Start-up 45
Parameter setting examples – ACSM1
The ACSM1 parameters and mandatory parameter settings for the
EtherCAT fieldbus communication with the CiA 402 profile are
listed in the following table.
Note:
All other ACSM1 parameters not mentioned in the table
below are assumed to be at their default values.
Drive parameter
Setting for ACSM1
drives
Description
50.01 FBA ENABLE
Enable
Enables communication
between the drive and the
fieldbus adapter module.
50.04 FBA REF1
MODESEL
Torque
Speed
Position
(Raw data)
Selects the source for fieldbus
actual value 1 (feedback
value).
1)
50.05 FBA REF2
MODESEL
Torque
Speed
Position
(Raw data)
Selects the source for fieldbus
actual value 2 (feedback
value).
1)
50.06 FBA ACT1 TR
SRC
P.1.06 TORQUE
P.1.01 SPEED ACT
P.1.12 POS ACT
Effective only if the FBA REF1
MODESEL parameter has been
set to "Raw data". In that case:
Selects the source for fieldbus
actual value 1.
2)
50.07 FBA ACT2 TR
SRC
P.1.06 TORQUE
P.1.01 SPEED ACT
P.1.12 POS ACT
Effective only if the FBA REF2
MODESEL parameter has been
set to "Raw data". In that case:
Selects the source for fieldbus
actual value 2.
51.02 FBA PAR2
(PROFILE)
0
(= CiA 402)
Selects the CiA 402 profile.
51.27 FBA PAR
REFRESH
REFRESH
Validates the FECA-01
configuration parameter
settings.
10.01 EXT1 START
FUNC
FBA
Selects the fieldbus interface as
the source of the start and stop
commands for external control
location 1.
Содержание FECA-01 EtherCAT
Страница 1: ...Options for ABB drives converters and inverters User s manual FECA 01 EtherCAT adapter module ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 14: ...14 Safety instructions ...
Страница 28: ...28 Mechanical installation ...
Страница 32: ...32 Electrical installation ...
Страница 63: ...Start up 63 ...
Страница 66: ...66 Start up ...
Страница 86: ...86 Communication profiles ...