![ABB relion REF615 Скачать руководство пользователя страница 94](http://html.mh-extra.com/html/abb/relion-ref615/relion-ref615_applications-manual_2824094.webp)
OR
B1
B2
O
OR6
B1
B2
B3
B4
B5
B6
O
OR6
B1
B2
B3
B4
B5
B6
O
SSCBR1_TRV_T_OP_ALM
SSCBR1_TRV_T_CL_ALM
SSCBR1_SPR_CHR_ALM
SSCBR1_OPR_ALM
SSCBR1_OPR_LO
SSCBR1_IPOW_ALM
SSCBR1_IPOW_LO
SSCBR1_CB_LIFE_ALM
SSCBR1_MON_ALM
SSCBR1_PRES_ALM
SSCBR1_PRES_LO
SSCBR1_ALARMS
GUID-ED84A0BD-A150-4BBA-8A82-8AC4B3CAE673 V1 EN
Figure 73:
Logic for circuit breaker monitoring alarm
NOT
IN
OUT
X110_BI4_CB_SPRING_CHARGED
CB_SPRING_DISCHARGED
GUID-7B9FF17E-827E-40A4-B1D2-F13E236D0381 V1 EN
Figure 74:
Logic for start of circuit breaker spring charging
Two separate trip circuit supervision functions are included, TCSSCBR1 for power
output X100:PO3 and TCSSCBR2 for power output X100:PO4. Both the functions
are blocked by the master trip TRPPTRC1 and TRPPTRC2 and the circuit breaker
open signal.
It is assumed that there is no external resistor in the circuit breaker
tripping coil circuit connected in parallel with the circuit breaker
normally open auxiliary contact.