NOT
IN
OUT
AND6
B1
B2
B3
B4
B5
B6
O
NOT
IN
OUT
NOT
IN
OUT
TRPPTRC2_TRIP
CBXCBR1_ENA_CLOSE
TRPPTRC1_TRIP
X110_BI3_GAS_PRESSURE_ALARM
DCSXSWI1_OKPOS
ESSXSWI1_OPENPOS
X110_BI4_CB_SPRING_CHARGED
GUID-4BD1BA07-C7A7-4510-BAB9-DBF3BABD1A02 V1 EN
Figure 587:
Circuit breaker close enable logic
The configuration includes the logic for generating circuit breaker external closing
and opening command with the IED in local or remote mode.
Check the logic for the external circuit breaker closing command and
modify it according to the application.
Connect the additional signal for closing and opening of circuit
breaker in local or remote mode if applicable for the configuration.
AND
B1
B2
O
AND
B1
B2
O
OR
B1
B2
O
FALSE
FALSE
CBXCBR1_AU_CLOSE
CONTROL_LOCAL
CONTROL_REMOTE
GUID-065B8F38-D535-4FBF-B2B5-9FB82191614C V1 EN
Figure 588:
External closing command for circuit breaker 1
AND
B1
B2
O
AND
B1
B2
O
OR
B1
B2
O
FALSE
FALSE
CBXBCR1_AU_OPEN
CONTROL_LOCAL
CONTROL_REMOTE
GUID-0978DD77-5996-4E3C-BFCE-E0726ED2BC9A V1 EN
Figure 589:
External opening command for circuit breaker 1
3.14.3.5
Functional diagrams for measurement functions
The phase current inputs to the IED are measured by the three-phase current
measurement function CMMXU1. The current input is connected to the X120 card in
the back panel. The sequence current measurement CSMSQI1 measures the sequence
current and the residual current measurement RESCMMXU1 measures the residual
current.
1MRS756378 S
Section 3
REF615 standard configurations
REF615
371
Application Manual