LED6
OK
ALARM
RESET
LED7
OK
ALARM
RESET
LED8
OK
ALARM
RESET
LED9
OK
ALARM
RESET
LED10
OK
ALARM
RESET
LED11
OK
ALARM
RESET
OR6
B1
B2
B3
B4
B5
B6
O
CCBRBRF1_TRBU
SEQSPVC1_FUSEF_U
SEQSPVC1_FUSEF_3PH
DARREC1_INPRO
SSCBR1_ALARMS
DISTURB_RECORD_TRIGGERED
TCSSCBR_ALARM
CCSPVC1_ALARM
ARCSARC_OPERATE
GUID-80EA7DF8-1DBE-4BFA-9086-E9202A417FB1 V2 EN
Figure 382:
Default LED connection
3.10.3.7
Functional diagrams for other timer logics
The configuration also includes overcurrent operate, earth-fault operate and
combined voltage and frequency operate logic. The operate logics are connected to the
minimum pulse timer TPGAPC for setting the minimum pulse length for the outputs.
The output from TPGAPC is connected to the binary outputs.
TPGAPC2
IN1
IN2
OUT1
OUT2
OR
B1
B2
O
OC_OPERATE_PULSE
EF_OPERATE_PULSE
PHxPTOC_OPERATE
EFxPTOC_OPERATE
ROVPTOV_OPERATE
GUID-FCD29EFB-54DE-459E-94FB-F459C6E94443 V1 EN
Figure 383:
Timer logic for overcurrent and earth-fault operate pulse
1MRS756378 S
Section 3
REF615 standard configurations
REF615
255
Application Manual