Table 16:
Default connections for binary inputs
Binary input
Description
X110-BI2
Directional earth-fault protection's basic angle control
X110-BI3
Circuit breaker low gas pressure indication
X110-BI4
Circuit breaker spring charged indication
X110-BI5
Circuit breaker truck in (service position) indication
X110-BI6
Circuit breaker truck out (test position) indication
X110-BI7
Earthing switch closed indication
X110-BI8
Earthing switch open indication
X120-BI1
Blocking of overcurrent instantaneous stage
X120-BI2
Circuit breaker closed indication
X120-BI3
Circuit breaker open indication
Table 17:
Default connections for binary outputs
Binary output
Description
X100-PO1
Close circuit breaker
X100-PO2
Circuit breaker failure protection trip to upstream breaker
X100-PO3
Open circuit breaker/trip coil 1
X100-PO4
Open circuit breaker/trip coil 2
X100-SO1
General start indication
X100-SO2
General operate indication
X110-SO1
Upstream overcurrent blocking
X110-SO2
Overcurrent operate alarm
X110-SO3
Earth-fault operate alarm
X110-HSO1
Arc protection instance 1 operate activated
X110-HSO2
Arc protection instance 2 operate activated
X110-HSO3
Arc protection instance 3 operate activated
Table 18:
Default connections for LEDs
LED
Description
1
Non-directional overcurrent operate
2
Directional/intermittent earth-fault operate
3
Double (cross country) earth-fault or residual overvoltage operate
4
Negative sequence overcurrent or phase discontinuity operate
5
Thermal overload alarm
6
Breaker failure operate
7
Disturbance recorder triggered
8
Circuit breaker condition monitoring alarm
Table continues on next page
1MRS756378 S
Section 3
REF615 standard configurations
REF615
73
Application Manual
Содержание relion REF615
Страница 1: ...Relion 615 series Feeder Protection and Control REF615 Application Manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 398: ...392 ...
Страница 402: ...396 ...
Страница 403: ...397 ...