336 Verification and validation
1. Check the wiring between the FSO module and safe brake, and make sure that
they are done correctly according to the design.
2. Make sure that the SBC function is configured correctly according to your design.
For a configuration example, see chapter
How to configure the SBC in the STO
. Check these settings:
Functionality:
•
•
•
> 0 rpm
•
•
•
•
.
3. Check that the drive STO and the SBC are activated correctly based on your
application needs.
4. Check that the brake is activated at the correct speed.
a) When
is 0 ms or greater, check that the SBC and drive
STO is activated at the same time at the speed limit.
b) When a negative
is used: Check that the SBC is
activated at the speed limit, and the drive STO after the delay has elapsed. This
parameter is only relevant for the SS1 or SSE ramp.
5. Make sure that the required failure reaction (
) takes place if there is no
SBC feedback signal (
). For example, disconnect the SBC feedback
cable to verify.
Содержание FSO-12
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 26: ...26 Introduction to the manual The PROFIsafe certificate for the FSO 12 module is attached below ...
Страница 36: ...36 Safety information and considerations ...
Страница 136: ...136 Safety functions ...
Страница 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 200: ...200 PROFIsafe ...
Страница 326: ...326 Start up ...
Страница 386: ...386 Dimension drawings ...