Verification and validation 345
3. Check from the safety PLC project that variable SLS scaling is set correctly.
Octet 3 for enabling the scaling:
•
bit 6 negative scaling
•
bit 7 positive scaling
Octets 4 and 5 for the variable SLS speed scaling value.
Test the variable SLS function as used in the application. Pay attention to the testing
of the relevant fault situations for the application, for example the tripping fault in the
drive, etc:
4. Start the drive with suitable speed reference. Activate the variable SLS function
via the safety bus.
5. Make sure that the variable SLS function limits the motor speed to the required
variable SLS limit by the application. Try to give a speed reference higher than the
limit. Make sure that the drive does not follow speed references higher that the
scaled SLS limit.
6. Make sure that
indicates safe speed when motor
speed is within the limits.
7. Scale down the variable SLS limit by various test scaling values.
8. Make sure that the deceleration ramp operates as required and no tripping fault
occurs during the deceleration and that the reference SLS4 limits (100% scaling)
are set according to the application requirements.
9. Make sure that
indicates safe speed when motor
speed is within the scaled variable SLS limits.
10. Deactivate variable SLS function. Make sure that the variable SLS indication goes
off, and the drive runs the motor according to the given user reference.
Note:
If the variable SLS function can be activated at a higher speed than the
variable SLS limit, validate the correct operation as follows:
11. Activate the variable SLS function at a motor speed above the variable SLS limit
(or scale down the variable SLS limit).
12. Activate the coast stop of the drive.
13. Make sure that the FSO module reacts according to your application
requirements, for example, it trips the drive with the STO.
14. Make sure that the following events occur only after the motor is in safe state:
•
SLS indication (
) goes on, if it is configured.
•
Acknowledgement of the stopping function (SSE or STO) is possible in case a
stopping function was triggered earlier. See step
Содержание FSO-12
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 26: ...26 Introduction to the manual The PROFIsafe certificate for the FSO 12 module is attached below ...
Страница 36: ...36 Safety information and considerations ...
Страница 136: ...136 Safety functions ...
Страница 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 200: ...200 PROFIsafe ...
Страница 326: ...326 Start up ...
Страница 386: ...386 Dimension drawings ...