![ABB relion REF615 Скачать руководство пользователя страница 117](http://html.mh-extra.com/html/abb/relion-ref615/relion-ref615_applications-manual_2824117.webp)
AND
B1
B2
O
AND
B1
B2
O
OR
B1
B2
O
FALSE
FALSE
CBXCBR1_AU_CLOSE
CONTROL_LOCAL
CONTROL_REMOTE
GUID-D25A5AD0-E5BF-476A-B844-9701D5EC44E7 V1 EN
Figure 118:
External closing command for circuit breaker
AND
B1
B2
O
AND
B1
B2
O
OR
B1
B2
O
FALSE
FALSE
CBXBCR1_AU_OPEN
CONTROL_LOCAL
CONTROL_REMOTE
GUID-DEFD10CB-6772-4DE5-952C-887F4E0CCFF2 V1 EN
Figure 119:
External opening command for circuit breaker
3.5.3.5
Functional diagrams for measurement functions
The phase current inputs to the IED are measured by the three-phase current
measurement function CMMXU1. The current input is connected to the X120 card in
the back panel. Similarly, the sequence current measurement CSMSQI1 measures the
sequence current and the residual current measurement RESCMMXU1 measures the
residual current.
The measurements can be seen from the LHMI and they are available under the
measurement option in the menu selection. Based on the settings, function blocks can
generate low alarm or warning and high alarm or warning signals for the measured
current values.
CMMXU1
BLOCK
HIGH_ALARM
HIGH_WARN
LOW_WARN
LOW_ALARM
GUID-91927236-4B19-4AF3-B708-E09EC75FC246 V1 EN
Figure 120:
Current measurement: Three phase current measurement
RESCMMXU1
BLOCK
HIGH_ALARM
HIGH_WARN
GUID-5A0C20F8-9B68-4104-9A45-0AE14A961904 V1 EN
Figure 121:
Current measurement: Residual current measurement
CSMSQI1
GUID-1B8391C6-5AF9-4CC5-A784-6E73487045F3 V1 EN
Figure 122:
Current measurement: Sequence current measurement
1MRS756378 S
Section 3
REF615 standard configurations
REF615
111
Application Manual