142 PROFIsafe
Status Byte and CRC2 bit order
PROFIsafe messages sent from the FSO module to the safety PLC include the
F-Input user data, the Status Byte and CRC2.
This table shows the bit order of the Status Byte and CRC2.
N
i
is the length of F-Input user data.
FSO PROFIsafe profiles
The content of the F-Input and F-Output user data is configured with FSO specific
PROFIsafe profiles. The FSO-12 module supports the ABB_PS1 profile.
The ABB_PS1 profile provides the functionality to control and monitor the safety
functions, the SLS limits, the safe speed value and the states of the FSO I/O.
Octet Bit
Name
Description
Status Byte
N
i
7
Reserved
The value is always 0. Must be ignored by the F-Host.
6
cons_nr_R
Vconsnr_d has been reset.
5
Toggle_d
Toggle bit
4
FV_activated
Fail-safe values (FV) activated.
3
WD_timeout
Communication fault: Watchdog timeout
2
CE_CRC
Communication fault: CRC error
1
Device_Fault
Failure exists in the F-Device.
0
iPar_OK
F-Device has new iParameter values assigned.
Not in use. The value is always 0.
CRC2
N
i
+1
7
CRC bit 23
Octet 3 (MSB) of 24 bit CRC
…
0
CRC bit 16
N
i
+2
7
CRC bit 15
Octet 2 of 24 bit CRC
…
0
CRC bit 8
Ni+3
7
CRC bit 7
Octet 1 (LSB) of 24 bit CRC
…
0
CRC bit 0
Содержание FSO-12
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 26: ...26 Introduction to the manual The PROFIsafe certificate for the FSO 12 module is attached below ...
Страница 36: ...36 Safety information and considerations ...
Страница 136: ...136 Safety functions ...
Страница 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 200: ...200 PROFIsafe ...
Страница 326: ...326 Start up ...
Страница 386: ...386 Dimension drawings ...