LED10
OK
ALARM
RESET
ARCSARC_OPERATE
LED9
OK
ALARM
RESET
TCSSCBR_ALARM
LED7
OK
ALARM
RESET
DISTURB_RECORD_TRIGGERED
LED11
OK
ALARM
RESET
DARREC1_INPRO
LED6
OK
ALARM
RESET
CCBRBRF1_TRBU
GUID-781E66E9-CE48-4DA6-8159-86BED9295D7C V1 EN
Figure 51:
Default LED connection
3.3.3.7
Other functions
The configuration includes few instances of multipurpose protection function
MAPGAPC, runtime counter for machines and devices MDSOPT and different types
of timer functions. These functions are not included in application configuration but
they can be added based on the system requirements.
3.4
Standard configuration B
3.4.1
Applications
The standard configuration for non-directional overcurrent and directional earth-fault
protection is mainly intended for cable and overhead-line feeder applications in
isolated and resonant-earthed distribution networks. The configuration also includes
additional options for selecting earth-fault protection based on admittance, wattmetric
or harmonic-based principles.
The IED with a standard configuration is delivered from the factory with default
settings and parameters. The end user flexibility for incoming, outgoing and internal
1MRS756378 S
Section 3
REF615 standard configurations
REF615
71
Application Manual