![ABB relion REF615 Скачать руководство пользователя страница 137](http://html.mh-extra.com/html/abb/relion-ref615/relion-ref615_applications-manual_2824137.webp)
OR6
B1
B2
B3
B4
B5
B6
O
CB_OPEN_COMMAND
CBXCBR1_EXE_OP
TRPPTRC1_TRIP
DARREC1_OPEN_CB
GUID-26BE8B84-99DF-44E7-BA2E-09EFC6A4EA76 V1 EN
Figure 153:
Signals for opening coil of circuit breaker 1
NOT
IN
OUT
AND6
B1
B2
B3
B4
B5
B6
O
NOT
IN
OUT
NOT
IN
OUT
TRPPTRC2_TRIP
CBXCBR1_ENA_CLOSE
TRPPTRC1_TRIP
X110_BI3_GAS_PRESSURE_ALARM
DCSXSWI1_OKPOS
ESSXSWI1_OPENPOS
X110_BI4_CB_SPRING_CHARGED
GUID-BA344D0E-6F99-4CAB-9DBF-7CD674525C88 V1 EN
Figure 154:
Circuit breaker 1 close enable logic
The configuration includes logic for generating circuit breaker external closing and
opening command with the IED in local or remote mode.
Check the logic for the external circuit breaker closing command and
modify it according to the application.
Connect additional signals for opening and closing of circuit breaker
in local or remote mode, if it is applicable for the configuration.
AND
B1
B2
O
AND
B1
B2
O
OR
B1
B2
O
FALSE
FALSE
CBXCBR1_AU_CLOSE
CONTROL_LOCAL
CONTROL_REMOTE
GUID-2BAE22BC-81C2-4F1B-AC3F-3F1663381794 V1 EN
Figure 155:
External closing command for circuit breaker 1
AND
B1
B2
O
AND
B1
B2
O
OR
B1
B2
O
FALSE
FALSE
CBXBCR1_AU_OPEN
CONTROL_LOCAL
CONTROL_REMOTE
GUID-9D61A2BA-90F0-4808-9282-C8DDDED6C80C V1 EN
Figure 156:
External opening command for circuit breaker 1
1MRS756378 S
Section 3
REF615 standard configurations
REF615
131