PROFIsafe 145
ABB_PS1 profile F-Input user data
This table shows the bit order of the F-Input user data, which is included in the
PROFIsafe message sent from the FSO module to the safety PLC. For all the bits in
the F-Input data, one (1) means active and zero (0) non-active.
Note
: In the Fail-safe and Configuration states, all the bits in the PROFIsafe message
are set to “0”. In these cases, you can read the FSO state from:
• Siemens PLC: bits QBAD and PASS_OUT in the PROFIsafe data block
• ABB PLC: bit Device_Fault in the PROFIsafe data structure.
See also section
on page
Octet Bit Name
Description
0
0
SLS2_active
SLS2 (Safely-limited speed) is active. Active when the
SLS2 function is active and the motor speed is below the
SLS1 limit (that is, when the SLS2 monitoring is on).
1
SLS1_active
SLS1 (Safely-limited speed) is active. Active when the
SLS1 function is active and the motor speed is below the
SLS1 limit (that is, when the SLS1 monitoring is on).
2
Reserved
*)
The value is 0. Must be ignored by the F-Host.
3
Reserved
*)
The value is 0. Must be ignored by the F-Host.
4
SS1_active
SS1 (Safe stop 1) is function active.
5
SSE_active
SSE (Safe stop emergency) function is active.
6
SBC_active
SBC (Safe brake control) function is active.
7
STO_active
STO (Safe torque off) function is active.
1
0
Reserved
*)
The value is 0. Must be ignored by the F-Host.
1
Reserved
*)
The value is 0. Must be ignored by the F-Host.
2
Reserved
*)
The value is 0. Must be ignored by the F-Host.
3
Reserved
*)
The value is 0. Must be ignored by the F-Host.
4
SAR1_active
SAR1 (Safe acceleration range) is active.
5
SAR0_active
SAR0 (Safe acceleration range) is active.
6
SLS4_active
SLS4 (Safely-limited speed) is active. Active when the
SLS4 function is active and the motor speed is below the
SLS4 limit (that is, when the SLS4 monitoring is on).
7
SLS3_active
SLS3 (Safely-limited speed) is active. Active when the
SLS3 function is active and the motor speed is below the
SLS3 limit (that is, when the SLS3 monitoring is on).
Содержание FSO-12
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 26: ...26 Introduction to the manual The PROFIsafe certificate for the FSO 12 module is attached below ...
Страница 36: ...36 Safety information and considerations ...
Страница 136: ...136 Safety functions ...
Страница 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 200: ...200 PROFIsafe ...
Страница 326: ...326 Start up ...
Страница 386: ...386 Dimension drawings ...