![ABB relion REF615 Скачать руководство пользователя страница 272](http://html.mh-extra.com/html/abb/relion-ref615/relion-ref615_applications-manual_2824272.webp)
Non-directional (cross-country) earth-fault protection, using calculated Io,
EFHPTOC1 protects against double earth-fault situations in isolated or compensated
networks. This protection function uses the calculated residual current originating
from the phase currents.
EFHPTOC1
BLOCK
ENA_MULT
OPERATE
START
EFHPTOC1_OPERATE
EFHPTOC1_START
GUID-D03A063B-438B-4282-B6B9-A61C404C25F5 V1 EN
Figure 395:
Earth-fault protection function
Phase discontinuity protection PDNSPTOC1 protects for interruptions in the normal
three-phase load supply, for example, in downed conductor situations.
PDNSPTOC1
BLOCK
OPERATE
START
PDNSPTOC1_OPERATE
PDNSPTOC1_START
GUID-7D77A0CB-7E59-4161-9451-F93E1B7D34CF V1 EN
Figure 396:
Phase discontinuity protection function
Three-phase thermal protection for feeders, cables and distribution transformers
T1PTTR1 detects overloads under varying load conditions. The
BLK_CLOSE
output
of the function is used to block the closing operation of circuit breaker.
T1PTTR1
BLK_OPR
ENA_MULT
TEMP_AMB
OPERATE
START
ALARM
BLK_CLOSE
T1PTTR1_BLK_CLOSE
T1PTTR1_START
T1PTTR1_OPERATE
T1PTTR1_ALARM
GUID-52DD9079-0F13-411A-8C7E-B5A89065765E V1 EN
Figure 397:
Thermal overcurrent protection function
Circuit breaker failure protection CCBRBRF1 is initiated via the
START
input by
number of different protection functions available in the IED. The breaker failure
protection function offers different operating modes associated with the circuit
breaker position and the measured phase and residual currents.
The circuit breaker failure protection function has two operating outputs:
TRRET
and
TRBU
. The
TRRET
operate output is used for retripping its own breaker through
TRPPTRC2_TRIP
. The
TRBU
output is used to give a backup trip to the breaker
feeding upstream. For this purpose, the
TRBU
operate output signal is connected to the
binary output X100:PO2.
Section 3