_OPR ENA_MULT TEMP_AMB OPERATE START ALARM BLK_CLOSE T1PTTR1_BLK_CLOSE T1PTTR1_START T1PTTR1_OPERATE T1PTTR1_ALARM GUID D24BA182 57B6 45D4 9D7D DE6431A2D40D V1 EN Figure 516 Thermal overcurrent protection function Circuit breaker failure pro...

Страница 339: ...SARC1 3 stages are included as an optional function The arc protection offers individual function blocks for three arc sensors that can be connected to the IED Each arc protection function block has two different operation modes that is with or without the phase and residual current check The operate signals from ARCSARC1 3 are connected to both trip logic TRPPTRC1 and TRPPTRC2 If the IED has been...

Страница 340: ...P CL_LKOUT TRPPTRC5 BLOCK OPERATE RST_LKOUT TRIP CL_LKOUT TRPPTRC3_TRIP TRPPTRC4_TRIP TRPPTRC5_TRIP ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE GUID 2C084651 18B3 4B64 A2A8 FA002A7A2789 V1 EN Figure 518 Arc protection with dedicated HSO The optional autoreclosing function is configured to be initiated by operate signals from a number of protection stages through the INIT_1 5 inputs It is po...

Страница 341: ...B6 O OR6 B1 B2 B3 B4 B5 B6 O OR6 B1 B2 B3 B4 B5 B6 O CBXCBR1_CLOSE_ENAD DARREC1_CLOSE_CB X110_BI3_CB_OPENED DARREC1_OPEN_CB WPWDE2_OPERATE WPWDE3_OPERATE PDNSPTOC1_OPERATE INTRPTEF1_OPERATE EFPADM2_OPERATE DEFLPDEF2_OPERATE DEFHPDEF1_OPERATE PHIPTOC1_OPERATE DPHLPDOC2_OPERATE DPHHPDOC1_OPERATE NSPTOC1_OPERATE NSPTOC2_OPERATE EFPADM3_OPERATE CBXCBR1_SELECTED ARCSARCx_OPERATE DARREC1_INPRO DARREC1_U...

Страница 342: ... Overvoltage protection function PHPTUV1 BLOCK OPERATE START PHPTUV2 BLOCK OPERATE START PHPTUV3 BLOCK OPERATE START OR6 B1 B2 B3 B4 B5 B6 O PHPTUV1_OPERATE PHPTUV1_OPERATE PHPTUV2_OPERATE PHPTUV2_OPERATE PHPTUV3_OPERATE PHPTUV3_OPERATE PHPTUV1_START PHPTUV2_START PHPTUV3_START SEQSPVC1_FUSEF_U SEQSPVC1_FUSEF_U SEQSPVC1_FUSEF_U PHPTUV_OPERATE GUID 495CB32C 5BEB 47DB ADB3 5FE266D3482D V2 EN Figure ...

Страница 343: ...K OPERATE START NSPTOV1_OPERATE NSPTOV1_START SEQSPVC1_FUSEF_U GUID 911F6005 2A2B 4012 85F8 BC6D88B453B6 V2 EN Figure 523 Negative sequence overvoltage protection function PSPTUV1 BLOCK OPERATE START PSPTUV1_OPERATE PSPTUV1_START SEQSPVC1_FUSEF_U GUID A60BCAA1 D381 4F34 9C15 56DD20DA737E V2 EN Figure 524 Positive sequence undervoltage protection function The selectable underfrequency or overfreque...

Страница 344: ...T FRPFRQ3_START FREQUENCY_OPERATE GUID F8133DC0 F5B6 4B19 993B A88C87927D48 V1 EN Figure 525 Frequency protection function General start and operate signals from all functions are connected to minimum pulse timer TPGAPC for setting the minimum pulse length for the outputs The output from TPGAPC can be connected to binary outputs However these are not connected in the configuration If a new protect...

Страница 345: ...HIPTOC1_START NSPTOC1_START NSPTOC2_START DEFLPDEF1_START DEFLPDEF2_START DEFHPDEF1_START INTRPTEF1_START EFHPTOC1_START PDNSPTOC1_START PHPTOV1_START PHPTOV2_START PHPTOV3_START PSPTUV1_START NSPTOV1_START PHPTUV1_START PHPTUV2_START PHPTUV3_START ROVPTOV1_START ROVPTOV2_START ROVPTOV3_START FRPFRQ1_START FRPFRQ2_START FRPFRQ3_START EFPADM1_START EFPADM2_START EFPADM3_START WPWDE1_START WPWDE2_ST...

Страница 346: ...ATE PHPTUV1_OPERATE WPWDE1_OPERATE WPWDE2_OPERATE WPWDE3_OPERATE ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE ROVPTOV3_OPERATE ROVPTOV2_OPERATE ROVPTOV1_OPERATE PDNSPTOC1_OPERATE EFHPTOC1_OPERATE INTRPTEF1_OPERATE EFPADM2_OPERATE EFPADM1_OPERATE DEFLPDEF2_OPERATE DEFLPDEF1_OPERATE DEFHPDEF1_OPERATE PHIPTOC1_OPERATE DPHLPDOC2_OPERATE DPHHPDOC1_OPERATE DPHLPDOC1_OPERATE NSPTOC1_OPERATE NSPTOC2...

Страница 347: ...1_OPERATE DPHLPDOC2_OPERATE DPHHPDOC1_OPERATE DPHLPDOC1_OPERATE NSPTOC1_OPERATE NSPTOC2_OPERATE EFPADM3_OPERATE GUID C7506F05 1EE1 466B B904 923D2568A6EC V1 EN Figure 528 Trip logic TRPPTRC2 3 13 3 2 Functional diagrams for disturbance recorder The START and OPERATE outputs from the protection stages are routed to trigger the disturbance recorder or alternatively only to be recorded by the disturb...

Страница 348: ...DOC2_START DPHHPDOC1_START PHIPTOC1_START NSPTOC1_START NSPTOC2_START DEFLPDEF1_START DEFLPDEF2_START DEFHPDEF1_START INTRPTEF1_START EFHPTOC1_START PDNSPTOC1_START PHPTOV1_START PHPTOV2_START PHPTOV3_START PSPTUV1_START NSPTOV1_START PHPTUV1_START PHPTUV2_START PHPTUV3_START ROVPTOV1_START ROVPTOV2_START ROVPTOV3_START FRPFRQ1_START FRPFRQ2_START FRPFRQ3_START T1PTTR1_START SEQPVC1_FUSEF_U CCBRBR...

Страница 349: ...LM SSCBR1_OPR_ALM SSCBR1_OPR_LO SSCBR1_IPOW_ALM SSCBR1_IPOW_LO SSCBR1_CB_LIFE_ALM SSCBR1_MON_ALM SSCBR1_PRES_ALM SSCBR1_PRES_LO GUID E3A89E30 4683 4F71 9306 6549552846DE V1 EN Figure 532 Circuit breaker condition monitoring function OR6 B1 B2 B3 B4 B5 B6 O OR6 B1 B2 B3 B4 B5 B6 O OR B1 B2 O SSCBR1_TRV_T_OP_ALM SSCBR1_TRV_T_CL_ALM SSCBR1_SPR_CHR_ALM SSCBR1_OPR_ALM SSCBR1_OPR_LO SSCBR1_IPOW_ALM SSCB...

Страница 350: ...1C0AD672 5573 4348 AADA DB5EA1326A76 V1 EN Figure 536 Logic for blocking trip circuit supervision 3 13 3 4 Functional diagrams for control and interlocking Two types of disconnector and earthing switch function blocks are available DCSXSWI1 3 and ESSXSWI1 2 are status only type and DCXSWI1 2 and ESXSWI1 are controllable type By default the status only blocks are connected in standard configuration...

Страница 351: ... can be activated by the configuration logic which is a combination of the disconnector or breaker truck and earth switch position status status of the trip logics gas pressure alarm and circuit breaker spring charging status The OKPOS output from DCSXSWI defines whether disconnector or breaker truck is either open in test position or close in service position This output together with the open ea...

Страница 352: ... of circuit breaker OR B1 B2 O CB_CLOSE_COMMAND CBXCBR1_EXE_CL DARREC1_CLOSE_CB GUID 13E343ED 6BDF 4C49 B87C 9102858743F6 V1 EN Figure 540 Circuit breaker control logic Signal for closing coil of circuit breaker 1 OR6 B1 B2 B3 B4 B5 B6 O CB_OPEN_COMMAND CBXCBR1_EXE_OP TRPPTRC1_TRIP DARREC1_OPEN_CB GUID C50B912E F0EE 4D07 8BB5 3BCCF0706C4F V1 EN Figure 541 Circuit breaker control logic Signal for o...

Страница 353: ...able for the configuration AND B1 B2 O AND B1 B2 O OR B1 B2 O FALSE FALSE CBXCBR1_AU_CLOSE CONTROL_LOCAL CONTROL_REMOTE GUID 3C821932 5AE1 49F7 9179 4414221BC7A8 V1 EN Figure 544 External closing command for circuit breaker AND B1 B2 O AND B1 B2 O OR B1 B2 O FALSE FALSE CBXBCR1_AU_OPEN CONTROL_LOCAL CONTROL_REMOTE GUID 7BBD30FE 55C8 4869 8680 91BFF424703E V1 EN Figure 545 External opening command ...

Страница 354: ...le The load profile function LDPRLRC1 is included in the measurements sheet LDPRLRC1 offers the ability to observe the loading history of the corresponding feeder The power quality functions CMHAI1 and VMHAI1 can be used to measure the harmonic contents of the phase current and phase voltages The voltage variation that is sage and swells can be measured by the voltage variation function PHQVVR1 By...

Страница 355: ...03E8 V1 EN Figure 551 Other measurement Frequency measurement PEMMXU1 RSTACM GUID F0DE06C2 085C 4D22 A335 BCD31825A860 V1 EN Figure 552 Other measurement Three phase power and energy measurement FLTRFRC1 BLOCK CB_CLRD GUID AF81ADD7 B8B0 4909 A853 BB2833B97F4C V2 EN Figure 553 Other measurement Data monitoring LDPRLRC1 RSTMEM MEM_WARN MEM_ALARM GUID EEB651DB EF5B 4AC5 A36C 5DD219289DAE V2 EN Figure...

Страница 356: ...nput 7 X110 BIO H X110 Input 1 X110 BIO H X110 Input 7 X110 BIO X110 Input 5 X110 BIO H X110 Input 6 X110 BIO H X110 Input 5 X110 BIO X110 Input 3 X110 BIO H X110 Input 2 X110 BIO H X110 Input 4 X110 BIO X110 Input 6 X110 BIO H X110 Input 3 X110 BIO H X110 Input 8 X110 BIO X110 Input 2 X110 BIO X110 Input 8 X110 BIO X110 Input 4 X110 BIO X110 Input 1 GUID F81BB3AC 2639 42F9 ABA0 2078F82B6371 V1 EN...

Страница 357: ... block CB_OPEN_COMMAND CB_CLOSE_COMMAND DC1_CLOSE_ENABLE ES1_CLOSE_ENABLED CCBRBRF1_TRRET CBXCBR1_CLOSE_ENAD X100 PSM X100 PO1 X100 PSM X100 PO2 X100 PSM X100 SO1 X100 PSM X100 SO2 X100 PSM X100 PO4 X100 PSM X100 PO3 GUID E3B54637 D2EA 41F7 9C10 645647E5F8D6 V1 EN Figure 557 Default binary outputs X100 terminal block 1MRS756378 S Section 3 REF615 standard configurations REF615 351 Application Manu...

Страница 358: ... DEFxPDEF_OPERATE LED4 OK ALARM RESET OR6 B1 B2 B3 B4 B5 B6 O PDNSPTOC1_OPERATE NSPTOC1_OPERATE NSPTOC2_OPERATE LED5 OK ALARM RESET OR B1 B2 O PSPTUV1_OPERATE NSPTOV1_OPERATE LED1 OK ALARM RESET CBXCBR1_CLOSE_ENAD GUID BCE4BD5B 5020 4EDB 9AE0 51D6BFE8C7C6 V2 EN Section 3 1MRS756378 S REF615 standard configurations 352 REF615 Application Manual ...

Страница 359: ...ration also includes overcurrent operate earth fault operate and combined voltage frequency operate logic The operate logics are connected to the minimum pulse timer TPGAPC for setting the minimum pulse length for the outputs The output from TPGAPC is connected to binary outputs TPGAPC2 IN1 IN2 OUT1 OUT2 OR6 B1 B2 B3 B4 B5 B6 O OR B1 B2 O EFHPTOC1_OPERATE INTRPTEF1_OPERATE PHIPTOC1_OPERATE DEFxPDE...

Страница 360: ...ions The standard configuration N provides the highest functionality level of all the REF615 standard configurations Standard configuration N is delivered as pre configured with the same configuration as standard configuration D Standard configuration N provides the possibility to standardize on one type of REF615 Depending on the specific feeder application the appropriate functionality can be se...

Страница 361: ...ventional transformer inputs ALSO AVAILABLE Disturbance and fault recorders Event log and recorded data High Speed Output module optional Local Remote push button on LHMI Self supervision Time synchronization IEEE 1588 v2 SNTP IRIG B User management Web HMI 1 2 3 1 2 SYNC 25 O I 79 2 I2 46 3Ith F 49F 3I 50P 51P 3 ARC 50L 50NL Master Trip Lockout relay 94 86 Master Trip Lockout relay 94 86 3 2 3I 6...

Страница 362: ...er failure protection trip to upstream breaker X100 PO3 Open circuit breaker trip coil 1 X100 PO4 Open circuit breaker trip coil 2 X100 SO1 General start indication X100 SO2 General operate indication X110 SO1 Upstream overcurrent blocking X110 SO2 Overcurrent opertae alarm X110 SO3 Earth fault operate alarm X110 HSO1 Arc protection instance 1 operate activated X110 HSO2 Arc protection instance 2 ...

Страница 363: ...ing 2 PHHPTOC1 start Positive or Rising 3 PHLPTOC2 start Positive or Rising 4 PHIPTOC1 start Positive or Rising 5 NSPTOC1 start Positive or Rising 6 NSPTOC2 start Positive or Rising 7 EFLPTOC1 start Positive or Rising 8 EFHPTOC1 start Positive or Rising 9 EFIPTOC1 start Positive or Rising 10 EFLPTOC2 start Positive or Rising 11 12 PDNSPTOC1 start Positive or Rising 13 T1PTTR1 start Positive or Ris...

Страница 364: ...cl Level trigger off 31 X120BI1 ext OC blocking Level trigger off 32 X120BI2 CB closed Level trigger off 33 X120BI3 CB opened Level trigger off 3 14 3 Functional diagrams The functional diagrams describe the default input output alarm LED and function to function connections The default connections can be viewed and changed with PCM600 according to the application requirements The analog channels ...

Страница 365: ...ons Four non directional overcurrent stage and three directional overcurrent stages are offered for overcurrent and short circuit protection Three phase non directional overcurrent protection instantaneous stage PHIPTOC1 can be blocked by energizing the binary input X120 BI1 PHIPTOC1 BLOCK ENA_MULT OPERATE START PHLPTOC1 BLOCK ENA_MULT OPERATE START PHHPTOC1 BLOCK ENA_MULT OPERATE START PHLPTOC2 B...

Страница 366: ...NSPTOC1 and NSPTOC2 are provided for phase unbalance protection These functions are used to protect the feeder against phase unbalance NSPTOC1 BLOCK ENA_MULT OPERATE START NSPTOC2 BLOCK ENA_MULT OPERATE START OR B1 B2 O NSPTOC1_OPERATE NSPTOC1_OPERATE NSPTOC2_OPERATE NSPTOC2_OPERATE NSPTOC1_START NSPTOC2_START NSPTOC_OPERATE GUID D2BCBB3A C69C 438B BC3F 31C77B49BCC5 V1 EN Figure 565 Negative seque...

Страница 367: ...566 Earth fault protection functions EFLPTOC2 BLOCK ENA_MULT OPERATE START EFLPTOC2_OPERATE EFLPTOC2_START GUID 65E9D918 294A 4936 9F02 65AD242EA181 V1 EN Figure 567 Sensitive earth fault protection function Phase discontinuity protection PDNSPTOC1 protects from interruptions in the normal three phase load supply for example in downed conductor situations PDNSPTOC1 BLOCK OPERATE START PDNSPTOC1_OP...

Страница 368: ...T OR6 B1 B2 B3 B4 B5 B6 O OR6 B1 B2 B3 B4 B5 B6 O OR6 B1 B2 B3 B4 B5 B6 O CCBRBRF1_TRBU X120_BI2_CB_CLOSED PHIPTOC1_OPERATE PHHPTOC1_OPERATE PHLPTOC2_OPERATE EFLPTOC1_OPERATE EFHPTOC1_OPERATE EFIPTOC1_OPERATE ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE CCBRBRF1_TRRET GUID 39F151C5 77E0 4268 99D6 0F172571155C V1 EN Figure 570 Circuit breaker failure protection function Three arc protection A...

Страница 369: ...RST_LOCKOUT X120_BI4_RST_LOCKOUT X120_BI4_RST_LOCKOUT ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE GUID 0F1C0838 790F 4526 801E DBA88E061C80 V1 EN Figure 571 Arc protection with dedicated HSO The optional autoreclosing function is configured to be initiated by operate signals from a number of protection stages through the INIT_1 5 inputs The INIT_6 input in the autoreclosing function block i...

Страница 370: ...N SYNC OPEN_CB CLOSE_CB CMD_WAIT INPRO LOCKED PROT_CRD UNSUC_RECL AR_ON READY ACTIVE OR6 B1 B2 B3 B4 B5 B6 O OR6 B1 B2 B3 B4 B5 B6 O OR B1 B2 O X120_BI3_CB_OPENED DARREC1_OPEN_CB DARREC1_CLOSE_CB X110_BI3_GAS_PRESSURE_ALARM X110_BI4_CB_SPRING_CHARGED PHIPTOC1_OPERATE PHHPTOC1_OPERATE NSPTOC1_OPERATE PHLPTOC2_OPERATE NSPTOC2_OPERATE EFLPTOC1_OPERATE EFHPTOC1_OPERATE PDNSPTOC1_OPERATE ARCSARC1_OPERA...

Страница 371: ...1_START PDNSPTOC1_START GUID 6BA9A7FE D984 48C6 B8E2 704C4C38FA44 V1 EN Figure 573 General start and operate signals The operate signals from the protection functions are connected to the two trip logics TRPPTRC1 and TRPPTRC2 The output of these trip logic functions is available at binary output X100 PO3 and X100 PO4 The trip logic functions are provided with a lockout and latching function event ...

Страница 372: ...RPPTRC2_TRIP PHIPTOC1_OPERATE PHLPTOC1_OPERATE PHHPTOC1_OPERATE NSPTOC1_OPERATE PHLPTOC2_OPERATE NSPTOC2_OPERATE EFLPTOC1_OPERATE EFHPTOC1_OPERATE EFIPTOC1_OPERATE EFLPTOC2_OPERATE PDNSPTOC1_OPERATE X120_BI4_RST_LOCKOUT ARCSARC1_OPERATE ARCSARC2_OPERATE ARCSARC3_OPERATE CCBRBRF1_TRRET GUID F22B7AB4 4791 4726 8AE6 04EA9D09F96B V1 EN Figure 575 Trip logic TRPPTRC2 3 14 3 2 Functional diagrams for di...

Страница 373: ... CCBRBRF1_TRRET PHLPTOC1_START PHHPTOC1_START PHLPTOC2_START PHIPTOC1_START NSPTOC1_START NSPTOC2_START EFLPTOC1_START EFLPTOC2_START EFIPTOC1_START EFHPTOC1_START PDNSPTOC1_START X120_BI1_EXT_OC_BLOCKING X110_BI2_EXT_START_AUTORECLOSE T1PTTR1_START ARCSARC1_ARC_FLT_DET ARCSARC2_ARC_FLT_DET ARCSARC3_ARC_FLT_DET INRPHAR1_BLK2H T1PTTR1_OPERATE DARREC1_INPRO DARREC1_UNSUC_RECL DISTURB_RECORD_TRIGGERE...

Страница 374: ...LM SSCBR1_TRV_T_CL_ALM SSCBR1_SPR_CHR_ALM SSCBR1_OPR_ALM SSCBR1_OPR_LO SSCBR1_IPOW_ALM SSCBR1_IPOW_LO SSCBR1_CB_LIFE_ALM SSCBR1_MON_ALM SSCBR1_PRES_ALM SSCBR1_PRES_LO SSCBR1_ALARMS GUID 001C6E30 A6E4 475D 9142 2CB675A26FCC V1 EN Figure 578 Logic for circuit breaker monitoring alarm NOT IN OUT X110_BI4_CB_SPRING_CHARGED CB_SPRING_DISCHARGED GUID BE312318 2FBB 4272 BE2B 835BD63D592E V1 EN Figure 579...

Страница 375: ...and ESXSWI1arecontrollabletype Bydefault thestatusonlyblocksareconnectedinthe standard configuration The disconnector CB truck and line side earthing switch status information are connected to DCSXSWI1 and ESSXSI1 DCSXSWI1 POSOPEN POSCLOSE OPENPOS CLOSEPOS OKPOS DCSXSWI1_OKPOS X110_BI6_CB_TRUCK_IN_TEST X110_BI5_CB_TRUCK_IN_SERVICE GUID 88089155 4117 4BF7 BEAD 8EB5D61595E1 V1 EN Figure 582 Disconne...

Страница 376: ... ENA_OPEN ENA_CLOSE BLK_OPEN BLK_CLOSE AU_OPEN AU_CLOSE TRIP SYNC_OK SYNC_ITL_BYP SELECTED EXE_OP EXE_CL OP_REQ CL_REQ OPENPOS CLOSEPOS OKPOS OPEN_ENAD CLOSE_ENAD TRUE X120_BI3_CB_OPENED X120_BI2_CB_CLOSED CBXCBR1_ENA_CLOSE CBXCBR1_EXE_CL CBXCBR1_EXE_OP FALSE CBXCBR1_AU_OPEN CBXCBR1_AU_CLOSE CBXCBR1_SELECTED GUID A9EA74A8 8931 4A9A B602 C5940687A28E V2 EN Figure 584 Circuit breaker control logic C...

Страница 377: ...uration AND B1 B2 O AND B1 B2 O OR B1 B2 O FALSE FALSE CBXCBR1_AU_CLOSE CONTROL_LOCAL CONTROL_REMOTE GUID 065B8F38 D535 4FBF B2B5 9FB82191614C V1 EN Figure 588 External closing command for circuit breaker 1 AND B1 B2 O AND B1 B2 O OR B1 B2 O FALSE FALSE CBXBCR1_AU_OPEN CONTROL_LOCAL CONTROL_REMOTE GUID 0978DD77 5996 4E3C BFCE E0726ED2BC9A V1 EN Figure 589 External opening command for circuit break...

Страница 378: ... side phase voltage inputs to the IED can be measured by three phase voltage measurement VMMXU1 and VMMXU2 The voltage input is connected to the X130 card in the back panel The sequence voltage measurement VSMSQI1 measures the sequence voltage and the residual voltage measurement RESVMMXU1 measures the residual voltage The frequency measurement FMMXU1 of the power system and the three phase power ...

Страница 379: ...ement Three phase voltage measurement FMMXU1 GUID D9F7BF94 F97E 4DE9 8F52 1EE26998B098 V1 EN Figure 596 Other measurement Frequency measurement PEMMXU1 RSTACM GUID C81ADCD4 65DF 477A 93D1 B272754B312B V1 EN Figure 597 Other measurement Three phase power and energy measurement FLTRFRC1 BLOCK CB_CLRD GUID CA3D6392 494E 4BC9 BBB9 9F98D96BE196 V2 EN Figure 598 Other measurement Data monitoring LDPRLRC...

Страница 380: ...110 Input 7 X110 BIO H X110 Input 3 X110 BIO H X110 Input 7 X110 BIO X110 Input 4 X110 BIO H X110 Input 8 X110 BIO H X110 Input 6 X110 BIO X110 Input 8 X110 BIO X110 Input 5 X110 BIO X110 Input 3 GUID 46F2BC2B B863 4F13 8EFE E10E5D695CE8 V1 EN Figure 600 Binary inputs X110 terminal block X120_BI3_CB_OPENED X120_BI2_CB_CLOSED X120_BI4_RST_LOCKOUT X120_BI1_EXT_OC_BLOCKING X120 AIM X120 Input 1 X120 ...

Страница 381: ...1E9425E V1 EN Figure 602 Binary outputs X110 terminal block CB_CLOSE_COMMAND CCBRBRF1_TRBU GENERAL_START_PULSE GENERAL_OPERATE_PULSE CB_OPEN_COMMAND TRPPTRC2_TRIP X100 PSM X100 PO1 X100 PSM X100 PO2 X100 PSM X100 SO1 X100 PSM X100 SO2 X100 PSM X100 PO3 X100 PSM X100 PO4 GUID 3817524D C0C1 42F8 A4DC FB5DA4EFFFD0 V1 EN Figure 603 Binary outputs X100 terminal block 1MRS756378 S Section 3 REF615 stand...

Страница 382: ...ALARM RESET LED5 OK ALARM RESET OR B1 B2 O EFLPTOC2_OPERATE PDNSPTOC1_OPERATE PHxPTOC_OPERATE EFxPTOC_OPERATE T1PTTR1_ALARM NSPTOC_OPERATE GUID 0A540AFB 3DD1 47A7 AE63 E65932766D34 V1 EN Section 3 1MRS756378 S REF615 standard configurations 376 REF615 Application Manual ...

Страница 383: ...ration also includes overcurrent operate and earth fault operate logic The operate logics are connected to the minimum pulse timer TPGAPC for setting the minimum pulse length for the outputs The output from TPGAPC is connected to binary outputs TPGAPC2 IN1 IN2 OUT1 OUT2 OR B1 B2 O OC_OPERATE_PULSE EF_OPERATE_PULSE EFLPTOC2_OPERATE PHxPTOC_OPERATE EFxPTOC_OPERATE GUID 5DAD5155 7666 4E05 B6AC 7CD7EB...

Страница 384: ...ervoltage protection frequency protection multipurpose protection MAPGAPC high impedance fault detection PHIZ runtime counter for machines and devices MDSOPT and different types of timers and control functions These functions are not included in application configuration but they can be added based on the system requirements Section 3 1MRS756378 S REF615 standard configurations 378 REF615 Applicat...

Страница 385: ...rotective current transformer of type 5P10 has the accuracy class 5P and the accuracy limit factor 10 For protective current transformers the accuracy class is designed by the highest permissible percentage composite error at the rated accuracy limit primary current prescribed for the accuracy class concerned followed by the letter P meaning protection Table 71 Limits of errors according to IEC 60...

Страница 386: ...th Fa of at least 20 The nominal primary current I1n should be chosen in such a way that the thermal and dynamic strength of the current measuring input of the protection relay is not exceeded This is always fulfilled when I1n Ikmax 100 Ikmax is the highest fault current The saturation of the CT protects the measuring circuit and the current input of the protection relay For that reason in practic...

Страница 387: ... the current is only slightly higher than the starting current This depends on the accuracy limit factor of the CT on the remanence flux of the core of the CT and on the operate time setting With inverse time mode of operation the delay should always be considered as being as long as the time constant of the DC component With inverse time mode of operation and when the high set stages are not used...

Страница 388: ...with the downstream protection In addition the start current settings have to be defined so that the protection relay operates with the minimum fault current and it does not operate with the maximum load current The settings for all three stages are as in Figure 606 For the application point of view the suitable setting for instantaneous stage I in this example is 3 500 A 5 83 I2n For the CT chara...

Страница 389: ...E F H J K and N Terminal Description X120 7 8 IL1 X120 9 10 IL2 X120 11 12 IL3 5 1 1 2 Residual current Table 73 Residual current input included in configurations A B C D E F H J and N Terminal Description X120 13 14 Io Table 74 Residual current input included in configuration K Terminal Description X120 5 6 IoB1 X120 13 14 Io 1 Used only for HREFPDIF1 Table 75 Residual current input included in c...

Страница 390: ...79 Additional residual voltage input included in configurations E F H J K and N Terminal Description X130 17 18 Uo 5 1 1 5 Sensor inputs Table 80 Combi sensor inputs included in configurations G and L Terminal Description X131 IL1 U1 X132 IL2 U2 X133 IL3 U3 5 1 2 Auxiliary supply voltage input The auxiliary voltage of the protection relay is connected to terminals X100 1 2 At DC supply the positiv...

Страница 391: ... E F G H J K L and N Table 82 Binary input terminals X110 1 13 with BIO0005 module Terminal Description X110 1 BI1 X110 2 BI1 X110 3 BI2 X110 4 BI2 X110 5 BI3 X110 6 BI3 X110 6 BI4 X110 7 BI4 X110 8 BI5 X110 9 BI5 X110 9 BI6 X110 10 BI6 X110 11 BI7 X110 12 BI7 X110 12 BI8 X110 13 BI8 Table 83 Binary input terminals X110 1 10 with BIO0007 module Terminal Description X110 1 BI1 X110 5 BI1 X110 2 BI2...

Страница 392: ... 6 Terminal Description X120 1 BI1 X120 2 BI1 X120 3 BI2 X120 2 BI2 X120 4 BI3 X120 2 BI3 X120 5 BI4 X120 6 BI4 Binary inputs of slot X120 are available with configurations A and B Table 85 Binary input terminals X120 1 4 Terminal Description X120 1 BI1 X120 2 BI1 X120 3 BI2 X120 2 BI2 X120 4 BI3 X120 2 BI3 Binary inputs of slot X130 are optional for configurations B and D Section 5 1MRS756378 S I...

Страница 393: ...130 6 BI3 X130 7 BI4 X130 8 BI4 5 1 4 Optional light sensor inputs If the IED is provided with the optional communication module with light sensor inputs the pre manufactured lens sensor fibers are connected to inputs X13 X14 and X15 See the connection diagrams For further information see arc protection The IED is provided with connection sockets X13 X14 and X15 only if the optional communication ...

Страница 394: ...le Terminal Description X130 1 mA1 AI1 X130 2 mA1 AI1 X130 3 mA2 AI2 X130 4 mA2 AI2 X130 5 RTD1 AI3 X130 6 RTD1 AI3 X130 7 RTD2 AI4 X130 8 RTD2 AI4 X130 9 RTD3 AI5 X130 10 RTD3 AI5 X130 11 Common1 X130 12 Common2 X130 13 RTD4 AI6 X130 14 RTD4 AI6 X130 15 RTD5 AI7 X130 16 RTD5 AI7 X130 17 RTD6 AI8 X130 18 RTD6 AI8 1 Common ground for RTD channels 1 3 2 Common ground for RTD channels 4 6 Table 90 Op...

Страница 395: ...nal Description X100 6 PO1 NO X100 7 PO1 NO X100 8 PO2 NO X100 9 PO2 NO X100 15 PO3 NO TCS resistor X100 16 PO3 NO X100 17 PO3 NO X100 18 PO3 TCS1 input NO X100 19 PO3 TCS1 input NO X100 20 PO4 NO TCS resistor X100 21 PO4 NO X100 22 PO4 NO X100 23 PO4 TCS2 input NO X100 24 PO4 TCS2 input NO 5 2 2 Outputs for signalling SO output contacts can be used for signalling on start and tripping of the IED ...

Страница 396: ... X110 17 SO2 common X110 18 SO2 NO X110 19 SO2 NC X110 20 SO3 common X110 21 SO3 NO X110 22 SO3 NC X110 23 SO4 common X110 24 SO4 NO Table 94 Optional high speed output contacts X110 15 24 with BIO0007 Terminal Description X110 15 HSO1 NO X110 16 HSO1 NO X110 19 HSO2 NO X110 20 HSO2 NO X110 23 HSO3 NO X110 24 HSO3 NO Output contacts of slot X130 are available in the optional BIO module BIO0006 Out...

Страница 397: ...the protection relay Under normal operating conditions the protection relay is energized and the contact is closed X100 3 5 When a fault is detected by the self supervision system or the auxiliary voltage is disconnected the output contact drops off and the contact closes X100 3 4 Table 96 IRF contact Terminal Description X100 3 IRF common X100 4 Closed IRF or Uaux disconnected X100 5 Closed no IR...

Страница 398: ...392 ...

Страница 399: ...mmand DNP3 A distributed network protocol originally developed by Westronic The DNP3 Users Group has the ownership of the protocol and assumes responsibility for its evolution DPC Double point control EMC Electromagnetic compatibility Ethernet A standard for connecting a family of frame based computer networking technologies into a LAN FIFO First in first out FTP File transfer protocol FTPS FTP Se...

Страница 400: ...rol systems IEEE 1686 Standard for Substation Intelligent Electronic Devices IEDs Cyber Security Capabilities IP address A set of four numbers between 0 and 255 separated by periods Each server connected to the Internet is assigned a unique IP address that specifies the location for the TCP IP protocol IRIG B Inter Range Instrumentation Group s time code format B LAN Local area network LC Connecto...

Страница 401: ... to EIA standard RS485 RSTP Rapid spanning tree protocol RTD Resistance temperature detector RTU Remote terminal unit SAN Single attached node SLD Single line diagram SMV Sampled measured values SNTP Simple Network Time Protocol SO Signal output Single line diagram Simplified notation for representing a three phase power system Instead of representing each of three phases with a separate line or t...

Страница 402: ...396 ...

Страница 403: ...397 ...

Страница 404: ...0 22 11 Fax 358 10 22 41094 www abb com mediumvoltage www abb com substationautomation ABB India Limited Distribution Automation Maneja Works Vadodara 390013 India Phone 91 265 6724402 Fax 91 265 6724423 www abb com mediumvoltage www abb com substationautomation 1MRS756378 S Copyright 2016 ABB All rights reserved ...

Отзывы: