Technical data 379
1)
Hint: If you use a 1-channel digital output without the diagnostic pulses but you connect a
status indication of the output back to an FSO module input, for example, by using an external
auxiliary contact, you can use the safety data for
1-ch. DO, pulses
in the calculations instead of
the data for
1-ch. DO, no pulses
. (You do not need to include the safety data of the feedback, in
other words the data for the input to which the status indication is connected.)
1-ch. DO,
pulses
2-ch. DO,
pulses
1-ch. DO,
no pulses
1)
2-ch. DO,
no pulses
STO
output
Safe speed
est.
SIL/SILCL
3
3
1
3
3
3
PL
d
e
c
e
e
e
PFH (1/h)
3.1E-09
1.3E-11
6.2E-08
1.4E-11
1.8E-11
6.6E-09
PFD
avg
(T1 =2 a)
3.0E-05
1.7E-07
5.5E-04
1.8E-07
2.5E-07
4.9E-05
PFD
avg
(T1 =5 a)
7.1E-05
3.4E-07
1.4E-03
3.6E-07
4.8E-07
1.2E-04
MTTF
d
(a)
1789
1789
1789
1789
1260
97
HFT
0
1
0
1
1
1
Cat.
2
3
1
3
3
4
SFF (%)
99.20
99.84
84.03
99.82
99.77
99.00
DC (%)
95.13
99.00
0.00
98.93
99.00
99.00
3AXD10000006135.xlsm L
Содержание FSO-12
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 26: ...26 Introduction to the manual The PROFIsafe certificate for the FSO 12 module is attached below ...
Страница 36: ...36 Safety information and considerations ...
Страница 136: ...136 Safety functions ...
Страница 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 200: ...200 PROFIsafe ...
Страница 326: ...326 Start up ...
Страница 386: ...386 Dimension drawings ...