![ABB FSO-12 Скачать руководство пользователя страница 107](http://html.mh-extra.com/html/abb/fso-12/fso-12_user-manual_2726107.webp)
Safety functions 107
SLS reaction if modulation is lost with Monitoring active and modoff delay time
- modulation returns
The operation of the SLS function in case the modulation of the drive is lost during the
deceleration ramp with Monitoring active and modoff delay time selected (parameter
SLSx.05 is set to Monitoring active and modoff delay time) is described in the time
diagram and table below. For configuration, see section
function behavior when drive modulation is lost
on page
A
SAR1 ramp monitoring
B
Actual motor speed (coasting after modoff)
C
SLS trip limit
D
SLS limit
E
Last valid speed estimate of FSO
Motor speed
Time
1
4
3
2
5
Drive modulation
SLS request
SAR1 monitoring
SLSx.06 Modoff
delay time monitoring
C
D
E
A
B
A
SLS indication
Содержание FSO-12
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 26: ...26 Introduction to the manual The PROFIsafe certificate for the FSO 12 module is attached below ...
Страница 36: ...36 Safety information and considerations ...
Страница 136: ...136 Safety functions ...
Страница 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 200: ...200 PROFIsafe ...
Страница 326: ...326 Start up ...
Страница 386: ...386 Dimension drawings ...