CCBRBRF1
BLOCK
START
POSCLOSE
CB_FAULT
CB_FAULT_AL
TRBU
TRRET
OR6
B1
B2
B3
B4
B5
B6
O
OR6
B1
B2
B3
B4
B5
B6
O
OR6
B1
B2
B3
B4
B5
B6
O
CCBRBRF1_TRBU
X120_BI2_CB_CLOSED
PHIPTOC1_OPERATE
DPHHPDOC1_OPERATE
DPHLPDOC1_OPERATE
EFPADM2_OPERATE
EFPADM3_OPERATE
DEFHPDEF1_OPERATE
DEFLPDEF2_OPERATE
WPWDE2_OPERATE
WPWDE3_OPERATE
ARCSARC1_OPERATE
ARCSARC2_OPERATE
ARCSARC3_OPERATE
CCBRBRF1_TRRET
GUID-3E7F088B-7253-451D-949B-28EF578ED260 V1 EN
Figure 234:
Circuit breaker failure protection function
Three arc protection stages ARCSARC1...3 are included as an optional function. The
arc protection offers individual function blocks for three arc sensors that can be
connected to the IED. Each arc protection function block has two different operation
modes, that is, with or without the phase and residual current check.
The operate signals from ARCSARC1...3 are connected to both trip logic TRPPTRC1
and TRPPTRC2. If the IED has been ordered with high speed binary outputs, the
individual operate signals from ARCSARC1...3 are connected to dedicated trip logic
TRPPTRC3...5. The output of TRPPTRC3...5 are available at high speed outputs
X110:HSO1, X110:HSO2 and X110:HSO3.
1MRS756378 S
Section 3
REF615 standard configurations
REF615
177
Application Manual
Содержание relion REF615
Страница 1: ...Relion 615 series Feeder Protection and Control REF615 Application Manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 398: ...392 ...
Страница 402: ...396 ...
Страница 403: ...397 ...