![ABB FSO-12 Скачать руководство пользователя страница 318](http://html.mh-extra.com/html/abb/fso-12/fso-12_user-manual_2726318.webp)
318 Parameters
Active high
Active state of the output is high voltage.
SAFEIO.76 DO X114:9 logic
state
Sets the logic state of digital output X114:9.
Active low
Active state of the output is low voltage.
Active high
Active state of the output is high voltage.
41
SBUSGEN
General parameters for safety fieldbusses
SBUSGEN.
01
SBUS activity and
version
Activates or deactivates the safety fieldbus.
Disabled
Disabled
Deactivates the safety fieldbus.
Version 1
Activates version 1 of the safety fieldbus.
SBUSGEN.
06
Safety fieldbus
speed scaling
Sets the rpm value that corresponds to
20000 for safety fieldbus communication.
1500.0 rpm
0.10…30000.0
SBUSGEN.10 STO indication
passivation
Sets the type of the event that the FSO
module generates when the FSO module is
passivated
due to safety fieldbus problems.
None
No event generated
Fault
Fault generated
Warning
Warning generated
Event
Pure event generated
41
PROFIsafe
Parameters for PROFIsafe
PROFIsafe.11 PROFIsafe
F_Dest_Add
Sets the PROFIsafe destination address,
that is, the address of the FENA adapter
module in the safety communication
network.
Note
: This address must be the same as is
set in the F-Parameters for the PROFIsafe
module properties (F_Dest_Add). For more
information, see section
on page
.
1
1…65534
PROFIsafe.
12
PROFIsafe telegram
type
Shows the PROFIsafe telegram type.
0x221
PROFIsafe telegram 0x221 (545).
Corresponds to profile ABB_PS1 in the GSD
file. See section
on page
.
Index
Name/Value
Description
Factory
default
Содержание FSO-12
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 26: ...26 Introduction to the manual The PROFIsafe certificate for the FSO 12 module is attached below ...
Страница 36: ...36 Safety information and considerations ...
Страница 136: ...136 Safety functions ...
Страница 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 200: ...200 PROFIsafe ...
Страница 326: ...326 Start up ...
Страница 386: ...386 Dimension drawings ...