CBXCBR1
POSOPEN
POSCLOSE
ENA_OPEN
ENA_CLOSE
BLK_OPEN
BLK_CLOSE
AU_OPEN
AU_CLOSE
TRIP
SYNC_OK
SYNC_ITL_BYP
SELECTED
EXE_OP
EXE_CL
OP_REQ
CL_REQ
OPENPOS
CLOSEPOS
OKPOS
OPEN_ENAD
CLOSE_ENAD
TRUE
CBXCBR1_CLOSE_ENAD
CBXCBR1_ENA_CLOSE
CBXCBR1_EXE_CL
X110_BI3_CB_OPENED
X110_BI4_CB_CLOSED
CBXCBR1_BLK_CLOSE
CBXCBR1_EXE_OP
FALSE
CBXCBR1_AU_OPEN
CBXCBR1_AU_CLOSE
CBXCBR1_OPENPOS
CBXCBR1_SELECTED
GUID-41D06A2F-930F-4252-8791-66809C2B53A5 V2 EN
Figure 539:
Circuit breaker control logic: Circuit breaker 1
Connect the additional signals required for the application for closing
and opening of circuit breaker.
OR
B1
B2
O
CB_CLOSE_COMMAND
CBXCBR1_EXE_CL
DARREC1_CLOSE_CB
GUID-13E343ED-6BDF-4C49-B87C-9102858743F6 V1 EN
Figure 540:
Circuit breaker control logic: Signal for closing coil of circuit breaker 1
OR6
B1
B2
B3
B4
B5
B6
O
CB_OPEN_COMMAND
CBXCBR1_EXE_OP
TRPPTRC1_TRIP
DARREC1_OPEN_CB
GUID-C50B912E-F0EE-4D07-8BB5-3BCCF0706C4F V1 EN
Figure 541:
Circuit breaker control logic: Signal for opening coil of circuit breaker
1
NOT
IN
OUT
AND6
B1
B2
B3
B4
B5
B6
O
NOT
IN
OUT
AND
B1
B2
O
CBXCBR1_ENA_CLOSE
TRPPTRC1_TRIP
DCSXSWI1_OKPOS
ESSXSWI1_OPENPOS
TRPPTRC2_TRIP
CB_SPRING_CHARGED
TCSSCBR_ALARM
GUID-29BE55F8-E969-45D3-A784-E733A8E28552 V2 EN
Figure 542:
Circuit breaker close enable logic
Section 3
1MRS756378 S
REF615 standard configurations
346
REF615
Application Manual