NOT
IN
OUT
X110_BI4_CB_SPRING_CHARGED
CB_SPRING_DISCHARGED
GUID-176F56D4-41CA-4646-AAA1-38E65632D403 V1 EN
Figure 250:
Logic for start of circuit breaker spring charging
Two separate trip circuit supervision functions are included: TCSSCBR1 for power
output X100:PO3 and TCSSCBR2 for power output X100:PO4. Both functions are
blocked by the master trip TRPPTRC1 and TRPPTRC2 and the circuit breaker open
signal.
It is assumed that there is no external resistor in the circuit breaker
tripping coil circuit connected in parallel with the circuit breaker
normally open auxiliary contact.
Set the parameters for TCSSCBR1 properly.
TCSSCBR1
BLOCK
ALARM
TCSSCBR2
BLOCK
ALARM
OR
B1
B2
O
TCSSCBR1_ALARM
TCSSCBR1_ALARM
TCSSCBR2_ALARM
TCSSCBR2_ALARM
TCSSCBR_BLOCKING
TCSSCBR_BLOCKING
TCSSCBR_ALARM
GUID-EC7D2528-4B38-4896-897A-7ACB910511A7 V1 EN
Figure 251:
Trip circuit supervision function
1MRS756378 S
Section 3
REF615 standard configurations
REF615
187
Application Manual