SEQSPVC1
BLOCK
CB_CLOSED
DISCON_OPEN
MINCB_OPEN
FUSEF_3PH
FUSEF_U
X110_BI4_CB_CLOSED
SEQPVC1_FUSEF_U
SEQPVC1_FUSEF_3PH
GUID-DDF6EFE9-7547-4CAD-8158-4A1A568C6B76 V2 EN
Figure 531:
Fuse failure supervision function
Circuit-breaker condition monitoring SSCBR1 supervises the switch status based on
the connected binary input information and the measured current levels. SSCBR1
introduces various supervision methods.
Set the parameters for SSCBR1 properly.
SSCBR1
BLOCK
POSOPEN
POSCLOSE
OPEN_CB_EXE
CLOSE_CB_EXE
PRES_ALM_IN
PRES_LO_IN
SPR_CHR_ST
SPR_CHR
RST_IPOW
RST_CB_WEAR
RST_TRV_T
RST_SPR_T
TRV_T_OP_ALM
TRV_T_CL_ALM
SPR_CHR_ALM
OPR_ALM
OPR_LO
IPOW_ALM
IPOW_LO
CB_LIFE_ALM
MON_ALM
PRES_ALM
PRES_LO
OPENPOS
INVALIDPOS
CLOSEPOS
CB_OPEN_COMMAND
CB_CLOSE_COMMAND
X110_BI3_CB_OPENED
X110_BI4_CB_CLOSED
CB_SPRING_CHARGED
X110_BI2_CB_SPRING_DISCHARGED
SSCBR1_TRV_T_OP_ALM
SSCBR1_TRV_T_CL_ALM
SSCBR1_SPR_CHR_ALM
SSCBR1_OPR_ALM
SSCBR1_OPR_LO
SSCBR1_IPOW_ALM
SSCBR1_IPOW_LO
SSCBR1_CB_LIFE_ALM
SSCBR1_MON_ALM
SSCBR1_PRES_ALM
SSCBR1_PRES_LO
GUID-E3A89E30-4683-4F71-9306-6549552846DE V1 EN
Figure 532:
Circuit-breaker condition monitoring function
OR6
B1
B2
B3
B4
B5
B6
O
OR6
B1
B2
B3
B4
B5
B6
O
OR
B1
B2
O
SSCBR1_TRV_T_OP_ALM
SSCBR1_TRV_T_CL_ALM
SSCBR1_SPR_CHR_ALM
SSCBR1_OPR_ALM
SSCBR1_OPR_LO
SSCBR1_IPOW_ALM
SSCBR1_IPOW_LO
SSCBR1_CB_LIFE_ALM
SSCBR1_MON_ALM
SSCBR1_PRES_ALM
SSCBR1_PRES_LO
SSCBR1_ALARMS
GUID-8DDFC2EE-F3B0-4CB9-9230-FC0D1493C37F V1 EN
Figure 533:
Logic for circuit-breaker monitoring alarm
NOT
IN
OUT
CB_SPRING_CHARGED
X110_BI2_CB_SPRING_DISCHARGED
GUID-90C81E51-8D41-46C0-A945-49469661F78F V1 EN
Figure 534:
Logic for start of circuit-breaker spring charged
Two separate trip circuit supervision functions are included: TCSSCBR1 for power
output X100:PO3 and TCSSCBR2 for power output X100:PO4. The functions are
blocked by the master trip, TRPPTRC1 and TRPPTRC2, and the binary input
X110:BI1 indicating IED plug out.
1MRS756378 S
Section 3
REF615 standard configurations
REF615
343
Application Manual