148 PROFIsafe
Note
: The states of all FSO inputs and outputs are shown in the PROFIsafe
message. These states also show the states of SBC outputs and feedback inputs.
FSO module modes and states
When the FSO module is connected to a safety PLC via the PROFIsafe
communications bus, the FSO module can be in the following modes and states:
• Start-up mode
• Configuration mode
• Fail-safe mode
• RUN states:
•
Operational
•
Safe (User acknowledgement request)
•
Safe (Module passivation)
•
Safe (Module passivation & reintegration)
•
Safe (Module passivation with a command).
The FSO module modes and states are described in the following two figures and
tables.
The first figure shows the modes, states and transitions during normal operation. The
second figure shows the modes, states and transitions when fatal errors in the FSO
module occur or when cycling power of the FSO module.
Note
: If PROFIsafe is not configured, see the FSO states described in section
in chapter
.
Note
: If PROFIsafe is configured, the FSO module stays in the Start-up mode until it
has received valid F-Parameters from the safety PLC.
Содержание FSO-12
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 26: ...26 Introduction to the manual The PROFIsafe certificate for the FSO 12 module is attached below ...
Страница 36: ...36 Safety information and considerations ...
Страница 136: ...136 Safety functions ...
Страница 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 200: ...200 PROFIsafe ...
Страница 326: ...326 Start up ...
Страница 386: ...386 Dimension drawings ...