![ABB FECA-01 EtherCAT Скачать руководство пользователя страница 75](http://html.mh-extra.com/html/abb/feca-01-ethercat/feca-01-ethercat_user-manual_2715075.webp)
Communication profiles 75
The following table describes the functionality of the Status word of
the CiA 402 profile:
Bit
Name
Value
Description
0
Ready to switch on
0
Not ready to switch on
1
Ready to switch on
1
Switched on
0
Not switched on
1
Switched on
2
Operation enabled
0
Operation not enabled
1
Operation enabled
3
Fault
0
No fault
1
Fault
4
Voltage enabled
0
No high voltage applied to the
drive
1
High voltage applied to the drive
5
Quick stop
0
Quick stop is active
1
Normal operation
6
Switch on disabled
0
Switch on enabled
1
Switch on disabled
7
Warning
0
No warning/alarms
1
Warning/Alarm is active
8
Drive-specific
9
Remote
0
Controlword is not processed
1
Controlword is processed
10
Operation mode
specific
See the table describing operation mode
specific bits on page
11
Internal limit active
0
Internal limit not active
1
Internal limit active
12…13
Operation mode
specific
See the table describing operation mode
specific bits on page
14…15
Drive specific
Содержание FECA-01 EtherCAT
Страница 1: ...Options for ABB drives converters and inverters User s manual FECA 01 EtherCAT adapter module ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 14: ...14 Safety instructions ...
Страница 28: ...28 Mechanical installation ...
Страница 32: ...32 Electrical installation ...
Страница 63: ...Start up 63 ...
Страница 66: ...66 Start up ...
Страница 86: ...86 Communication profiles ...