Safety functions 91
Step Description
1
The SSE request is received (for example, from the I/O). The FSO starts a counter for
time B.
2
After time E has elapsed, the drive starts to ramp down the motor speed. SAR0
parameter
defines the deceleration ramp.
3
The motor speed goes below the SBC speed limit (A), the FSO activates SBC function.
The FSO starts counters for times C and D.
Note
: You can define an extra delay (parameter
, not shown in the figure) before
the FSO activates the SBC function. This affects also the STO activation (step 4).
3b
If the drive has not ramped down fast enough when time B has elapsed, the FSO
activates the STO function. See section
on page
for more
information on how to configure the STO function.
4
After time C has elapsed, the FSO activates the drive STO function.
5
The SSE request is removed.
6
After time D has elapsed, the safety function is completed, the SSE completed
indication goes on and the acknowledgement becomes allowed as soon as the SSE
request has been removed (step 5).
7
After the acknowledgement, the SSE, STO and SBC functions are deactivated and the
control is given back to the drive, which is allowed to modulate again. The indications
go off.
Содержание FSO-12
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 26: ...26 Introduction to the manual The PROFIsafe certificate for the FSO 12 module is attached below ...
Страница 36: ...36 Safety information and considerations ...
Страница 136: ...136 Safety functions ...
Страница 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 200: ...200 PROFIsafe ...
Страница 326: ...326 Start up ...
Страница 386: ...386 Dimension drawings ...