344 Verification and validation
Validation of the variable SLS function
Note:
STO and SSE validation and PROFIsafe interface validation must always be
done before SLS or any other validation tests.
Follow these steps to validate the variable SLS function:
1. Make sure that the input for the variable SLS function is configured in use in the
safety PLC project.
2. Make sure that the variable SLS function is configured in the FSO module
according to your design. For a configuration example, see section
. Check these settings:
Activation:
•
SLS variable activity and version
Functionality for the SLS function
•
•
•
•
Acknowledgement:
•
•
if manual acknowledgement is
used.
Functionality for the deceleration ramp:
a) with ramp monitoring:
•
SLS activation monitoring method
•
•
•
•
•
•
drive parameter
23.23 emergency stop time
, If
= 0 ms.
OR
b) with time monitoring:
•
SLS activation monitoring method
= Time
•
drive parameter
23.13 deceleration time 1
(or
23.15 deceleration time 2
)
•
Indication:
•