Safety functions 115
SLS reaction if modulation is lost with Monitoring active
The operation of the SLS function in case the modulation of the drive is lost during the
deceleration ramp with Monitoring active selected (parameter SLSx.05 is set to
Monitoring active) is described in the time diagram and table below. For configuration,
see section
How to configure SLS function behavior when drive modulation is lost
on
B
Actual motor speed (coasting after modoff)
C
SLS trip limit
D
SLS limit
E
Last valid speed estimate of FSO
SLS indication
Motor speed
Time
1
3
4
2
B
E
STO active
Drive modulation
SLS request
SLSx.04 time
delay monitoring
C
D
STO.14 delay