80 Communication profiles
6
RAMP_IN_ZERO
1
Normal operation.
Proceed to
OPERATION
.
Note:
This is effective only if the
fieldbus interface is set as the
source for this signal by drive
parameters.
0
Force the Ramp Function
Generator input to zero.
7
RESET
0=>1
A fault is reset if an active fault
exists.
Proceed to
SWITCH-ON
INHIBITED
.
Note:
This is effective only if the
fieldbus interface is set as the
source for this signal by drive
parameters.
0
Continue normal operation.
8…9
Drive-specific
10
REMOTE_CMD
1
Fieldbus control is enabled.
0
Control word and reference not
getting through to the drive,
except for CW bits OFF1, OFF2
and OFF3.
11
EXT_CTRL_LOC
1
Select External Control Location
EXT2.
This is effective if the control
location is parametrized to be
selected from the fieldbus.
0
Select External Control Location
EXT1.
This is effective if the control
location is parametrized to be
selected from fieldbus.
12…
15
Reserved
Bit
Name
Value Description
Содержание FECA-01 EtherCAT
Страница 1: ...Options for ABB drives converters and inverters User s manual FECA 01 EtherCAT adapter module ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 14: ...14 Safety instructions ...
Страница 28: ...28 Mechanical installation ...
Страница 32: ...32 Electrical installation ...
Страница 63: ...Start up 63 ...
Страница 66: ...66 Start up ...
Страница 86: ...86 Communication profiles ...